City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1624
Prior Inspection 493
Number Fill this field if it is available, it will auto-fill business name and address.
Inspector* Jeff Siebel
Waterloo Fire Rescue
715 Mulberry Street Waterloo, IA 50703
Phone(319)-230-1224 Fax. (319)-291-4262
Email:Jeff.Siebel@waterloo-ia.org
File Upload
Address* 1425 San Marnan Drive
Business name Longhorn Steakhouse
Inspection Date* 7/5/2018
Proprietor Tammi
Business Phone 319-235-4336
Email* TBunger@loho.com
Email 2 tammybung159@yahoo.com
Property Owner Josue Carmona
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation&Location Corrected
1 NFPA 25 Provide current annual fire sprinkler system inspection/testing
report with all deficiencies corrected by a contractor certified to
perform work in the State of Iowa.
2 NFPA 72 Provide current annual fire alarm inspection/testing report with all
deficiencies corrected by a contractor certified to perform work in
the State of Iowa.
3 609.3.3.1 Provide current semi-annual kitchen hood exhaust system
cleaning/inspection report with all deficiencies corrected.
Ref# CODE Violation &Location Corrected
4 904.11.6. Provide current semi-annual kitchen hood fire suppression system
2 inspection/testing with all deficiencies corrected by a contractor ,
certified to work in the State of Iowa
5 Repair egress light by table 21
6 Repair egress light by griddle in kitchen
7 Repair egress light sauces
8 Currently the back exit door violates several sub-sections of 2015
IFC section 1010 by obstructing release button, requiring more
than one motion of hand to open door, No signage about delayed
or controlled exit, changed original operation of electromagnetic
locking system, and failure to use listed parts of original installation.
Provide compliance with 2015 IFC section 1010.1.9.9(see
attached) Note:the electronic release shall be contained within
door hardware of the exit door. Employ a qualified contractor with
proper permit and inspections.
9 Remove combustible material from top and sides of enclosure in
exit path.
10 Repair egress light in Fire Sprinkler Riser Room
Comments: On 7/6/18 disconnect cover obstructing release and combustible material on
structure were removed.
Maintain storage a minimum of 18"below fire sprinkler deflector through out
building including office.
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Fire Extinguisher Service
Comment Summit 9/17
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 80.00
Received By Josue Carmona
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long Longhorn 1425 San Marnan 001.JPG 3.1 MB
inspections) Longhorn 1425 San Marnan 002.JPG 3.13MB
Longhorn 1425 San Marnan 004.JPG 2.68MB
Electromagetically locked egress doors Section 1010.1.9.9.pdf 721.07KB
Reinspection
Re-inspection# Date Time
1 7/26/2018