COMMERCIAL INSPECTION -4550 LA PORTE RD - 8-22-23 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
15249 09/19/2023 09/26/2023 2024-00000113 $100.00
Less Prepayment $0.00
Total Due— $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
,i3u\C\
�p,TER��O
WATERLOO FIRE RESCUE
INSPECTION REPORT
BAMBOO RIDGE,4550 LA PORTE RD,BLDG 4550 LA PORTE ROAD,WATERLOO L4 50702
DETAILS
Inspection Date:08/22/2023 Inspection Type:Annual Inspection(1Yr) ! Inspection Number:9172 j Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL j Other Inspectors: N/A j Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:unable to test emergency lights.provide test and
repair documentation with a signature and date.
Location:Upper women's restroom
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:One lamp on egress light not working.Provide
documentation of repair with signature and date.
Location: Lower Men's restroom by shower
FAIL 507.5.3-Private fire service Private fire service mains and water tanks shall be periodically inspected,tested and
mains and water tanks. maintained in accordance with NFPA 25 at the following intervals: 1.Private fire
hydrants of all types:Inspection annually and after each operation;flow test and
maintenance annually.2.Fire service main piping: Inspection of exposed,annually;
flow test every 5 years.3.Fire service main piping strainers: Inspection and
maintenance after each use.Records of inspections,testing and maintenance shall
be maintained.
Inspector:JEFF SIEBEL-Comments:Provide current annual private fire hydrant
inspection report with all discrepancies corrected.Currently 23 days past due.
Contractor must upload online to the compliance engine.
Location:Not Provided
Printed on 08/24/2023 @ 07:13
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent falling
compressed gas containers, caused by contact,vibration or seismic activity.Securing of compressed gas
cylinders and tanks. containers,cylinders and tanks shall be by one of the following methods: 1.Securing
containers,cylinders and tanks to a fixed object with one or more restraints.
2.Securing containers,cylinders and tanks on a cart or other mobile device designed
for the movement of compressed gas containers,cylinders or tanks.3. Nesting of
compressed gas containers,cylinders and tanks at container filling or servicing
facilities or in sellers'warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks, if dislodged,do not obstruct
the required means of egress.4.Securing of compressed gas containers,cylinders
and tanks to or within a rack,framework,cabinet or similar assembly designed for
such use. Exception:Compressed gas containers,cylinders and tanks in the process
of examination,filling,transport or servicing.
Inspector:JEFF SIEBEL-Comments:secure compressed gas cylinders in back store
room by pop rack with chain.
Location:back mechanical room.
FAIL 606.3.3.3-Records. Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments:Provide current semi-annual kitchen hood
cleaning inspection report for auto-fry.Currently cleaning 910 days past due.Fire
suppression report due 9/21/23.Contractor must upload reports online to the
compliance engine.
Location:kitchen in camp store
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEFF SIEBEL-Comments:provide documentation of dryer vent cleaning to
the outside with signature and date.Report may be emailed to fire inspector.
Location:All commercial and residential clothes dryers in office,shower houses,
maintenance building.
Printed on 08/24/2023 @ 07:13
Page 2 of 3
s • '
STATUS CODE DESCRIPTION
FAIL6109.1 -General. Storage of portable LP-gas containers of 1,000 pounds(454 kg)or less,whether filled,
partially filled or empty,at consumer sites or distribution points,and for resale by
dealers or resellers shall comply with Sections 6109.2 through 6109.15.1.Exceptions:
1.LP-gas containers that have not previously been in LP-gas service.2.LP-gas
containers at distribution plants.3.LP-gas containers at consumer sites or
distribution points,which are connected for use.
Inspector:JEFF SIEBEL-Comments:remove 100#L.P.cylinder from shop.Cylinder
should be stored in outside location in upright position securely stabilized with chain.
Location: Maintenance building
GENERAL NOTES
JEFF SIEBEL-08/24/2023 @ 06:39 annual inspection$100
JEFF SIEBEL-08/24/2023 @ 06:40 obstructions removed from electrical panel during inspection.
REINSPECTION DATE
09/12/2023
CONTACT SIGNATURE
Matt Abben �QQ
Signed on:08/24/2023 @ 07:10
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:08/24/2023 @ 07:11