COMMERCIAL FIRE INSPECTION-4550 LAPORTE RD-07/15/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
15249 07/24/2026 08/28/2026 2027-00000029 $100.00
Less Prepayment $0.00
Total Due—* $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue �y �'{
�� Inspection Report 425 E.3rd Street
Bamboo Ridge-4550 La Porte RD,BLDG 4550 La Porte Road,Waterloo IA 50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
07/15/2026 Annual Inspection(1Yr) IC49 .s 4 , 21110
Lead Inspector Shift Stations
Unit
BRAD BALDWIN N/A N/A N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
030 029 ® 36
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
Reinspection Date
BRAD BALDWIN
brad.baldwin@waterloo-ia.org,3192914319
08/11/2026
GENERAL NOTES
BRAD BALDWIN-07/2012026 @ 11:20
•$100 annual inspection fee
BRAD BALDWIN-07120/2026 @ 11:18
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-07/20/2026 @ 11:18
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-07/20/2026 @ 11:18
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
SIGNATURES
Contact signature Inspector signature
No signatureedpost
Report completed post inspection
Matt Abben(2025) Date: BRAD BALDWIN 07/20/2026
CHECKLISTS
GENERATED ON 7/20/26, 11:21 AM
1 OF 10
Means of Egress
Status Code Description
Fail 1032.2-Reliability.
ORequired exit accesses,exits and exit discharges shall be Location:Gas station-Mechanical room
continuously maintained free from obstructions or Comments:REPEAT VIOLATION:Remove obstructions to path of
impediments to full instant use in the case of fire or other egress of exit.Maintain clear path of egress at all times.
emergency where the building area served by the means of
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
1,TT a
w .
it
1
GENERATED ON 7/20/26, 11:21 AM 2 OF 10
Emergency Equipment
Status Code
Description
Fail 1103.9-Carbon monoxide alarmsdetection.
OCarbon monoxide alarms detection shall be installed in Location:Cabins
existing dwelling units and sleeping units Group 1-1,1-2,1-4
Comments:Provide document of testing,including repairs made to
and R occupancies and In classrooms in Group E
maintain working properly of carbon monoxide detectors in each
occupancies where those units include any of the conditions
cabin.Document shall include date&signature,email document to
identified in Sections 915.1.2 through 915.1.6.The carbon
monoxide alarms shall be installed in the locations specified inspector.
in Section 915.2 and the installation shall be in accordance
with Section 915.4.Exceptions:1.Carbon monoxide alarms
are permitted to be solely battery operated where the code
that was in effect at the time of construction did not require
carbon monoxide detectors to be provided.2.Carbon
monoxide alarms are permitted to be solely battery operated
in dwelling units that are not served from a commercial power
source.3.A carbon monoxide detection system in accordance
with Section 915.5 shall be an acceptable alternative to
carbon monoxide alarms.
Fail 1203.2.15-Means of egress illumination.
OEmergency power shall be provided for means of egress Location:Gas station-Near fountain drinks machine
illumination in accordance with Sections 1008.3 and 1104.5.1.
Comments:Repair or replace egress lights that failed to illuminate,
currently blinking red indicator light"Battery"
Fail 1203.2.15-Means of egress illumination,
Emergency power shall be provided for means of egress Location:Gas station-Women's bathroom
illumination in accordance with Sections 1008.3 and 1104.5.1.
Comments:Repair or replace egress lights that failed to illuminate
Fail 1203.2.15-Means of egress illumination.
Ox Emergency power shall be provided for means of egress Location:Gas station-Men's bathroom
illumination in accordance with Sections 1008.3 and 1104.5.1.
Comments:Repair or replace egress lights that failed to illuminate
Fail 1203.2.15-Means of egress illumination.
0 Emergency power shall be provided for means of egress Location:Gas station-Above ATM
illumination in accordance with Sections 1008.3 and 1104.5.1.
Comments:Repair or replace egress lights,currently blinking red
indicator light"Battery"
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Gas station-Front vestibule
illumination in accordance with Sections 1008.3 and 1104.5.1.
Comments:Repair or replace egress lights that failed to illuminate
during test,currently blinking red indicator light"Battery"
Fail 1203.2.15-Means of egress illumination.
Ox Emergency power shall be provided for means of egress Location:Shower house(west)-Men's bathroom
illumination in accordance with Sections 1008.3 and 1104.5.1.
Comments:Repair or replace egress lights near showers that failed
to illuminate during test
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Gas station-Near laundry room
illumination in accordance with Sections 1008.3 and 1104.5.1.
Comments:Repair or replace egress lights that failed to illuminate
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Gas station-Dining area
illumination in accordance with Sections 1008.3 and 1104.5.1.
Comments:Repair or replace egress lights,currently blinking red
indicator light"Battery"
GENERATED ON 7/20/26, 11:21 AM
3 OF 10
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress
Location:Gas station-Kitchen
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights that failed to illuminate
during test near back exit.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress
Location:Shower house(east)-Men's bathroom
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights above sink that failed to
illuminate during test
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Gas station-Near laundry room
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign,currently blinking red
the required load for a duration of not less than 90 minutes. indicator light"Battery"
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Gas station-Front main exit
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign,currently blinking red
the required load for a duration of not less than 90 minutes. indicator light"battery"
4 OF 10
GENERATED ON 7/20/26, 11:21 AM
Additional Codes
Status Code Description
Fail 507.5.3-Private fire service mains and water tanks.
CG Private fire service mains and water tanks shall be Location:Private fire hydrants
periodically inspected,tested and maintained in accordance Comments:Provide contractors inspection and report including any
with NFPA 25 at the following intervals:1.Private fire hydrants
deficiencies corrected to be uploaded to Compliance Engine.of all types:Inspection annually and after each operation;
flow test and maintenance annually.2.Fire service main Inspection due as of 719/26.
piping:Inspection of exposed,annually;flow test every 5
years.3.Fire service main piping strainers:Inspection and
maintenance after each use.Records of inspections,testing
and maintenance shall be maintained.
Fail 610.1.2-Maintenance.
Ox The lint trap,mechanical and heating components,and the Location:Maintenance garage
exhaust duct system of a clothes dryer shall be maintained in Comments:Provide documentation of cleaning of dryer vent from the
accordance with the manufacturer's operating appliance to the exterior of the building with signature and date.
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion. Email documentation to fire inspector.
Fail 610.1.2-Maintenance.
0 The lint trap,mechanical and heating components,and the Location:Gas station-Laundry dryer
exhaust duct system of a clothes dryer shall be maintained in Comments:Provide documentation of cleaning of dryer vent from the
accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that appliance to the exterior of the building with signature and date.
prevents the exhaust of air and products of combustion. Email documentation to fire inspector.
Fail 6104.1-General.
OThe storage and handling of LP-gas and the installation and Location:Gas station-Exterior patio(west)storage room.
maintenance of related equipment shall comply with NFPA 58 Comments:Remove propane tank from storage closet.
and be subject to the approval of the fire code official,except
as provided in this chapter.
Fail 6104.1-General.
QThe storage and handling of LP-gas and the installation and Location:Maintenance garage
maintenance of related equipment shall comply with NFPA 58 Comments:Remove propane tank(see attachment)and(2)grill size
and be subject to the approval of the fire code official,except propane tanks from building.Also,tanks shall be secured to avoid
as provided in this chapter, tip-over hazard.
P r
,
li
0
a t �.
c.
111
ff. ,
it x
GENERATED ON 7/20/26, 11:21 AM 5 OF 10
Fail 6107.3-Clearance to combustibles.
Weeds,grass,brush,trash and other combustible materials Location:Cabins DK 19&20
shall be kept not less than 10 feet(3048 mm)from LP-gas Comments:Remove combustible materials(birds nests)from tanks.
tanks or containers.
f
/
Fail 907.2.8-Group R-1.
Fire alarm systems and smoke alarms shall be installed in Location:Cabins
Group R-1 occupancies as required in Sections 907.2.8.1 Comments:Provide document of testing,including repairs made to
through 9072.8.1 maintain working properly of smoke detectors in each cabin.
Document shall include date&signature,email document to
inspector.
6 OF 10
GENERATED ON 7/20/26, 11:21 AN
Electrical Safety
Status Code
Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Shower house(west)
prohibited.Approved covers shall be provided for all switch
and electrical outlet boxes. Comments:Replace missing exterior outlet cover near bathrooms.
Fail 603.4-Working space and clearancesclearance.
OA working space of not Working space around electrical Location:Gas station-Electric panels
equipment shall be provided in accordance with Section
Comments:Clear storage within t a of electrical equipment.Maintain
110,26 of NFPA 70 for electrical equipment rated 1,000 volts or
less,and Section 110.33 of NFPA 70 for electrical equipment proper clearances of equipment at all times.
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
tvi
l
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Gas station-Laundry room closet
equipment shall be provided in accordance with Section
Comments:Remove storage within 36"of electric panels.Maintain
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less,and Section 110.33 of NFPA 70 for electrical equipment clearances at all times.
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
GENERATED ON 7/20/26, 11:21 AM
7 OF 10
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical
Location:Maintenance garage
equipment shall be provided in accordance with Section Comments:REPEAT VIOLATION:Remove storage within 36"of
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or electric panel,maintain clear path of access at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
1 k
\
\r. '
t
‘ ,
\ , ,
;iT ;`.:
1111111"111A rd.-
8 OF 10
GENERATED ON 7/20/26, 11:21 AM
Fail 603.5.3-Installation.
0 Relocatable power tap cords shall not extend through walls, Location:Gas station-IT closet
ceilings,floors,under doors or floor coverings,or be subject
Comments:Properly mount power strip to avoid being supported by
to environmental or physical damage.
wires.
411
9 /
c fF/jJ
I
I,,
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Gas station-Kitchen
for permanent wiring and shall be listed and labeled in
Comments:Remove large freezer from plugged to extension cord
accordance with UL 817.Extension cords and flexible
and running across walkway.Extension cords shall not be used as
cordsshall not be affixed to structures,extended through
permanent wiring.If needing to add an outlet,licensed electrical
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or contractor shall obtain permit and inspection.
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Maintenance garage-Mechanical room
for permanent wiring and shall be listed and labeled in
Comments:Remove dehumidifier plugged to extension cord,
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through extension cords shall not be used as permanent wiring.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
OExtension cords and flexible cordsshall not be a substitute Location:Gas station-Above beer walk-in cooler
for permanent wiring and shall be listed and labeled in
Comments:Remove green extension cord extending above cooler,
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through extension cords shall not be used as permanent wiring
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.