COMMERCIAL INSPECTION- 1825 LA PORTE RD - 6-20-18 FOR BILLING INQUIRY: (319)291-4323
Description I Total Price J
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4899 06/20/2018 07/20/2018 2018-00000416 $100.00
Less Prepayment $0.00
Total Due— $100.00
City of Waterloo
REINSPECTION - Commercial Fire Inspection Form
Inspection Number 1335
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 1825 Laporte Rd
Business Name Super 8
Inspection Date* 6/20/2018
Proprietor Imdar Lutchmansingh
Business Phone 319-229-5574
Email* stay@super8waterloo.com
Email 2
Property Owner
Emergency Contact Imdar Lutcmansingh
Information
Phone 1-847-650-7941
Violations
Ref# Code Violation&Location Corrected
1 2015 IFC General Requirements Section 315 General
Storage
315.3.1 Ceiling clearance.Storage shall be maintained 2
feet or more below the ceiling in nonsprinklered areas of
buildings or not less than 18 inches below sprinkler head
deflectors in sprinklered areas of buildings.
*Corrective action, ensure that all storage is 2 feet below
ceiling in all areas of the building.
*Storage was in violation of the code in the following
areas, closet by 301,storage room by 323,storage room
by 223, closet by room 201,storage by room 123
RefitCode Violation&Location Corrected
2 2015 IFC Building Services and Systems Section 605
Electrical Equipment,Wiring and Hazards
605.3 Working space and clearance.A working space of
not less than 30 inches in width, 36 inches in depth and
78 inches in height shall be provided in front of electrical
service equipment.Where the electrical service
equipment is wider than 30 inches,the working space
shall be not less than the width of the equipment.Storage
of materials shall not be located within the designated
working space.
*Corrective action,maintain working clearance around
electrical panels
*Violations found in Laundry room
3 2015 IFC Building Services and Systems Section 605
Electrical Equipment,Wiring and Hazards
605.4 Multiplug adapters. Multiplug adapters, such as
cube adapters,unfused plug strips or any other device
not complying with NFPA 70 shall be prohibited.
*Corrective action, remove all unapproved multiplug
adapters from building
*Violations were found in room 301
4 2015 IFC Building Services and Systems Section 605
Electrical Equipment,Wiring and Hazards
605.6 Unapproved conditions.Open junction boxes and
open-wiring splices shall be prohibited.Approved covers
shall be provided for all switch and electrical outlet boxes.
*Corrective action, repair or replace coverings on
exposed wiring
*Violations found:exposed wiring in bath fan in room
315,exposed wiring in bath fan in room 216
**Romex cable, improper wiring to TV in front lobby
5 2015 IFC Building Services and Systems Section 605
Electrical Equipment,Wiring and Hazards
605.10.1 Listed and labeled. Only listed and labeled
portable,electric space heaters shall be used
2015 IFC Building Services and Systems Section 605
Electrical Equipment,Wiring and Hazards
605.10.4 Prohibited areas. Portable,electric space
heaters shall not be operated within 3 feet of any
combustible materials. Portable,electric space heaters
shall be operated only in locations for which they are
listed.
*Corrective action, remove all unlisted space heaters
*Violations found: space heater in owners office
Ref# Code Violation &Location Corrected
6 2015 IFC Fire and Smoke Protection Features Section
703 Fire-Resistance-Rated Construction
703.2.3 Door operation.Swinging fire doors shall close
from the full-open position and latch automatically.The
door closer shall exert enough force to close and latch
the door from any partially open position.
*Corrective action, repair ALL doors in the building and
ensure that they are able to function properly. Replace all
missing rated fire doors.
*Violations found: Missing fire door on 2nd floor, repair
all stair access fire doors, repair all room doors to
corridor, room 301,closet by 301, housekeeping by 308,
311,312, 313,315, 317, 319,323, stair door by 323,2nd
floor housekeeping by 208,laundry chute,storage by
223,223,221,217,215,211,210, 209,208,207,206,
203,fire doors by room 101,storage by room 101, 104,
105, 107,fire door by 107,elevator equipment room
door, 113, 116, 117,fire door by 117, 123
**Remove all unapproved hold open devices attached to
doors throughout the building
**Repair/replace smoke seals on doors room 308
7 2015 IFC Fire Protection Systems Section 901 General
901.4 Installation. Fire protection systems shall be
maintained in accordance with the original installation
standards for that system. Required systems shall be
extended,altered or augmented as necessary to maintain
and continue protection where the building is altered,
remodeled or added to.Alterations to fire protection
systems shall be done in accordance with applicable
standards.
*Corrective action, repair or replace holes in
ceilings/walls
*Violations found: bathroom ceiling room 215, closet
ceiling by room 210,ceiling in owners office,walls in
laundry room,ceiling in bathroom of 114
8 2015 IFC Fire Protection Systems Section 901 General
901.6 Inspection,testing and maintenance. Fire
detection,alarm,and extinguishing systems, mechanical
smoke exhaust systems,and smoke and heat vents shall
be maintained in an operative condition at all times,and
shall be replaced or repaired where defective.
Nonrequired fire protection systems and equipment shall
be inspected,tested and maintained or removed.
*Corrective action, repair or replace faulty smoke
detectors,ensure that ALL smoke detectors in the
building are working at ALL times
*Violations found: room 315, 313,312, 311,219,218,
217,215,202,201, 118, 115, 111
Ref# Code Violation &Location Corrected
g 2015 IFC Means of Egress Section 1008 Means of
Egress Illumination
1008.2 Illumination required.The means of egress
serving a room or space shall be illuminated at all times
that the room or space is occupied.
*Corrective action, repair or replace egress lights
*Violations found: by 319,west stairs between 2nd&3rd
floors, by 219,east stairs between 1st&2nd floors
10 2015 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at
all times.To ensure continued illumination for a duration
of not less than 90 minutes in case of primary power loss,
the sign illumination means shall be connected to an
emergency power system provided from storage
batteries, unit equipment or an on-site generator.The
installation of the emergency power system shall be in
accordance with Section 604.
*Corrective action, repair or replace Exit signs
*Violations found: by 301, by 315, by 323,by 223, by
214,
11 Provide current annual inspection/maintenance reports:
*Fire Alarm
*Dryer vent/exhaust cleaning report
**Dryer vent/exhaust cleaning/maintenance should be
done in accordance with manufacturer's
recommendations. Document the date,time, personnel
performing maintenance and signature.
Maintenance/cleaning may be done by hotel personnel.
Comments: Adequate time was given to have these violations corrected.On a previous visit
around June 4th,the property owner asked for another 2 weeks to have all of the
violations fixed/repaired.This time was given. Upon reinspection on June 19th,
violations were still not repaired/fixed. Reinspection fees will now be assessed for
future reinspections.A follow up reinspection will be made July 3 2018.
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports
Comment
Inspection Fee $
Occupancy Fee
Re-inspection Fee S 100.00
Total Fee* S 100.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection Date Time
7/3/2018