HomeMy WebLinkAboutM&J CARIBBEAN MARKET-928 LA PORTE RD �h-lhl.ny.
Waterloo Fire Rescue
Inspection Report 425 E.3rd Street
M&J Caribbean Market-928 La Porte RD,BLDG 928 La Porte Rd,Waterloo IA 50702
INSPECTION DETAILS
Inspection Date tnspect,on Type Inspection Number
07127/2026 Annual Inspection(1Yr) /4 4. go. 23495
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 38 0 17 ® 24
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 08/24/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-07/27/2026 @ 11:48
•$80 annual inspection fee
BRAD BALDWIN-07/27/2026 @ 11:48
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
SIGNATURES
Contact signature Inspector signature
No signat
Report completeded post
inspection
John Alesse-2025 Date: BRAD BALDWIN 07127/2026
CHECKLISTS
GENERATED ON 7/27/26, 3:33 PM 1 OF 12
Means of Egress
5t tus Code Description
Fail 1010.1.3-Door opening force Forces to unlatch and open
doors. Location:South exit door(Mitchell Ave)side
The force for pushing or pulling open interior swinging Comments:Repair or replace exit door that failed to open.
egress doors,other than fire doors,shall not exceed 5 Replacement of door requires obtaining permit and inspection.
pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
GENERATED ON 7/27/26, 3:33 PM 2 OF 12
Additional Codes
_, tus Code Description
Fail 1018.4-Aisle accessways In Group M.
An aisle accessway shall be provided on not less than one Location:Product shelving aisles
side of each element within the merchandise pad.The Comments:Remove all obstructions to maintain clear aisle widths of
minimum clear width for an aisle accessway not required to 30 inches.Several aisles noted during inspection less than the
be accessible shall be 30 inches(762 mm).The required clear required minimum of 30 inches in width.
width of the aisle accessway shall be measured perpendicular
to the elements and merchandise within the merchandise
pad.The 30-inch(762 mm)minimum clear width shall be
maintained to provide a path to an adjacent aisle or aisle
accessway.The common path of egress travel shall not
exceed 30 feet(9144 mm)from any point in the merchandise
pad.Exception:For areas serving not more than 50
occupants,the common path of egress travel shall not
exceed 75 feet(22 860 mm).
Fail 315.3-Storage in buildings.
Storage of materials in buildings shall be orderly and stacks
shall be stable.Storage of combustible materials shall be
separated from heaters or heating devices by distance or
shielding so that ignition cannot occur.
Fail 603.1.1-Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment, Location:Chest freezer near back storage
wiring,devices and appliances shall be tested;and listed by Comments:Appliances including motors or heat producing elements
an approved agency and labeled;and installed,used and shall plug directly to a permanent outlet.Freezer currently plugged ed to
maintained in accordance with NFPA 70 and all instructions
an extension cord shall be corrected.
included as part of such listing.
Fail 901.4-Installation.Fire protection and life safety systems.
Fire protection systems shall be maintained in accordance Location:Sprinkler system
with the original installation standards for that system. Comments:5 year sprinkler inspection past due as of 1114125.
Required systems shall be extended,altered or augmented as Provide contractors inspection report including any deficiencies
necessary to maintain and continue protection where the corrected to be uploaded to Compliance Engine.
building is altered,remodeled or added to.Alterations to fire
protection systems shall be done in accordance with
applicable standards.Fire protection and life safety systems
shall be installed,repaired,operated and maintained in
accordance with this code and the International Building
Code.
GENERATED ON 7/27/26, 3:33 PM 3 OF 12
General Housekeeping
Status Code Description
Fail 305.1-Clearance from ignition sources.
0 Clearance between ignition sources,such as luminaires, Location:Mechanical room
heaters,flame-producing devices and combustible materials, Comments:Remove all storage within 36 inches of water heater.
shall be maintained in an approved manner, Storage seen in picture attached also blocks access to furnace.
Appliances shall be accessible and clearances maintained from
combustibles at all times.
0 ",.--",...Iiii
Fail 315.3.1-Ceiling clearance.
Storage shall be maintained 2 feet(610 mm)or more below Location:Storage shelving near bathroom
the ceiling in nonsprinklered areas of buildings or not less Comments:Lower all storage within 18 inches below sprinkler head.
than 18 inches(457 mm)below sprinkler head deflectors in Storage along walls that do not interfere with sprinkler head coverage
sprinklered areas of buildings.Exceptions:1.The 2-foot(610 does not apply,
mm)ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings.2.The 18-inch(457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1,903.3.1.2 or
903.3.1.3.
GENERATED ON 7/27/28, 3:33 PM 4 OF 12
Fire Sprinkler System
status Code Descriptlof
Fail 903.3.3-Obstructed locations.
Automatic sprinklers shall be installed with regard to Location:Drink fridge near front exit
obstructions that will delay activation or obstruct the water Comments:Remove storage above fridge to avoid obstructing
distribution pattern and shall be in accordance with the sprinkler head spray pattern.Maintain storage 18"below sprinkler
applicable automatic sprinkler system standard that is being head.
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
/
t {ifa
%! ._ .ems tiara
., -. ',,,. r. loilitr, "
. ,!.....„4.,.... ..46„ . 1 ail
1
.,..,i.. 4. , , ,..,.. _ _ : .. ,,,,--.;
_,J,,, ,.. 1.11;s4t.,__,..111.1.:.:.11 ,;, , :ii, .z.,_".,:,,..,, i
GENERATED ON 7/27/26, 3:33 PM 5 OF 12
Fire Service Features
Status Code Description
Fail 509.2-Equipment access.
0 Approved access shall be provided and maintained for all fire Location:Front wall near exit door
protection system equipment to permit immediate safe Comments:Relocate ice cream freezer to avoid obstructing clear
operation and maintenance of such equipment.Storage,trash path of access to fire alarm pull station.Maintain ready access to pull
and other materials or objects shall not be placed or kept in station at all times.
such a manner that would prevent such equipment from
being readily accessible.
-00
GENERATED ON 7/27/26, 3:33 PM 6 OF 12
Electrical Safety
saws Code Description
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Back storage
equipment shall be provided in accordance with Section comments.Remove storage within 36 inches of electric panel and
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or maintain clear path of access at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
t"
1
a ,, sut •
„, dr 3 GENERATED ON 7/27/26, 3;33 PM 7 OF 12
Fail 603.5.2-Application and usePower supply.
l:l Relocatable power taps and current taps shall be directly Location:Behind register counter
connected to a permanently installed receptacle,Exceptions: Comments:Each power strip shall be plugged directly to a
1.Where approved for use in a Group A occupancy or in a permanent outlet,not allowed to daisy chain(as seen in photo
meeting room in a Group B occupancy,not more than five attached).Power strips shall be properly supported or mounted to
relocatable power taps shall be permitted to be connected avoid hanging by wires and used for low wattage electronics only.
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2,Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
-72
Lori (,
It4i,.
9 r
t �
Fail 603.5.3-Installation.
Relocatable power tap cords shall not extend through walls, Location:Front wall near exit door
ceilings,floors,under doors or floor coverings,or be subject Comments:Power strip shall be properly mounted to wall to avoid
to environmental or physical damage. hanging by wires.Power strips shall be used for low wattage
electronics only.
sx
# h
�Sm
8 OF 12
GENERATED ON 7/27/26, 3:33 PM
Fail 603.5.3-Installation.
`:J Relocatable power tap cords shall not extend through walls, Location:Front wall near exit door
ceilings,floors,under doors or floor coverings,or be subject Comments:Multi plug adapter shall be replaced with power strip with
to environmental or physical damage. manual reset button,properly mounted to avoid hanging by wires
and used for low wattage electronics only.
Y
7
Ati
1 to;.,
\%SI
73-,,,;im'''...... :*4..''''''''':2'.::::::11:e:'(kt'i ,,,,,:71:'''''''''''':77'-7-‘7''o,,
Fail 603.6-Extension cords.
CI) Extension cords and flexible cordsshall not be a substitute Location:Behind register counter and throughout entire space
for permanent wiring and shall be listed and labeled in Comments:Remove all extension cords,they shall not be used as a
accordance with UL 817.Extension cords and flexible substitute for permanent wiring.If adding a new outlet,a licensed
cordsshall not be affixed to structures,extended through electrical contractor shall obtain permit and inspection.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
. ,-it !
'4a 14 .F `.
tom .
.,„,„., k .,.,
it
1*�
' r
►
R
GENERATED ON 7/27/26, 3:33 PM 9 OF 12
Fire Resistant Construction Maintenance
Status Code Description
Fail 704.1-Maintaining protection.
0 Where required when the building was originally constructed, Location:Above product shelving
materials and systems used to protect joints and voids in the Comments:Replace all missing ceiling tiles
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.3oints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.3oints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
10 OF 12
GENERATED ON 7/27/26, 3:33 PM
Portable Fire Extingusihers
Status Code Description
Fail 906.2-General requirements.
O Portable fire extinguishers shall be selected,installed and Location:Back storage
maintained in accordance with this section and NFPA 10. Comments:Provide required annual service to extinguisher,last
Exceptions:1.The distance of travel to reach an extinguisher tagged for service in May 2021.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
t
rah;
Fail 906.7-Hangers and brackets.
Hand-held portable fire extinguishers,not housed in cabinets, Comments:Annually serviced extinguisher shall be properly
shall be installed on the hangers or brackets supplied. mounted on wall bracket from 4"-5'from the floor.Travel distance to
Hangers or brackets shall be securely anchored to the access extinguisher shall not exceed 75 ft.Currently sitting on floor
mounting surface in accordance with the manufacturer's near back storage roomtmechanicai room
installation instructions.
GENERATED ON 7/27/26, 3:33 PM 11 OF 12
re Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 7/27/26, 3;33 PM 12 OF 12
Of W A p INVOICE DATE DUE DATE INVOICE# TOTAL DUE
07/31/2026 09/04/2026 2027-00000055 $80.00
rrirr�•s.
I. y p
Customer#: 24594 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
M&J CARIBBEAN BAR RESTAURANT 715 Mulberry St
926 LA PORTE RD WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 928 LAPORTE RD-07/27/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING',DATE DUE DATE INVOICE# CHARGES
24594 07/31/2026 09/04/2026 2027-00000055 $80.00
Less Prepayment $0.00
Total Due— $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.