HomeMy WebLinkAbout1809 LA PORTE RD INVOICE DATE J)UE DATE INVOICE# TOTAL DUE
/lil�
/ 11���, 07/05/2018 08/10/2018 2019-00010011 $100.00
�� .
'NIt's'/i
c?rerTo ‘o
Customer#: 15259 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
DAYS INN& SUITES 715 Mulberry St
1809 LA PORTE RD WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION- 1809 LA PORTE RD- 6-26-18 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price J
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
15259 07/05/2018 08/10/2018 2019-00010011 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
Commercial Fire Inspection Report
inspection Number 1609
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 1809 LaPorte Rd
Business name Days Inn&Suites
Inspection Date* 6/26/2018
Proprietor Dharmendra Patel
Business Phone 319-235-4461
Email* medha601@mchsi.com
Email 2
Property Owner Shri Lambodara
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation&Location Corrected
1 2015 IFC General Requirements Section 315 General Storage
315.3.1 Ceiling clearance. Storage shall be maintained 2 feet or
more below the ceiling in nonsprinklered areas of buildings or not
less than 18 inches below sprinkler head deflectors in sprinklered
areas of buildings.
*Maintain clearances as described above
Ref# CODE Violation &Location Corrected
2 2015 IFC Fire and Smoke Protection Features Section 703 Fire-
Resistance-Rated Construction
703.2.3 Door operation. Swinging fire doors shall close from the
full-open position and latch automatically.The door closer shall
exert enough force to close and latch the door from any partially
open position.
*Fire door by room 147 and another fire door in the 1st floor
corridor area did not shut properly
*Corrective action,adjust doors to operate properly
3 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
*Egress light in the pool room was out when tested
*Corrective action, repair/replace egress light.
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Black Hawk Sprinkler, 11-29-2017
Reports Annual Fire Alarm
Comment Hawkeye Alarm, 11-29-2017
Reports Fire Extinguisher Service
Comment Proshield, 10-2017
Reports
Comment Dryer vents, monthly log kept/checked by staff
Inspection Fee $ 90.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 100.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload(for long
inspections)
Reinspection
Re-inspection# Date Time
7/17/2018