HomeMy WebLinkAbout310 CONGER ST INVOICE DATE I DUE,DATE INVOICE# TOTAL DUE
/lll\\�ya \�IIf�i.
/� sip iiiprir;. 04/03/2018 05/10/2018 2018-00000254 $80.00
4'11er14;o
Customer#: 12078 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
ELECTRIC PARK BALLROOM 715 Mulberry StWATERLOO, IA 50703
310 CONGER
WATERLOO,IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION -310 W CONGER ST-3-15-18 FOR BILLING INQUIRY: (319)291-4323
[Description I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12078 04/03/2018 05/10/2018 2018-00000254 $80.00
Less Prepayment $0.00
Total Due— $80.00
City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1358
Prior Inspection 281
Number Fill this field if it is available, it will auto-fill business name and address.
Inspector* Jeff Siebel
Waterloo Fire Rescue
715 Mulberry Street Waterloo, A 50703
Phone(319)-230-1224 Fax. (319)-291-4262
Email:Jeff.Siebel@waterloo-la.org
File Upload
Address* 310 W Conger Street
Business name Electric Park
Inspection Date* 3/15/2018
Proprietor Jim Koch
Business Phone 319-415-7361
Email* Jim@nationalcattlecongress.com
Email 2 Karen@nationalcattlecongress.com
•
Property Owner Jim Koch
Emergency Contact Jim Koch
Information
Phone Jim 319-415-7361 Dan 415-6174
Violations
Ref# CODE Violation &Location Corrected
1 NFPA 25 Provide current annual fire sprinkler system inspection/testing
report with all deficiencies corrected by a contractor certified to
perform work in the State of Iowa.
2 904.11.6. Provide current semi-annual kitchen hood fire suppression system
2 inspection/testing with all deficiencies corrected by a contractor
certified to work in the State of Iowa
3 609.3.3.1 Provide current semi-annual kitchen hood exhaust system
cleaning/inspection report with ail deficiencies corrected.
Ref#
CODE Violation&Location Corrected
4 904.11.6. Provide current semi-annual kitchen hood fire suppression system
2 inspection/testing with all deficiencies corrected by a contractor
certified to work in the State of Iowa
5 Replace broken lamp in basement coat check.
6 Replace missing knock out plug in electrical panel in wild animal
area.
7 Immediately remove chains and paddle lock from exit doors on East
end of stage(back stage doors). (see attached pics)Panic
hardware is only device allowed on doors and doors must swing to
full open with less than 15#force
8 Properly secure compressed gas cylinders behind bar with CHAIN.
9 Remove all strings,wires,objects from fire sprinkler lines and
hangers on dance floor and through-out entire building.
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Re ports
Comment
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 80.00
Received By Dan
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long I pad pics 732.JPG 558.34KB
inspections) I pad pics 731.JPG 866.54KB
Reinspection
Re-inspection# Date Time
1 4/5/2018