Commercial Fire Inspection Report
Inspection Number 1569
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 1518 Flammang Dr
Business name Barnes&Noble+Starbucks Coffee
Inspection Date* 6/14/2018
Proprietor Steve Olsson
Business Phone 319-232-0475
Email* crm2168@bn.com
Email 2
Property Owner
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation &Location Corrected
1 2015 IFC Section 1013 Exit Sign
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss, the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator.
*Exit light at the front entrance was out when tested
-Corrective action, repair or replace Exit light
Ref# CODE Violation&Location Corrected
•
2 2015 IFC Section 315 General Storage
315.3.1 Ceiling clearance.Storage shall be maintained 2 feet or
more below the ceiling in nonsprinklered areas of buildings or not
less than 18 inches below sprinkler head deflectors in sprinklered
areas of buildings.
*Storage in back office area shelves was up next to the ceiling
-Corrective action, lower storage to 18 inches below sprinkler head
deflectors
3 2015 IFC Section 901 General
901.6 Inspection,testing acid maintenance. Fire detection,alarm,
and extinguishing systems, mechanical smoke exhaust systems,
and smoke and heat vents shall be maintained in an operative
condition at all times,and shall be replaced or repaired where
defective.
*Fire Extinguisher in Starbucks prep/storage area near sink was
found to be out date on inspection tag.
-Corrective action, have extinguisher inspected and brought
current or replace extinguisher with current extinguisher.
4 Follow up with Fire Alarm inspector/tester/contractor about the
deficiencies noted on their inspection form.They had listed that
they were unable to identify 2 duct detector stations during testing.
Provide documentation that they have repaired the problem
5 Please provide current annual inspection/test reports listed below
-Fire Sprinkler annual report
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100,00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Fire Extinguisher Service
Comment Received, Hawkeye Fire&Safety Co, Sept 2017
Reports Annual Fire Alarm
Comment Received, Stanley Security Lic#TSO1238, 13705 26th Ave N, Plymouth, MN
Follow up about deficiencies on report,duct detector
Reports Annual Fire Sprinkler
Comment Please provide current annual report
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee*
S 80.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection# Date Time
7/5/2018