COMMERCIAL FIRE INSPECTION- 6237 DONEGAL CIR- FOR BILLING INQUIRY: (319)291-4323
07/20/2026
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24446 07/24/2026 08/28/2026 2027-00000041 $80.00
Less Prepayment $0.00
Total Due-4 $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
lutInspection Report
425 E.3rd Street
BLDG 6237 Donegal Cir-6025 Donegal CIR,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
07120/2026 Residential Common Areas Inspection aq`T`/6, 4 17719
Lead Inspector Shift
Station Unit
JEREMIAH VANDYKE NIA NIA NIA
Other Inspectors
N/A
SUMMARY OF INSPECTION
011 04 ® 16
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
Reinspection Date
jeremiah.vandyke@waterloo-ia.org 08/21/2026
GENERAL NOTES
JEREMIAH VANDYKE-07/22/2026 @ 09:05
PERMIT INFO:•Any construction,electrical,plumbing,life safety,and HVAC requires proper permit and inspections.•All electrical work and repair must
be completed by a licensed electrical contractor with permits and inspections.
JEREMIAH VANDYKE-07/22/2026 @ 09:06
Re-inspection dates are automatically generated 30 days out from the initial inspection.Normal operating hours for inspections&re-inspections are
Monday-Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on a weekend,the re-inspection will typically be performed
the following Monday or Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier re-inspection."****Re inspection fees
may be assessed for subsequent re-inspections.Re-inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-07/22/2026 @ 09:06
Lt.J.D.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883-1615
JEREMIAH VANDYKE-07/22/2026 @ 09:06
Inspection Fee=$80.00(To be mailed out by City via snail mail.)
SIGNATURES
Contact signature Inspector signature
No signature .//)‘N°
Report completed post inspection
Shane Sage-Tech Director Date: JEREMIAH VANDYKE 07/22/2026
CHECKLISTS
GENERATED ON 7/22/26, 9;12 AM
1 OF 3
Residential Common Areas Inspection
S�atus Code Description
Fail 1104.5-Illumination emergency power.
Where means of egress illumination is provided,the power Location:Egress lighting outside of apartments.
supply for means of egress illumination shall normally be Comments:Have a licensed electrician inspect all exterior emergency
provided by the premises'electrical supply.In the event of egress lighting on the building.Verify that each fixture is operating
power supply failure,illumination shall be automatically properly and complies with applicable requirements.Upon
provided from an emergency system for the following completion of the inspection,provide a written report stating that all
occupancies where such occupancies require two or more exterior emergency egress lights were inspected and are currently
means of egress:1.Group A having 50 or more occupants. operating correctly with no issues identified.
Exception:Assembly occupancies used exclusively as a
place of worship and having an occupant load of less than
300.2.Group B buildings three or more stories in height,
buildings with 100 or more occupants above or below a level
of exit discharge serving the occupants or buildings with
1,000 or more total occupants.3.Group E in interior exit
access and exit stairways and ramps,corridors,windowless
areas with student occupancy,shops and laboratories.
4.Group F having more than 100 occupants.Exception:
Buildings used only during daylight hours and that are
provided with windows for natural light in accordance with
the International Building Code.5.Group I.6.Group M.
Exception:Buildings less than 3,000 square feet(279 m2)in
gross sales area on one story only,excluding mezzanines.
7.Group R-1.Exception:Where each sleeping unit has direct
access to the outside of the building at grade.8.Group R-2.
Exception:Where each dwelling unit or sleeping unit has
direct access to the outside of the building at grade.
Fail 506.2-Key box maintenance.
The operator of the building shall immediately notify the fire Location:Need to update knox box keys.
code official and provide the new key where a lock is changed Comments:Need to update knox box keys.
or rekeyed.The key to such lock shall be secured in the key
box.
Fail 610.1.2-Maintenance.
The lint trap,mechanical and heating components,and the Location:Entire apartment.
exhaust duct system of a clothes dryer shall be maintained in Comments:All Clothes Dryer Exhaust Duct systems must be cleaned
accordance with the manufacturer's operating from the dryer to the outside DOCUMENTED by who and when
instructions to prevent the accumulation of lint or debris that serviced.
prevents the exhaust of air and products of combustion.
Fail 901.6-Inspection,testing and maintenance.
Fire detection and alarm systems,emergency alarm systems, Location:Deficiency Found:Answer:Apartment L has bent deflector
gas detection systems,fire-extinguishing systems, in laundry room
mechanical smoke exhaust systems and smoke and heat Comments:Contact sprinkler contractor to correct and have
vents protection and life safety systems shall be maintained contractor update Compliance engine.
in an operative condition at all times,and shall be replaced or
repaired where defective.Nonrequired fire protection and life
safety systems and equipment shall be inspected,tested and
maintained or removed in accordance with Section 901.8.