Commercial Fire Inspection Report
Inspection Number 1613
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 226 W 5th St
Business name EconoLodge Inn&Suites
Inspection Date* 7/2/2018
Proprietor
Business Phone 319-235-0301
Email* Qualityinnsuites226@gmail.com
Email 2 gm.IA003@choicehotels.com
Property Owner Birchwood Hospitality LLC
Emergency Contact
Information
Phone
Violations
Refs# CODE Violation&Location Corrected
1 2015 IFC General Requirements Section 315 General Storage
315.3.1 Ceiling clearance. Storage shall be maintained 2 feet or
more below the ceiling in nonsprinklered areas of buildings or not
less than 18 inches below sprinkler head deflectors in sprinklered
areas of buildings.
*Please maintain storage according to the description above
*Was unable to access housekeeping closets on inspection,
provide access to closets upon reinspection
Ref# CODE Violation &Location Corrected
2 2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.5 Extension cords. Extension cords and flexible cords shall not
be a substitute for permanent wiring. Extension cords and flexible
cords shall not be affixed to structures, extended through walls,
ceilings or floors, or under doors or floor coverings, nor shall such
cords be subject to environmental damage or physical impact.
Extension cords shall be used only with portable appliances.
*Extension cord with a multiplug adapter was found to be in use in
room 421
*Corrective action, remove all extension cords being used for
permanent wiring in the entire building
3 2015 IFC Building Services and Systems Section 605 Electrical
Equipment, Wiring and Hazards
605.6 Unapproved conditions. Open junction boxes and open-
wiring splices shall be prohibited.Approved covers shall be
provided for all switch and electrical outlet boxes.
*Open junction box was found above room 210 in the main hallway
*Corrective action, replace junction box cover
*There is a security camera wire hanging down by room 215,
repair/replace the camera/wires
4 2015 IFC Fire and Smoke Protection Features Section 703 Fire-
Resistance-Rated Construction
703.2.3 Door operation. Swinging fire doors shall close from the
full-open position and latch automatically.The door closer shall
exert enough force to close and latch the door from any partially
open position.
*Numerous doors to rooms were found to not self close and latch
properly
*Corrective action, ensure that all rated fire doors operate
properly, doors found were, but not limited to, rooms 501, 517,
524, 525,412, 327, 325, 303,229,224, 222, 221
5 2015 IFC Fire Protection Systems Section 901 General
901.4.6 Pump riser room size. Where provided,fire pump and
automatic sprinkler system riser rooms shall be designed with
adequate space for all equipment necessary for the installation, as
defined by the manufacturer,with sufficient working space around
the stationary equipment. Clearances around equipment to
elements of permanent construction, including other installed
equipment and appliances, shall be sufficient to allow inspection,
service, repair or replacement without removing such elements of
permanent construction or disabling the function of a required fire-
resistance-rated assembly. Fire pump and automatic sprinkler
system riser rooms shall be provided with a door(s)and an
unobstructed passageway large enough to allow removal of the
largest piece of equipment.
*Items were being stored in the Sprinkler Riser space
*Corrective action, remove all storage from around Sprinkler Riser
area, ensure that this area is kept clear at all times
Ref# CODE Violation &Location Corrected
6 2015 IFC Fire Protection Systems Section 901 General
901.6 Inspection, testing and maintenance. Fire detection,alarm,
and extinguishing systems, mechanical smoke exhaust systems,
and smoke and heat vents shall be maintained in an operative
condition at all times, and shall be replaced or repaired where
defective. Nonrequired fire protection systems and equipment shall
be inspected,tested and maintained or removed.
*Annual inspections were being performed when the building was
being inspected, please provide current annual report of all
systems
*Numerous Smoke Detectors were found to be out when tested
*Corrective action, repair/replace smoke detectors, ensure that all
Smoke Detectors in the building are working at all times
**Smoke Detectors found to be out when tested are, but not limited
to rooms 515, 516 (LR), 517 both, 521 (LR), 525 both,422 both,
421 both,416(LR),415(LR),412(BR), 303(LR), 312 (LR), 320
(BR), 327 both, 328, 223, 222, 221,212, 203
Hallway smoke by 312
LR=Living Room, BR=Bedroom
7 2015 IFC Fire Protection Systems Section 901 General
901.4 Installation. Fire protection systems shall be maintained in
accordance with the original installation standards for that system.
Required systems shall be extended, altered or augmented as
necessary to maintain and continue protection where the building is
altered, remodeled or added to.Alterations to fire protection
systems shall be done in accordance with applicable standards.
*Rooms were found to be under construction at the time of
inspection, please ensure that all Fire and Life Safety Systems are
being maintained as initially installed
**Rooms include 505, 507, 510, 512, 515, 529,407
*Ceiling tiles are missing from the maintenance storage unit.The
ceiling is part of the Sprinkler System, missing ceiling tiles may
allow smoke and fire to bypass the sprinkler deflector heads and
rendering the sprinkler system ineffective.
**Corrective action, replace missing ceiling tiles
8 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
*Egress lights were found to be out when tested
**Corrective Action, replace/repair egress lights, lights found to be
out are egress light between 4&5 by 528 and egress light
between 2&3 by 305
9 2015 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator. The
installation of the emergency power system shall be in accordance
with Section 604.
*Exit lights were found to be out when tested
**Corrective Action, replace/repair exit lights, lights found to be out
were exit light in stairway between floors 4&5 by room 528, exit
light by room 405,and exit light in stairwell off of main lobby
RefitCODE Violation &Location Corrected
10 2015 IFC Means of Egress Section 1031 Maintenance of the
Means of Egress
1031.2 Reliability. Required exit accesses, exits and exit discharges
shall be continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress
is occupied.An exit or exit passageway shall not be used for any
purpose that interferes with a means of egress.
2015 IFC Means of Egress Section 1031 Maintenance of the
Means of Egress
1031.2 Reliability. Required exit accesses,exits and exit discharges
shall be continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress
is occupied.An exit or exit passageway shall not be used for any
purpose that interferes with a means of egress.
*The marked Exit door in the maintenance storage room was
blocked by storage items.
**Corrective action, keep all marked exits free and clear at all times
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Please provide current annual inspection
Reports Annual Fire Alarm
Comment Please provide current annual inspection
Reports Fire Extinguisher Service
Comment Proshield,July 2018
Accepted
Inspection Fee $ 90.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 100.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
• File'Upload(for long
inspections)
Reinspection
Re-inspection# Date Time
7/24/2018