HomeMy WebLinkAbout1334 FLAMMANG INVOICE DATE , DUE DATE INVOICE# TOTAL DUE
fl1 II�.
+ 1iiN -41r�; 08/20/2018 09/30/2018 2019-00010104 $610.00
°i'erloo •o
Customer#: 4747 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
WALMART 715 Mulberry St
1334 FLAMMANG DR WATERLOO, IA 50703
WATERLOO,IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION- 1334 FLAMMANG- 8-15-18 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price J
INSPECTION 100,000 $600.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4747 08/20/2018 09/30/2018 2019-00010104 $610.00
Less Prepayment $0.00
Total Due $610.00
City of Waterloo
Commercial Fire Inspection Report
}
Inspection Number 1720
Prior Inspection 527
Number Fill this field if it is available, it will auto-fill business name and address,
Inspector* Jeff Siebel
Waterloo Fire Rescue
715 Mulberry Street Waterloo, IA 50703
Phone(319)-230-1224 Fax. (319)-291-4262
Email:Jeff.Siebel@waterloo-ia.org
File Upload
Address* 1334 Flammang Dr.
Business name Walmart#1496
Inspection Date* 8/15/2018
Proprietor Ryan Rand
Business Phone 319-232-3661
Email* BFjacob.S01496.US@wal-mart.com
Email 2
Property Owner Walmart Corp
Emergency Contact Bren Jacobs
Information
Phone Ryan 319-610-6232/Bren 319-563-568-
8230
Violations
Ref# CODE Violation &Location Corrected
1 NFPA 25 Perform annual tests of private fire hydrants.The test is to be in
7.3.2 compliance with NFPA 25 7.3.2. The test will include dry barrel test,
hydrants to be fully opened and water flowed to clear, confirm
proper drainage, properly lubricate caps,general inspection.
2 NFPA 72 Provide immediate correction for Fire Alarm Trouble signal for
phone line.
Provide documentation,
3 609.3.3.1 Provide current semi-annual kitchen hood exhaust system
cleaning/inspection report with all deficiencies corrected.
For Fryer and Rotisserie
Ref# CODE Violation &Location Corrected
4 Reduce storage to a minimum of 18"below fire sprinkler deflector
5 . Replace missing fire sprinkler escutcheon and remove ice from
fire sprinkler head in ice cream freezer.
6 Remove extension cord powering new meat cooler door. Install
permanent power with permits and inspections.
7 Replace missing ceiling tiles in bakery area
8 Mount a currently serviced 2A-10BC fire extinguisher 4"to 5'above
the floor in an accessible location in Deli backroom.
9 Remove extension cord to TV in grocery entrance. Install
permanent approved restrained power supply.
10 .Provide documentation of corrections for 3 deficiencies on
emergency egress and exit light test.
11
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Viking Auto Fire Sprinkler 5/24/18 Jeff Erickson Sprinkler Installer lic FES 0444
Reports Annual Fire Alarm
Comment Walmart Security Technology 5/3/18 Iowa lic AL 599
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment Bakery 5/11/18 Commercial Cleaning
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Hawkeye fire Fryer 3/21/18
Reports Fire Door
Comment Wondoor 9/14/17
Reports Fire Extinguisher Service
Comment Hawkeye Fire 3/18
Reports Emergency Egress Exit and Egress Lights Testing.
Comment 159 Tested by Bren Jacobs 7/31/18 with 3 deficiencies.
Inspection Fee S 600.00
Occupancy Fee S 10.00
Re-inspection Fee S
Total Fee* $ 610.00
Received By Jeff Siebel
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection# Date Time
1 9/7/2018