COMMERCIAL INSPECTION-209 E TOWER PARK DR- 7-9-18 FOR BILLING INQUIRY: (319)291-4323
L Description Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
8008 07/10/2018 08/22/2018 2019-00010035 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1639
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 209 E Tower Park Dr
Business name Culvers
Inspection Date* 7/9/2018
Proprietor Austin Wyre
Business Phone 319-291-6640
Email* 61culvers@gmail.com
Email 2
Property Owner DaII Haus LTD
Emergency Contact
Information
Phone
Violations
CODE Violation &Location
Corrected
Ref#
1 2015 IFC General Requirements Section 315 General Storage
315.3.1 Ceiling clearance. Storage shall be maintained 2 feet or
more below the ceiling in nonsprinklered areas of buildings or not
less than 18 inches below sprinkler head deflectors in sprinklered
areas of buildings.
*Storage was found to be stacked up to the ceiling in the office
area and kitchen area
**Corrective action, lower storage
Ref# CODE Violation &Location Corrected
2 2015 IFC Building Services and Systems Section 609 Commercial
Kitchen Hoods
609.3.3.3 Records. Records for inspections shall state the
individual and company performing the inspection, a description of
the inspection and when the inspection took place. Records for
cleaning shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be
completed after each inspection or cleaning and maintained.
*Please provide current reports for both the Hood Cleaning and
Hood Suppression System
3 2015 IFC Fire Protection Systems Section 901 General
901.6 Inspection,testing and maintenance. Fire detection, alarm,
and extinguishing systems, mechanical smoke exhaust systems,
and smoke and heat vents shall be maintained in an operative
condition at all times, and shall be replaced or repaired where
defective. Nonrequired fire protection systems and equipment shall
be inspected,tested and maintained or removed.
*There are 3 Fire Doors in the front dining area that need current
annual inspection/testing
4 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
*Egress light was out when tested, light was in the main dining
area on east side of the building
**Corrective action, repair or replace egress light
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment Please provide current report, report may be emailed to the email address above
Performed by B&B Vent Cleaning 5-2-2018
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Please provide current report, report may be emailed to the email address above
Performed by Superior, March 2018
Reports Fire Extinguisher Service
Comment Superior, March 2018
Inspection Fee S 70.00
Occupancy Fee S 10.00
Re-inspection Fee $
Total Fee* $ 80.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection# Date Time
7/30/2018