HomeMy WebLinkAbout3658 KIMBALL AVE INVOICE DATE DUE DATE INVOICE# TOTAL DUE
oripâ– \ r.t. 07/24/2018 07/31/2018 2019-00010053 $80.00
Customer#: 5894 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
MCDONALD'S 715 Mulberry St
2016 HOWARD AV WATERLOO, IA 50703
WATERLOO,IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION-3658 KIMBALL AVE- 7-10-18 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
5894 07/24/2018 07/31/2018 2019-00010053 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1647
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 3658 Kimball Ave
Business name McDonalds
Inspection Date* 7/10/2018
Proprietor Michelle Smith
Business Phone 319-234-3517
Email* cindy.young@waterloo-ia.org
Email 2
Property Owner McDonalds Corporation
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation&Location Corrected
1 2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.3 Working space and clearance.A working space of not less
than 30 inches in width,36 inches in depth and 78 inches in height
shall be provided in front of electrical service equipment.Where
the electrical service equipment is wider than 30 inches,the
working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated
working space.
*Combustible waste material was being temporarily stored in front
of electrical panels in the rear of the building
**Corrective action, ensure that this area is kept free of storage
Ref# CODE Violation&Location Corrected
2 2015 IFC Fire Protection Systems Section 901 General
901.6 Inspection,testing and maintenance. Fire detection,alarm,
and extinguishing systems, mechanical smoke exhaust systems,
and smoke and heat vents shall be maintained in an operative
condition at all times,and shall be replaced or repaired where
defective. Nonrequired fire protection systems and equipment shall
be inspected,tested and maintained or removed.
*Escutcheon ring of sprinkler deflector head was found to be loose
in rear hallway area, by electrical panels
**Corrective action, repair/replace escutcheon ring
***Fire Alarm and Fire Sprinkler Systems need current annual
inspection/testing, provide current annual reports
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Please provide current report, report may be emailed to the email address above
**Not current, last performed by Continental 9-19-2014
Reports Annual Fire Alarm
Comment Please provide current report, report may be emailed to the email address above
**Not current, last performed by Hawkeye Alarm 3-21-2015
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment Hoodz,July 2018
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Please provide current report, report may be emailed to the email address above
Due, last performed July 2017
Reports Fire Extinguisher Service
Comment Superior, March 2018
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 80.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection# Date Time
7/31/2018