4 Inspection Report
� 425 E.3rd Street
Chilitos Mexican Bar-441E Tower Park DR,BLDG 441 E Tower Park Dr,Waterloo IA
50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
07127/2626 Annual Inspection(lYr) (REINSPECTION , n� 17827-R2
.r�E•r—r
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA N/A
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 0 0 3 0 7
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
08/1712026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-07102/2026 @ 12:17
•$80 annual inspection fee
BRAD BALDWIN-07/02/2026 @ 12:17
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-07/02/2026 @ 12:17
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-07102/2026 @ 12:17
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-07/02/2026 @ 12:17
Withholding re-inspection fee on 7/2126,complete corrections to avoid fees at following inspections.
BRAD BALDWIN-07/27/2026 @ 11:23
$100 re-inspection fee for failure to complete corrections on scheduled 7127126 inspection.Complete corrections to avoid fees at following inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Aurora Torres Date: BRAD BALDWIN 07/27/2026
GENERATED ON 7/27/2e, 11:25 AM 1 OF 6
Reinspection
Status Code Description
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Front exit(exterior door)
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign and lights that failed to
the required load for a duration of not less than 90 minutes. illuminate during test
Additional comments:Failed test today-7127126
Fail 304.3.1-Spontaneous ignition.
OMaterials susceptible to spontaneous ignition,such as oily Location:Kitchen
rags,shall be stored in a listed disposal container.Contents Comments:Provide listed container for disposal of oily rags.See
of such containers shall be removed and disposed of daily. attached
• 0
Fail 603.2-Abatement of unsafe conditions and electrical
CDhazards. Location:North exterior of building
Identified electrical hazards shall be abated.Identified Comments:Licensed electrician shall make necessary repairs to
hazardous electrical conditions in permanent wiring shall be damaged conduit to avoid exposed wiring.Obtain invoice of work
brought to the attention of the responsible code official. completed to provide to inspector.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that Additional comments:Light and wiring has been removed by
constitute an electrical shock or fire hazard shall be abated Henninger Electric,provide contractor's invoice of work completed.
not be used.
a m .r , . i
%
is
{
s
GENERATED ON 7/27/26, 11:25 AM 3 OF 6
Fail 603.6-Extension cords,
Extension cords and flexible cordsshall not be a substitute Location:Outdoor patio
for permanent wiring and shall be listed and labeled in Comments:Per City Electrical Inspector:Remove extension cord
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through plugged to patio"tree"with lights.Licensed electrician shall be
walls,ceilings or floors,or under doors or floor coverings, obtained to inspect proper wiring connections and wiring to the tree
nor shall such cords be subject to environmental damage or and make any necessary repairs,report or repair invoice shall be
physical impact.Extension cords shall be used only with kept and shown to inspector
portable appliances.Extension cords marked for indoor use Additional comments:Discussed having electrical contractor review
shall not be used outdoors, and make necessary repairs with Aurora during phone call(7127126)
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Outdoor patio bar
for permanent wiring and shall be listed and labeled in Comments:Remove brown extension cord in bar
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Northwest dining area
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord plugged to Dos Equis lighted
accordance with UL 817.Extension cords and flexible sign.Flexible wiring also not allowed to extend through drop ceiling
cordsshall not be affixed to structures,extended through in to concealed spaces.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
f
l
'II,Aft A r k tee.
i':
3
,, ,
GENERATED ON 7/27/26, 11:25 AM 4 OF 6
Fail 606.2-Where required.
QA Type I hood shall be installed at or above all commercial Location:Kitchen-Mini fryer
cooking appliances and domestic cooking appliances used Comments:Cooking equipment producing grease laden vapors shall
for commercial purposes that produce grease vapors, be installed under hood exhaust system.Currently mini fryer is
Exceptions:1.Factory-built commercial exhaust hoods that outside of hood coverage.Mini fryer shall also be removed from
are listed and labeled in accordance with UL 710,and plugged to an extension cord.
installed in accordance with Section 304.1 of the International
Mechanical Code,shall not be required to comply with Additional comments:Cords shall be removed
Sections 507.1.5,507.2.3,507.2.5,507.2,8,507.3.1,507.3.3,
507.4 and 507.5 of the International Mechanical Code.
2.Factory-built commercial cooking recirculating systems that
are listed and labeled in accordance with UL 710B,and
installed in accordance with Section 304.1 of the International
Mechanical Code,shall not be required to comply with
Sections 507.1.5,507.2.3,507.2.5,507.2.8,507.3.1,507.3.3,
507.4 and 507.5 of the International Mechanical Code.Spaces
in which such systems are located shall be considered to be
kitchens and shall be ventilated in accordance with Table
403.3.1.1 of the International Mechanical Code.For the
purpose of determining the floor area required to be
ventilated,each individual appliance shall be considered as
occupying not less than 100 square feet(9.3 m2).3.Where
cooking appliances are equipped with integral down-draft
exhaust systems and such appliances and exhaust systems
are listed and labeled for the application in accordance with
NFPA 96,a hood shall not be required at or above them.4.A
Type I hood shall not be required for an electric cooking
appliance where an approved testing agency provides
documentation that the appliance effluent contains 5 mgim3
or less of grease when tested at an exhaust flow rate of 500
cfm(0.236 m31s)in accordance with UL 710B.
GENERATED ON 7/27/26, 11:25 AN 5 OF 6
D Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $100.00
Invoice Number Check Number Transaction Number
N/A NIA NIA
GENERATED ON 7/27/26, 11:25 AM 6 OF 6
F WA?, INVOICE DATE DUE DATE INVOICE# TOTAL DUE
�� Q 07/31/2026 09/04/2026 2027-00000053 $100.00
• o
• .e n 'n wren •
S
Customer#: 21369 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
CHILITO'S 715 Mulberry St
441 E TOWER PARK DR WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION -441 E TOWER PARK DR- FOR BILLING INQUIRY: (319)291-4323
07/27/26
Description Total Price
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
21369 07/31/2026 09/04/2026 2027-00000053 $100.00
Less Prepayment $0.00
Total Due—> $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.