COMMERCIAL FIRE INSPECTION- 508 BROADWAY ST- FOR BILLING INQUIRY: (319)291-4323
07/16/2026
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
20748 07/24/2026 08/28/2026 2027-00000047 $80.00
Less Prepayment $0.00
Total Due —+ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
titWaterloo Fire Rescue
': Inspection Report 425 E.3rd Street
Prime Mart#5-508 Broadway ST,BLDG 508 Broadway St,Waterloo IA 50703
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
07/16/2026 Annual Inspection(1Yr) o74, 4,► 00
rf, 17433
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
032 04 Q38
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
0811112026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-07/17/2026 @ 11:27
•$80 annual inspection fee
BRAD BALDWIN-07/17/2026 @ 11:27
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-07117/2026 @ 11:27
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-07/17/2026 @ 11:27
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost ostinspection
Shahid Chatdren Date: BRAD BALDWIN 07117/2026
CHECKLISTS
GENERATED ON 7/17/26, 11:40 AM 1 OF 4
Additional Codes
Status Code Description
Fail 1018.4-Aisle accessways in Group M.
An aisle accessway shall be provided on not less than one Location:Aisles
side of each element within the merchandise pad.The Comments:Clear obstructions to minimum aisle width requirements
minimum clear width for an aisle accessway not required to
be accessible shall be 30 inches(762 mm).The required clear (30inches in width).Maintain clearances at all times.
width of the aisle accessway shall be measured perpendicular
to the elements and merchandise within the merchandise
pad.The 30-inch(762 mm)minimum clear width shall be
maintained to provide a path to an adjacent aisle or aisle
accessway.The common path of egress travel shall not
exceed 30 feet(9144 mm)from any point in the merchandise
pad.Exception:For areas serving not more than 50
occupants,the common path of egress travel shall not
exceed 75 feet(22 860 mm).
General Housekeeping
Status Code Description
Fail 305.1-Clearance from ignition sources,
Clearance between ignition sources,such as luminaires, Location:Furnace
heaters,flame-producing devices and combustible materials, Comments:Remove storage within 36"of appliance.Maintain proper
shall be maintained in an approved manner. clearances at all times.
Electrical Safety
Status Code Description
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Electric panel
equipment shall be provided in accordance with Section Comments:Remove storage within 36"of panel,maintain proper
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or clearances and clear path of access at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
GENERATED ON 7/17/26, 11:40 AM 2 OF 4
Portable Fire Extingusihers
Status Code Description
Fail 906.2-General requirements.
O Portable fire extinguishers shall be selected,installed and Location:All extinguishers
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to extinguishers,last recorded
Exceptions:1.The distance of travel to reach an extinguisher service in September 2024
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 7/17/26, 11:40 AM 3 OF 4