COMMERCIAL INSPECTION-3028 ANSBOROUGH AVE- 7-9-18 FOR BILLING INQUIRY: (319)291-4323
Description I Total Price J
INSPECTION 1 $40.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23045 07/24/2018 07/31/2018 2019-00010063 $50.00
Less Prepayment $0.00
Total Due-* $50.00
City of Waterloo
Cbmmercial Fire Inspection Report
Inspection Number 1636
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 3028 Ansborough Ave
Business name Marcos Pizza
Inspection Date* 7/9/2018
Proprietor Patrick Cox
Business Phone 319-234-1366
Email* alexbullington@highlandventuresltd.com
Email 2
Property Owner Family Video Movie Club Inc
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation &Location Corrected
1 2015 IFC Fire Protection Systems Section 901 General
901.6 Inspection,testing and maintenance. Fire detection,alarm,
and extinguishing systems, mechanical smoke exhaust systems,
and smoke and heat vents shall be maintained in an operative
condition at all times, and shall be replaced or repaired where
defective. Nonrequired fire protection systems and equipment shall
be inspected,tested and maintained or removed.
*Please provide copies of current bi-annual inspection and
servicing reports for both hood cleaning and hood suppression
system
**These reports may be emailed to the email address above
R if# CODE Violation &Location Corrected
2 2015 IFC Building Services and Systems Section 609 Commercial
Kitchen Hoods
609.3.3.3.1 Tags.When a commercial kitchen hood or duct system
is inspected,a tag containing the service provider name, address,
telephone number and date of service shall be provided in a
conspicuous location. Prior tags shall be covered or removed.
*Hood cleaning tag was not present on the hood when inspected
3 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
2015 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator.The
installation of the emergency power system shall be in accordance
with Section 604.
*Egress/Exit light was out when tested, Light is located above the
front main door.
**Corrective action, repair or replace the Exit/Egress light
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment please provide current report
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment please provide current report
Inspection Fee $ 40.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 50.00