COMMERCIAL INSPECTION-2034 LA PORTE RD - 8-17-23 FOR BILLING INQUIRY: (319)291-4323
L Description ( Total Price
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12855 09/19/2023 09/26/2023 2024-00000112 $100.00
Less Prepayment $0.00
Total Due— $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
` b
WATERLOO FIRE RESCUE �� ota ,
INSPECTION REPORT t Pt
�t
HAMPTON INN&SUITES,2034 LA PORTE RD,BLDG 2034 LA PORTE RD,WATERLOO IA 50702
DETAILS
Inspection Date:08/17/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number: 10671 j Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 704.1 -Maintaining Where required when the building was originally constructed,materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:Repair all holes created in sheetrock walls and
ceiling to repair frozen fire sprinkler lines WITH proper permits and inspections.
including:A.4th floor electric room by elevator.B.electric room by room 431. D.
repair ceiling in dining area by fire sprinkler repair.Contractor must obtain permits
and inspections for work on fire walls and ceiling.The fire sprinkler head in electrical
room is obstructed by sheetrock and must be braced to avoid going into wall and
install escutcheon.6/6/23 Contractor has not obtained permit.Also fire sprinkler
head not repaired properly and pushed right back into wall and escutcheon slipped
off
Location: Not Provided
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEFF SIEBEL-Comments: Fire doors must completely self-close and latch.
repair the following doors:D.Pool chemical room door(door fell off of frame 4/17/23
Obtain permits and final inspections for fire door installations fire wall/ceiling repair
Location: Not Provided
Printed on 08/21/2023 @ 09:55
Page 1 of 2
STATUS CODE DESCRIPTION
FAIL 903.3.1 -Standards. Sprinkler systems shall be designed and installed in accordance with Section
903.3.1.1,unless otherwise permitted by Sections 903.3.1.2 and 903.3.1.3 and other
chapters of this code,as applicable.
Inspector:JEFF SIEBEL-Comments:Fire sprinkler lines have frozen and broke,and
have been repaired in several areas including electrical rooms on two floors.Provide
PERMANENT HEAT to these rooms to avoid compromising the fire sprinkler system.
repair walls also)The fire sprinkler head in electrical room by room 431 must be
outside of wall and braced.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-07/17/2023 @ 08:27 dryer vent cleaned by Harris Cleaning 2/20/23
JEFF SIEBEL-08/21/2023 @ 09:52 re-inspection fee$100
REINSPECTION DATE
09/20/2023
CONTACT SIGNATURE
Mitch Goodrich-Maintenance C/
Signed on:08/21/2023 @ 09:53
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:08/21/2023 @ 09:53