Total Due-- $80.00
City of Waterloo
•
Conn 'iercial Fire Inspection Report
Inspection Number 1411
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 229E 4th St
Business name Locals
Inspection Date* 4/19/2018
Proprietor Yashpal Saini
Business Phone 319-215-5053
Email* yashpalsaini@yahoo.com
Email 2 brock.weliver@waterloo-ia.org
Property Owner
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation&Location Corrected
605.6 Open junction boxes and open wiring splices shall be prohibited.
Approved covers shall be provided for all switch and outlet boxes.
Corrective action, replace/install cover plates on electrical outlets
throughout building, mostly on main floor,and replace/install the
cover plate on the breaker panel in the basement.
Ref# CODE Violation &Location Corrected
2 904.12.5 Portable fire extinguishers for commercial cooking
equipment. Portable fire extinguishers shall be provided within a
30-foot distance of travel from commercial-type cooking equipment.
Cooking equipment involving solid fuels or vegetable or animal oils
and fats shall be protected by a Class K rated portable extinguisher
in accordance with Section 904.12.5.1 or 904.12.5.2, as applicable.
Corrective action, mount Class K fire extinguisher and information
placard in kitchen area
3 906.7 Hangers and brackets. Hand-held portable fire extinguishers,
not housed in cabinets, shall be installed on the hangers or
brackets supplied. Hangers or brackets shall be securely anchored
to the mounting surface in accordance with the manufacturer's
installation instructions.
Corrective action, mount fire extinguishers in building on main floor
and basement
4 304.1 Waste accumulation prohibited. Combustible waste material
creating a fire hazard shall not be allowed to accumulate in
buildings or structures or upon premises.
Corrective action, clean up construction debris through out building
main floor and basement.
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment AKA 4-17-2018
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Superior Fire Protection Equipment 4-18-2018
Reports Knox Box
Comment Box ordered, supposed to be installed on 4-20-2018
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 80.00
Received By
AN
INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection# Date Time
5/10/2018