Commercial Fire Inspection Report
Inspection Number 1524
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 1119 Kent Cir
Business name Liberty Manor
Inspection Date* 6/7/2018
Proprietor Deb Frost
Business Phone 319-236-5790
Email* dfrost@cardinalcapital.us
Email 2
Property Owner Cardinal Capital Management, Inc
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation &Location Corrected
1 2015 IFC Section 1008 Means of Egress Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times the room or space is
occupied.
*Egress light in south stairs between 2nd and 3rd floors near room
319 was out.
-Corrective action, repair or replace egress light
1 Y
Ref# CODE Violation &Location Corrected
2 2015 IFC Section 315 General Storage
315.3.1 Ceiling clearance. Storage shall be maintained 2 feet or
more below the ceiling in nonsprinklered areas of buildings or not
less than 18 inches below sprinkler head deflectors in sprinklered
areas of buildings.
"Storage in closet by room 219 was found to be near the ceiling.
-Corrective action, lower storage to 2 feet below ceiling
3 Provide documentation of dryer vent/exhaust cleaning to outside of
the building.
*Maintenance personnel may perform this. Document dates,times,
names and signatures of personnel performing cleaning.
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Alarm
Comment Primary Systems 1-1-2018
Reports Fire Extinguisher Service
Comment Proshield, 5-1-2018
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 80.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload(for long
inspections)
Reinspection
Re-inspection# Date Time
6/28/2018