Commercial Fire Inspection Repoli
Inspection Number 1654
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 3821 University Ave
Business name Little Caesars
Inspection Date* 7/16/2018
Proprietor Abby Flockhart
Business Phone
Email* derek-carlson@hotmail.com
Email 2
Property Owner
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation &Location Corrected
Ref# CODE Violation &Location Corrected
1 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
2015 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator.The
installation of the emergency power system shall be in accordance
with Section 604.
*Exit/Egress combination light above the front entrance door was
found to be out when tested
**Corrective action, repair or replace the Exit/Egress combination
light
2 2015 IFC Means of Egress Section 1031 Maintenance of the
Means of Egress
1031.2 Reliability. Required exit accesses, exits and exit discharges
shall be continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress
is occupied.An exit or exit passageway shall not be used for any
purpose that interferes with a means of egress.
*The back door marked as a required EXIT was found to be
blocked when opened.There was a piece of metal that would not
allow the door to be opened fully.
**Corrective action, remove any and all obstructions from allowing
the door to open fully.
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment AKA, Feb 2018
Reports Fire Extinguisher Service
Comment Superior,June 2018
Inspection Fee $ 40.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 50.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload(for long
inspections)
Reinspection
Re-inspection# Date Time
8/6/2018