-for rcial Fire Inspection Report
Inspection Number 1418
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 4025 Hammond Ave
Business name Country Inn and Suites
Inspection Date* 4/24/2018
Proprietor Tai Parkhurst
Business Phone 319-233-2336
Email* tai.parkhurst@countryinns.com
Email 2 brock.weliver@waterloo-ia.org
Property Owner
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation&Location Corrected
703.2.3 Swinging fire doors shall close from the full open position and latch
automatically.
Fire doors near elevator on 3rd floor do not close and latch
2 703.2.3 Swinging fire doors shall close from the full open position and latch
automatically.
Fire doors near elevator on 2nd floor do not close and latch
CODE Violation &Location Corrected
3 605.6 Open junction boxes and open wiring splices shall be prohibited.
Approved covers shall be provided for all switch and outlet boxes.
Open wire splices on mechanical equipment in pool mechanical
room.
4 Egress light out in stairway, near room 329
5 Egress light by room 312, has exposed wire that need to be
concealed in the wall or covered by conduit.
6 Egress light out in stairway on 2nd floor, north side of the building
7 Egress light out by room 202
8 Egress light out by room 222
9 Egress light out in 1st floor exit, south side of the building
10 Egress light out, 1st floor by pool exit
11 Egress light out, pool east well
12 Exit light out by room 129
13 Smoke detector not working in Gym
14 Storage in maids closet by room 203. Storage shall be maintained
2 feet or more below the ceiling in nonsprinklered areas of
buildings or not less than 18 inches below sprinkler head deflectors
in sprinklered areas of buildings
15 Excessive lint build up behind dryers in main laundry area
16 Provide documentation of cleaning of dryer vents to the exterior of
building. Maintenance may be performed by staff, however,
documentation of dates will need to be provided.
17 Repair holes in ceiling drywall in sprinkler room, 3 holes found.
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Discrepancies noted on annual sprinkler inspection, no corrective actions taken,
due for 5 year inspection/test
*Report not accepted 6
Reports Annual Fire Alarm
Comment Last annual fire alarm test was performed in 2014
"Report not accepted
Reports Fire Extinguisher Service
� l
Comment Proshield performed extinguisher maintenance Jan 2018
*Accepted
Inspection Fee $ 90,00
Occupancy Fee $ 10,00
Re-inspection Fee
Total Fee* $ 100.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW.DO NOT PAY FROM THIS FORM.
File Upload(for long
inspections)
Reinspection
Re-inspection# Date Time
5/15/2018