Commercial Fire Inspection Report
Inspection Number 1663
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 1818 LaPorte Rd
Business name Panera Bread
Inspection Date* 7/23/2018
Proprietor Tanner Everding
Business Phone 319-433-3003
Email* cafe3211@panerabread.com
Email 2
Property Owner
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation &Location Corrected
1 2015 IFC General Requirements Section 315 General Storage
315.3.1 Ceiling clearance. Storage shall be maintained 2 feet or
more below the ceiling in nonsprinklered areas of buildings or not
less than 18 inches below sprinkler head deflectors in sprinklered
areas of buildings.
*Storage was found to be stacked up to the ceiling in the back
service area
**Corrective action, lower storage to heights described above
Ref# CODE Violation&Location Corrected
2 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
*Egress lights were found to be out when tested, lights include:
light in back service area by soda machine, light in back service
area above ice machine, light in rear dinning area by soda machine
**Corrective action, repair or replace egress lights
3 2015 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator.The
installation of the emergency power system shall be in accordance
with Section 604.
*Exit light was found to be out when tested, light by back door in
dinning area
**Corrective action, repair or replace exit light
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment Cody's INC, May 2018
Reports Fire Extinguisher Service
Comment Hawkeye Fire&Safety,Jan 2018
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee S
Total Fee* $ 80.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload(for long
inspections)
Reinspection
Re-inspection# Date Time
8/13/2018