COMMERCIAL INSPECTION-2060 CROSSROADS - 8-24-23 FOR BILLING INQUIRY: (319)291-4323
L Description ( Total Price J
REINSPECTION 3 $200.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
3989 09/19/2023 09/26/2023 2024-00000094 $200.00
Less Prepayment $0.00
Total Due $200.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE Y� 40ER1.o0
INSPECTION REPORT
CROSSROADS MALL,2060 CROSSROADS BLVD,BLDG 2060 CROSSROADS BLVD,WATERLOO IA
50702
DETAILS
Inspection Date:08/24/2023 Inspection Type:Annual Inspection(1Yr) I Inspection Number: 10618 Shift: N/A I Station: N/A I
Unit: N/A I Lead Inspector:JEREMIAH VANDYKE I Other Inspectors: BROCK WELIVER
STATUS CODE DESCRIPTION
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEREMIAH VANDYKE-Comments:5 year inspection is due.ALL
DEFIECIENCIES NEED TO BE ADDRESSED that were called out by sprinkler contractor
for GORDMANS,YOUNKERS,SEARS,&CROSSROADS MALL.SEARS AUTO garage has
bid out for turning sprinkler heads up. If some of the deficiencies have been repaired
or addressed by the sprinkler contractor they will have to change the deficiencies on
Compliance Engine.Contact the Sprinkler contractor to have the Deficiencies
changed.
Location: Not Provided
FAIL 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction,including,
but not limited to,walls,firestops,shaft enclosures,partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
elements shall be visually inspected by the owner annually and properly repaired,
restored or replaced where damaged,altered, breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
not be required to be visually inspected by the owner unless the concealed space is
accessible by the removal or movement of a panel,access door,ceiling tile or similar
movable entry to the space.Openings made therein for the passage of pipes,
electrical conduit,wires,ducts,air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
and fire.Openings through fire-resistance-rated assemblies shall be protected by
self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector:JEREMIAH VANDYKE-Comments:Missing Ceiling Tiles in tenant and
common spaces: 1.Waterbed store#141.2.Roc fit#113.3.SEARS store both upper
and lower space.4.Pro Nails#215.5.Gordmans.6.Younkers 7.Amish Connection
2602 building.8.Sears Auto garage,ALSO will contact sprinkler company about
turning heads up and pulling down tile/grid system.CURRENTLY being replaced.
Location: Not Provided
GENERAL NOTES
Printed on 08/24/2023 @ 16:54
Page 1 of 3
JEREMIAH VANDYKE-07/07/2023 @ 15:25 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-07/07/2023 @ 15:25 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-08/24/2023 @ 16:53 RE Inspection Fee=$200.00
JEREMIAH VANDYKE-07/07/2023 @ 15:25 Emailed Manager Keri on 5/26/2023 and she states that the corrections for the
sprinkler system been approved by owners and should be having the deficiencies
being corrected.
JEREMIAH VANDYKE-07/07/2023 @ 15:25 Met with Manager Keri on 7/7/2023 and she states that the corrections for the
sprinkler system been approved by owners and should be having the deficiencies
being corrected.
JEREMIAH VANDYKE-08/24/2023 @ 16:53 Emailed Manager Keri,close to getting Black Hawk scheduled when approved.
REINSPECTION DATE
09/23/2023
CONTACT SIGNATURE
Keri Bentley Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE7) J
L.,
Signed on:08/24/2023 @ 16:51 l/// /,,/
Printed on 08/24/2023 @ 16:54