COMMERCIAL INSPECTION -3550 KIMBALL AVE- 8-23-23 FOR BILLING INQUIRY: (319)291-4323
LDescription
Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE
$10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13263 09/19/2023 09/26/2023 2024-00000104 $80.00
Less Prepayment $0.00
Total Due--* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO
FIRE RESCUE � � �PtERt°
INSPECTION REPORT °
t #I fS NEIGHBORHOOD BAR&GRILL,3550 KIMBALL AVE,BLDG 3550 KIMBALL AVE,WATERLOO
424tio
IA 50701
DETAILS
Inspection Date:08/23/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number:9013 Shift: N/A i Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL ( Other Inspectors: N/A j Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments:remove obstructions to exit door. maintain clear
path at all times.
N
Location:Side exit door by bar
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
$ Inspector:JEFF SIEBEL-Comments:Remove exit light on south side of entry or
remove arrow punch out to direct people to main door.This exit is obstructed.
[ Location:south side of front door.
jf-
Printed on 08/24/2023 @ 10:19
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent falling
compressed gas containers, caused by contact,vibration or seismic activity.Securing of compressed gas
cylinders and tanks. containers,cylinders and tanks shall be by one of the following methods: 1.Securing
containers,cylinders and tanks to a fixed object with one or more restraints.
2.Securing containers,cylinders and tanks on a cart or other mobile device designed
for the movement of compressed gas containers,cylinders or tanks.3. Nesting of
compressed gas containers,cylinders and tanks at container filling or servicing
facilities or in sellers'warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks, if dislodged,do not obstruct
""'""••.-_ the required means of egress.4.Securing of compressed gas containers,cylinders
-----; ,•,. � and tanks to or within a rack,framework,cabinet or similar assembly designed for
such use. Exception:Compressed gas containers,cylinders and tanks in the process
of examination,filling,transport or servicing.
Inspector:JEFF SIEBEL-Comments:secure all compressed gas cylinders with chain to
�;(` wall or stable object(pop rack)
2 /
�- - it Location:behind bar and 3 places in kitchen area
Aim-
mmr
lQ a J'Wiz:.
Printed on 08/24/2023 @ 10:19
Page 2 of 4
STATUS CODE DESCRIPTION
,ry' lw 606.2-Where required. A Type I hood shall be installed at or above all commercial cooking appliances and
domestic cooking appliances used for commercial purposes that produce grease
vapors. Exceptions: 1.Factory-built commercial exhaust hoods that are listed and
labeled in accordance with UL 710,and installed in accordance with Section 304.1 of
\ 410
the International Mechanical Code,shall not be required to comply with Sections
507.1.5,507.2.3,507.2.5,507.2.8,507.3.1,507.3.3,507.4 and 507.5 of the International
t . ' Mechanical Code.2.Factory-built commercial cooking recirculating systems that are
r' listed and labeled in accordance with UL 710B,and installed in accordance withSection 304.1 of the International Mechanical Code,shall not be required to comply
— with Sections 507.1.5,507.2.3,507.2.5,507.2.8,507.3.1,507.3.3,507.4 and 507.5 of the
4 .;a International Mechanical Code.Spaces in which such systems are located shall be
f f•
considered to be kitchens and shall be ventilated in accordance with Table 403.3.1.1
of the International Mechanical Code. For the purpose of determining the floor area
required to be ventilated,each individual appliance shall be considered as occupying
not less than 100 square feet(9.3 m2).3.Where cooking appliances are equipped with
integral down-draft exhaust systems and such appliances and exhaust systems are
listed and labeled for the application in accordance with NFPA 96,a hood shall not be
required at or above them.4.A Type I hood shall not be required for an electric
cooking appliance where an approved testing agency provides documentation that
the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust
flow rate of 500 cfm(0.236 m3/s)in accordance with UL 710B.
Inspector:JEFF SIEBEL-Comments:All appliances must be a minimum of 6"under
kitchen hood exhaust system and properly covered by ansul.
Location:kitchen
FAIL 906.7-Hangers and brackets. Hand-held portable fire extinguishers,not housed in cabinets,shall be installed on
the hangers or brackets supplied. Hangers or brackets shall be securely anchored to
the mounting surface in accordance with the manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:properly mount fire extinguisher 4"to 5'above
the floor in an accessible location.
Location:Currently on floor in front of side exit door.
REINSPECTION DATE
09/13/2023
CONTACT SIGNATURE
John Royer
Signed on:08/24/2023 @ 10:17
Printed on 08/24/2023 @ 10:19
Page 3 of 4
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:08/24/2023 @ 10:17
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 08/24/2023 @ 10:19
Page 4 of 4
INVOICE DATE DUE DATE INVOICE# TOTAL DUE
09/19/2023 09/26/2023 2024-00000103 $80.00
IV 0
�,ttt�r�rr�ri�l ri; e
S 7ti1'��
Customer#: 9511 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
PETERSEN&TIETZ FLORISTS & GREENHOUSES 715 Mulberry St
2275 INDEPENDENCE AV WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION-2275 INDEPENDENCE AVE- 8-29-23 FOR BILLING INQUIRY: (319)291-4323
L Description J Total Price
J
INSPECTION 2,000 $70.00
OCCUPANCY FEE
$10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
9511 09/19/2023 09/26/2023 2024-00000103 $80.00
Less Prepayment $0.00
Total Due—f $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
CO\
WATERLOO FIRE RESCUE •t���ER��O
INSPECTION REPORT
PETERSEN&TIETZ FLORISTS,2275 INDEPENDENCEAVE,BLDG 2275 INDEPENDENCEAVE,
WATERLOO IA 50703
DETAILS
Inspection Date:08/29/2023 ; Inspection Type:Annual Inspection(1Yr) Inspection Number:8639 Shift: N/A I Station: N/A
Unit: N/A ! Lead Inspector:JEFF SIEBEL j Other Inspectors: N/A j Fee:$80.00
VIOLATIONS
No Violations Found
GENERAL NOTES
JEFF SIEBEL-08/30/2023 @ 08:44 annual inspection$80
JEFF SIEBEL-08/30/2023 @ 08:45 extension cord and temporary yard light removed during inspection.
NEXT INSPECTION DATE
08/29/2024
CONTACT SIGNATURE
Jeremy Tietz /
Signed on:08/30/2023 @ 08:46 d�
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:08/30/2023 @ 08:46 $1,11