Commercial Fire Inspection Report
Inspection Number 1419
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 2141 LaPorte Rd
Business name Motel 6
Inspection Date* 4/25/2018
Proprietor Andy Patel
Business Phone 319-233-9191
Email* m64746bo@6franchise.com
Email 2
Property Owner
Emergency Contact Andy Patel
Information
Phone 319-830-3609
Violations
Ref# CODE Violation&Location Corrected
1 2015 IFC 1013.6.3 Exit signs shall be illuminated at all times.To
ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the illumination means shall
be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator.
*Multiple Egress lights were found to be out when tested
*Corrective action, repair or replace egress lights found to be out
1)Exit light by the main entrance
2)Exit light in the pool room
Ref#
CODE Violation &Location Corrected
2 703.2.3 Swinging fire doors shrill close from the full open position and latch
automatically.
*Multiple doors to rooms were found that do not close and latch at
all. It is recommended that maintenance staff check all the doors on
premises and ensure that they close and latch properly. Upon
reinspection,doors will be check again for proper operation.
*Both sets of fire doors serving the elevators on both floors did not
fully shut as well.
3 2015 IFC 1008.2 Illumination required.The means of egress
serving a room or space shall be illuminated at all times that the
room or space is occupied.
2015 IFC 1008.3.4 Duration.The emergency power system shall
provide power for a duration of not less than 90 minutes and shall
consist of storage batteries, unit equipment or an on-site
generator.
*Multiple egress light were found not to be working
1) Egress light at the front/main door
2)Egress light in the west stairs
3) Egress light by room 223
4)Egress light in east stairs
5) Egress light in guest laundry/vending room
4 2015 IFC 901.4 Fire protection systems shall be maintained in
accordance with the original installation standards for that system.
*Multiple doors to rooms and to the main office were out of
adjustment as to not provide a complete smoke seal when fully
closed.The door to the main office also had an unapproved hold
open device attached to the bottom of the door
5 2015 IFC 901.4.5 Appearance of equipment.Any device that has
the physical appearance of life safety or fire protection equipment
but that does not perform that life safety or fire protection function
shall be prohibited.
Ref#
CODE Violation &Location Corrected
6 2015 IFC 901'.6 Inspection,testing and maintenance. Fire
detection, alarm, and extinguishing systems, mechanical smoke
exhaust systems,and smoke and heat vents shall be maintained in
an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems and
equipment shall be inspected,tested and maintained or removed.
1)The sprinkler system annual check performed by Black Hawk
Sprinkler noted multiple deficiencies that were not repaired.
Including a 5 year test of the system.
2)The sprinkler piping and heads in the pool mechanical room
have excessive corrosion on them.
3)Annual alarm system check is years out of date, need to have a
current inspection.
4) Have the alarm inspection personnel review for the requirements
of strobe notification in the handicap bathrooms in 127 and 128.
5)Smoke detectors are out in rooms 239, 234, 138,ensure all
smoke detectors are in working condition at all times.
6) Fire extinguisher cabinet on 2nd floor is missing the tool to break
the glass in case of emergency.
7)Sprinkler head outside of main office has texture on it, sprinkler
heads are not to be painted or allowed to accumulate dirt/debris.
8) Box for spare sprinkler heads in sprinkler room needs to be
mounted on the wall in the sprinkler room.
9)There is a wire hanging on the sprinkler head in the laundry
shoot
10)Missing escushion for sprinkler head in pool bathroom
7 605.3 Maintain 36" path to and around electrical panels
*Storage around panels in electrical room
8 2015 IFC 605.1 Abatement of electrical hazards. Identified
electrical hazards shall be abated.
*Improper wiring/exposed wires on the exhaust fan in the pool
mechanical room
9 2015 IFC 605.2 Illumination. Illumination shall be provided for
service equipment areas, motor control centers and electrical panel
boards.
*Provide permanent lighting in sprinkler room, a plug in work light is
being used as the light source.
10 605.6 Open junction boxes and open wiring splices shall be prohibited.
Approved covers shall be provided for all switch and outlet boxes.
*Multiple junction box covers are missing on the 1st floor near
rooms 145, 143, 141, 139, 126
*Exposed wiring on light ballasts in the laundry room
11 2015 IFC 509.1 Identification. Fire protection equipment shall be
identified in an approved manner. Rooms containing controls for
air-conditioning systems, sprinkler risers and valves,or other fire
detection,suppression or control elements shall be identified for
the use of the fire department.Approved signs required to identify
the fire protection equipment and equipment location shall be
constructed or durable materials, permanently installed and readily
visible.
*Install a sign marking the sprinkler riser room
Ref#
CODE Violation &Location Corrected
12 2015 IFC 703:1 Maintenance.The required fire-resistance rating of
fire-resistance-rated construction, including, but not limited to,
walls,firestops, shaft enclosures, partitions, smoke barriers,floors,
fire-resistive coatings and sprayed fire-resistant materials applied
to structural members and fire-resistant joint systems, shall be
maintained.
*Wiring from security cameras penetrates a fire-rated wall in the
east stairway. hole needs to be fire caulked.
13 Provide cleaning/maintenance records for dryer vents, both hotel
and guest dryers. Maintenance/cleaning of vents may be
performed by hotel staff,dates/times/names/signatures of
personnel performing cleaning need to be recorded.
14 Celings need to be patched/repaired in sprinkler room and pool
mechanical room. Scuttle hole cover in laundry room,over dryers,
needs to be replaced.
15 Final inspection needs to be called in for the water heater,call the
building department for a plumbing inspection.
16 Door handle on room 134 needs repair, is about to fall apart
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Fire Extinguisher Service
Comment Good, performed by Superior Fire Equipment Feb 2018
Reports Annual Fire Sprinkler
Comment Not accepted, performed by Black Hawk Sprinkler, numerous deficiencies notated
and not fix, 5 year over due
Reports Annual Fire Alarm
Comment Not accepted,out of date, numerous years since last performed
Inspection Fee $ 90.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee' $ 100.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
•File Upload(for long
inspections)
Reinspection
Re-inspection# Date Time
5/16/2018