City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1532
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 3720 Village PI
Business name Friendship Village
Inspection Date* 6/8/2018
Proprietor Chad Wagner
Business Phone 319-231-6735
Email* cwagner@fvrc.com
Email 2
Property Owner
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation&Location Corrected
Ref# CODE Violation &Location Corrected
1 2015 IFC Means of Egress
Section 1010 Doors, Gates and Turnstiles
1010.1.3 Door opening force.The force for pushing or pulling open
interior swinging egress door, other than fire doors, shall not
exceed 5 pounds. These forces do not apply to the force required
to retract latch bolts or disengage other devices that hold the door
in a closed position. For other swinging doors,as well as sliding
and folding doors, the door latch shall released when subjected to
a 15-pound force.The door shall be set in motion when subjected
to a 30-pound force.The door shall swing to a full-open position
when subjected to a 15-pound force.
*Exit door in the Cove stairs, stairwell 5,was difficult to open
-Corrective action, adjust/repair the door so it is easier to open
2 2015 IFC Fire and Smoke Protection Features
Section 703 Fire-Resistance-Rated Construction
703.2.3 Door operation. Swinging fire doors shall close from the
full-open position and latch automatically.The door closer shall
exert enough force to close and latch the door from any partially
open position.
*Door in Stairway 6 did not fully close and latch properly
-Corrective action,adjust/repair door to close and latch properly
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Black Hawk Sprinkler 4-3-2018
Reports Annual Fire Alarm
Comment Hawkeye Alarm 5-2-2018
Reports Fire Extinguisher Service
Comment Superior 10-2017
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Superior 5-2018
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment Harris Cleaning 5-9-2018
Reports Annual Generator Load Test
Comment Staff,weekly
Reports
Comment Fire Drills, monthly
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee
Total Fee* $ 80.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload(for long
inspections)
Reinspection
Re-inspection# Date Time
6/29/2018