Commercial Fire Inspection Report
Inspection Number 1650
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 1331 Flammang Dr
Business name Chick-RI-A
Inspection Date* 7/12/2018
Proprietor Chris Bradshaw
Business Phone 319-233-0274
Email* 03679@chick-fil-a.com
Email 2
Property Owner HP Holdings LLC
Emergency Contact
Information
Phone
Violations
Ref#
CODE Violation &Location Corrected
1 2015 IFC Fire Protection Systems Section 904 Alternative
Automatic Fire-Extinguishing Systems
904.12.6.2 Extinguishing system service.Automatic fire-
extinguishing systems shall be serviced at least every six months
and after activation of the system. Inspection shall be by qualified
individuals,and a certificate of inspection shall be forwarded to the
fire code official upon completion.
*Provide current servicing report
Ref#
CODE Violation &Location Corrected
2 2015 IFC Building Services and Systems Section 609 Commercial
Kitchen Hoods
Table 609.3.3.1 Commercial Cooking System Inspection Frequency
Type of Cooking Operations
• High-volume cooking operations such as 24-hour
cooking, charbroiling or wok cooking, Frequency of Inspection 3
months
•Low-volume cooking operations such as places of
religious worship, seasonal businesses and senior centers,
Frequency of Inspection 12 months
•Cooking operations utilizing solid fuel-burning
cooking appliances, Frequency of Inspection 1 month
•All other cooking operations, Frequency of Inspection 6 months
*Cleaning was up to date
3 2015 IFC Fire Protection Systems Section 901 General
901.6 Inspection,testing and maintenance. Fire detection, alarm,
and extinguishing systems, mechanical smoke exhaust systems,
and smoke and heat vents shall be maintained in an operative
condition at all times, and shall be replaced or repaired where
defective. Nonrequired fire protection systems and equipment shall
be inspected,tested and maintained or removed.
*Fire Alarm needs current inspection/service
*Fire Sprinkler needs current inspection/service
*Fire Extinguishers need current inspection/service
*Hood Suppression System needs current inspection/service
4 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
2015 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss, the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator. The
installation of the emergency power system shall be in accordance
with Section 604.
*Combination Egress/Exit light by the main lobby/dinning room
door was out when tested
**Corrective action, repair or replace Egress/Exit light
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Please provide current report, report may be emailed to the email address above
If annual testing, inspection or servicing is due, please arrange to have it
performed
Reports Annual Fie Alarm
Comment Please provide current report, report may be emailed to the email address above
If annual testing, inspection or servicing is due, please arrange to have it
performed
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
Reports Fire Extinguisher Service
Comment Please provide current report, report may be emailed to the email address above
If annual testing, inspection or servicing is due, please arrange to have it
performed
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 80.00