COMMERCIAL INSPECTION-2830 GERALDINE RD - 8-24-23 FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 50,000 $225.00
OCCUPANCY FEE
$10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
14236 I 09/19/2023
I 09/26/2023 2024-00000100 024 00000100 $235.00
Less Prepayment $0.00
Total Due $235.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
t
•
WATERLOO FIRE RESCUE 4,pCERtoo
INSPECTION REPORTft `,
il
NORTHLAND PRODUCTS CO.,2830 GERALDINE RD,BLDG 2830 GERALDINE RD,WATERLOO IA
507034%0
DETAILS
Inspection Date:08/24/2023 Inspection Type:Annual Inspection(1Yr) ; Inspection Number: 194 Shift: N/A Station: N/A
Unit: N/A ! Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A ! Fee:$235.00
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
;- r �. exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
r _ -E--- Inspector:JEREMIAH VANDYKE-Comments:Cage door needs to be removed or door
locking mechanism of cage door removed.
Agin irr
Location:Trucker door entrance.
"eio I
04kiiS s
_ ■aA Is:' .
r,
.N ..,. a
, ,
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:Outside broken egress light above entry
door.
Location:Outside broken egress light above entry door.
C 1
OCf
N
&
V 1. 1
Printed on 08/24/2023 @ 15:18
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 4006.1 -Hazard identification Unless otherwise exempted by the fire code official,visible hazard identification
signs. signs,as specified in NFPA 704 for the specific material contained,shall be placed on
stationary containers and above-ground tanks;at entrances to locations where
hazardous materials are stored,dispensed,used or handled in quantities requiring a
permit;and at specific entrances and locations designated by the fire code official.
Inspector:JEREMIAH VANDYKE-Comments:Appropriate NFPA 704placards needed
for hazardous material inside building for Fire Fighter safety.
4
Location:All outside entry doors of building.
,.
1
V
1,V
tit
FAIL 506.2-Key box maintenance. The operator of the building shall immediately notify the fire code official and provide
the new key where a lock is changed or rekeyed.The key to such lock shall be secured
in the key box.
Inspector:JEREMIAH VANDYKE-Comments:Fire inspector will check master key in
Knox box to confirm entry on locked doors.
Location:Not Provided
Printed on 08/24/2023 @ 15:18
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 603.4.1 -Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and
legible sign stating"ELECTRICAL ROOM"or similar approved wording.The
disconnecting means for each service,feeder or branch circuit originating on a
switchboard or panelboard shall be legibly and durably marked to indicate its
purpose unless such purpose is clearly evident.Where buildings or structures are
supplied by more than one power source,markings shall be provided at each service
$p �" equipment location and at all interconnected electric power production sources
identifying all electric power sources at the premises in accordance with NFP
A 70.
}
• Inspector:JEREMIAH VANDYKE-Comments:Outside door needs labeling"Electrical
Room".
Location:Outside door of electrical Panel door.
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:JEREMIAH VANDYKE-Comments:Microwaves,toasters,refridgerators,air
s fryers must be plugged directly into wall outlets and not into Power taps/strips.
Location:Office/Break area
4
Printed on 08/24/2023 @ 15:18
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL 903.3.3-Obstructed Automatic sprinklers shall be installed with regard to obstructions that will delay
locations. activation or obstruct the water distribution pattern and shall be in accordance with
the applicable automatic sprinkler system standard that is being used.Automatic
sprinklers shall be installed in or under covered kiosks,displays,booths,concession
-;, stands or equipment that exceeds 4 feet(1219 mm)in width.Not less than a 3-foot
s (914 mm)clearance shall be maintained between automatic sprinklers and the top of
piles of combustible fibers.Exception: Kitchen equipment under exhaust hoods
t- protected with a fire-extinguishing system in accordance with Section 904.
Inspector:JEREMIAH VANDYKE-Comments:Office/break room has no heads
03� installed.Contact Sprinkler contractor to install.
Location:Office/break room has no heads installed.
i
FAIL 903.3.3-Obstructed Automatic sprinklers shall be installed with regard to obstructions that will delay
locations. activation or obstruct the water distribution pattern and shall be in accordance with
the applicable automatic sprinkler system standard that is being used.Automatic
sprinklers shall be installed in or under covered kiosks,displays, booths,concession
�,, stands or equipment that exceeds 4 feet(1219 mm)in width. Not less than a 3-foot
(914 mm)clearance shall be maintained between automatic sprinklers and the top of
piles of combustible fibers.Exception: Kitchen equipment under exhaust hoods
iprotected with a fire-extinguishing system in accordance with Section 904.
---___T__., , , ,
F. Inspector:JEREMIAH VANDYKE-Comments:Need sprinkler head under north garage
door in barrel washing room.Contact Sprinkler contractor to install.
Location:North garage door in barrel washing room.
GENERAL NOTES
JEREMIAH VANDYKE-08/24/2023 @ 14:53 Fire extinguishers serviced by Hawkeye Fire and Safety in July 2023.
JEREMIAH VANDYKE-08/24/2023 @ 15:14 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
Printed on 08/24/2023 @ 15:18
Page 4 of 5
GENERAL NOTES
JEREMIAH VANDYKE-08/24/2023 @ 15:14 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-08/24/2023 @ 15:14 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-08/24/2023 @ 15:17 Inspection Fee=$235.00
JEREMIAH VANDYKE-08/24/2023 @ 15:16 Lt.Van Dyke-jeremiah.vandyke@waterloo-ia.org-319-290-5337
REINSPECTION DATE
09/23/2023
CONTACT SIGNATURE
Bret Mcshane Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE � V
Signed on:08/24/2023 @ 15:17