City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1573
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock,Weliver@waterloo-ia.org
File Upload
Address* 610E 4th St
Business name IA Tahf
Inspection Date* 6/15/2018 (R-91("\WP1)
Proprietor Eric Lampe
Business Phone 319-234-1411
Email* iatahfl @yahoo.com
Email 2
Property Owner
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation&Location Corrected
1 2015 IFC Section 1008 Means of Egress Illumination
1008.2 Illumination required.The means of egress illumination
serving a room or space shall be illuminated at all times that the
room or space is occupied.
*Egress lights were found to be out when tested
-Egress light in the South Stairwell between 6th and 7th floor
-Egress light by room 57
#Corrective action, repair or replace egress light
Ref# CODE Violation &Location Corrected
2 2015 IFC Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator.
*Exit light was found to be out when tested
-Exit light on 4th floor by south stairwell
#Corrective action, repair or replace Exit light
3 NFPA 13 Automatic Sprinkler Systems
System components and hardware
6.2.8 Sprinklers subject to mechanical injury shall be protected with
listed guards.
*Sprinkler deflector heads underneath both stairwells are very
close to areas being utilized for storage and may be subject to
damage.
#Corrective action,contact your sprinkler contractor and install
guards over these sprinkler head deflectors
4 Please provide annual reports listed below.These reports may be
emailed to the email address listed above.
*Annual Sprinkler inspection/test
*Annual Fire Alarm inspection/test
*Dryer exhaust cleaning report
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Fire Extinguisher Service
Comment Proshield, Sept 2017
Reports Annual Fire Sprinkler
Comment Please provide current annual report
Reports Annual Fire Alarm
Comment Please provide current annual report
Reports
Comment Dryer exhaust cleaning report.
*Maintenance should be conducted according to manufacturer's recommendations
Exhaust cleaning and maintenance may be performed by on-site maintenance
technicians,document date,time,name and signature of personnel performing the
maintenance.