City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1374
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Chris Ferguson
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)493-1025
Email:chris.ferguson@waterloo-ia.org
File Upload
Address* 515 Lime St
Business name Boys and Girls Club
Inspection Date* 3/29/2018
Proprietor Boys and Girls Club
Business Phone 319-234-2839
Email* bryan@cedarvalleyclubs.org
Email 2
Property Owner
Emergency Contact Bryan Burton
Information
Phone 319-234-2839
Violations
Ref#
CODE Violation &Location Corrected
1 [Staff Breakroom]2015 IFC: Section 605.7 Appliances-Electrical
appliances...shall be maintained in accordance with all instructions
included...Coffee maker was found to be plugged into portable
power tap during inspection. Item was corrected on site during
inspection.
2 [Staff Breakroom]2015 IFC: Section 605.4.2 Power Supply-
Relocatable power taps shall be directly connected to a
permanently installed receptacle. During inspection several power
taps were found to be"daisy chained"together. Corrective action:
All relocatable power taps shall be plugged directly into a wall outlet
and not into another power tap or extension cord.
Ref# CODE Violation&Location Corrected
3 [Staff Breakroom]2015 IFC:Section 605.7 Appliances- Electrical
appliances...shall be maintained in accordance with all instructions
included... Full sized refrigerator was found to be plugged into a
relocatable power tap during inspection. Corrective action:
Refrigerator shall be plugged directly into a permanent wall outlet
not power tap or extension cord.
4 [Staff offices]2015 IFC: Section 605.10.4 Prohibited areas-
Portable, electric space heaters shall not be operated within 3 feet
of any combustible materials. On day of inspection portable space
heater was found with numerous combustible items located within 3
feet of heater. Corrective action: heater was removed by staff on
site.
5 [Teen Center]2015 IFC: Section 605.4.2 Power Supply-
Relocatable power taps shall be directly connected to a
permanently installed receptacle. During inspection several power
taps were found to be"daisy chained"together near television
area. Corrective action:All relocatable power taps shall be plugged
directly into a wall outlet and not into another power tap or
extension cord.
6 [Teen Center]2015 IFC: Section 703.2.3 Door Operation-Swinging
fire doors shall close and latch from the full-open position and latch
automatically. Fire door exiting from teen center to the exit stairway
did not close and latch.Corrective action: provide corrective
repair/replacement to ensure door will close and latch
automatically.
7 [Teen Center]2015 IFC: Section 1010:1.2.1 Direction of swing-
Pivot or side-hinged doors shall swing in the direction of egress
travel where serving a room or area containing an occupant load of
50 or more persons... The double doors leading into the center
swung into the room. Room size was roughly calculated at 36'x36'
using ceiling tiles, placing the occupant load over 50. Corrective
action: Provide corrective repair so that doors will swing in the
direction of egress travel.
8 [IT room off of Teen Center]2015 IFC Section 605.6 Unapproved
conditions-Open junction boxes and open-wiring splices shall be
prohibited. Open-wiring splice was noted involving mechanical
equipment above. Corrective action: ensure open splices are
corrected by a qualified electrician.
9 [Dance Studio]2015 IFC: Section 703.1 Maintenance-Ceiling tiles
were found to be missing from the dance studio. Corrective action:
replace missing ceiling tiles.
10 [Cafeteria]2015 IFC: Section 605.7 Appliances-Electrical
appliances...shall be maintained in accordance with all instructions
included... Electric window air conditioner was found to be plugged
into an extension cord.The manufacturer had stamped onto plug
that it must plugged into permanent outlet. Corrective action:
ensure window air conditioner is plugged directly into permanent
wall outlet.
11 [2nd Floor]2015 IFC: Section 703.1 Maintenance-Several areas
were found to have missing ceiling tiles. Staff stated this was due to
ongoing work on the building's i-NAC system.All ceiling tiles should
be replaced upon the completion of l-NAC work.
Ref#
CODE Violation &Location Corrected
12 [2nd Floor Storage Room]2015 IFC: Section 315.3.1 Ceiling
Clearance-Storage shall be maintained 2 feet or more below the
ceiling in non-sprinklered buildings. Storage was found within 2 feet
of the ceiling on day of inspection. Corrective action:ensure that
the top of storage items is not located within 2 feet of the ceiling.
13 [2nd Floor Storage Room]2015 IFC: Section 703.1 Maintenance-A
large hole was found in the ceiling in the storage room area.
Corrective action: repair hole found in ceiling of storage room.
14 [Exit stairway by front desk]2015 IFC: Section 703.2.3 Door
Operation-Swinging fire doors shall close and latch from the full-
open position and latch automatically. Fire door exiting from the
second floor to the front desk area did not close and latch.
Corrective action: provide corrective repair/replacement to ensure
door will close and latch automatically.
15 2015 IFC: Section 901.6 Inspection,testing, and maintenance- Fire
detection,alarm. and extinguishing system...shall be maintained in
an operative condition at all times. Several fire protection systems
were found to be out of compliance with required testing and
maintenance. Please provide testing and inspection reports for
review during re-inspection of the following items:
a.Annual inspection of fire alarm systems with any deficiencies
corrected
b. Semi-annual hood cleaning and inspection report
c. Semi-annual hood suppression system inspection report
Comments: Please have violations corrected or a plan of correction in placed by the re-
inspection date listed below to avoid any additional re-inspection fees. Feel free to
contact me with any additional questions cr concerns you may have.Thank you for
your time and cooperation.
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200 -Third and subsequent Re-inspections
Reports
Reports Fire Extinguisher Service
Comment Proshield-May of 2017.All extinguishers were found to be tagged current and
gauges were in the green.
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 80.00