COMMERCIAL INSPECTION- 1120 FRANKLIN ST-9-11-23
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE $70.00
$10.00
546
CUSTOMER# BILLING DATE
3423 DUE DATE INVOICE#
09/19/2023 09/26/2023 CHARGES
2024-00000097 $80.00
Less Prepayment $0.00
Total Due—f $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in
late fee applied to any outstanding balance. The delinquent account will be forwar an additional twenty-five percent
America for further collection efforts. Debts shall also be subject to collection through to Municipal Collectionsf of
Administrative Services Offset Program if not paid in full within ninety days. the Iowa Department of
WATERLOO FIRE RESCUE 4,7.00
:z INSPECTION REPORT
FAMILY DOLLAR,1120 FRANKLIN ST,BLDG 1120 FRANKLIN ST,WATERLOO IA S0703
DETAILS
Inspection Date:09/1 1/2023 Inspection Type:Annual Inspection(1 Yr) Inspection Number: 10911 Shift: N/', Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
Printed on 09/12/2023 @ 09:49
Page 1 of 4
PAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
111,111111i-Pf,*k tliiiik- j-_. means of egress.
.a - � - Inspector:JEFF SIEBEL-Comments: Remove obstructions from exit paths.Maintain
'. -- - `" clear paths throughout store.A.Stock items not allowed to be stored in exit paths on
\ ,, , _ carts.Only cart allowed in exit paths are those that are attended and being actively
unloaded. B. Remove obstruction to rear store exit.Maintain a clear 36"pathway and
` \ , ��` 1«'1,- _,` all storage must be stable.
N = Location: Not Provided
4
fir.
, .. ;�s , �
, „J.:4 A r- -- , -
. ^..'
,:,-. '' . igli - -- ‘,.... --- ,
Si
s ;ice
i 4r*'' .'*°° ,
#
4,
-, '• - 'pc, N. -----4,--..,:%,---:,----,,,
Printed on 09/12/2023 @ 09:49
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 5303.5-Security. Compressed gas containers,cylinders,tanks and systems shall be secured against
accidental dislodgement and against access by unauthorized personnel in
accordance with Sections 5303.5.1 through 5303.5.3.
4 £` � �.� Inspector:JEFF SIEBEL-Comments:Properly secure compressed gas cylinders to
stable object with chain.Bungees that are on them will not prevent tip-over
NNW
-howeLocation: By front counter
= 1
- ^p' •
.4p
-_
FAIL 704.1 -Maintaining Where required when the building was originally constructed,materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:replace missing ceiling tile along the back wall.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-09/12/2023 @ 09:25 annual Inspection fee$80.provide corrections to avoid progressive re-inspection fees
beginning at$100
REINSPECTION DATE
10/02/2023
Printed on 09/12/2023 @ 09:49