COMMERCIAL INSPECTION- 812 IDAHO ST-9-6-18 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price
J
INSPECTION 50,000 $225.00
OCCUPANCY FEE
$10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23093 09/04/2018 10/10/2018 2019-00010138 $235.00
Less Prepayment $0.00
Total Due $235.00
City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1776
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 812 Idaho St
Business name Highland Elementary School
Inspection Date* 9/6/2018
Proprietor Waterloo Community Schools/Marty Metcalf
Business Phone 319-433-1828
Email* metcalfm@waterlooschools.org
Email 2 willandm@waterlooschools.org
Property Owner Waterloo Community Schools
Emergency Contact Matt Willand
Information
Phone 319-433-2630
Violations
Ref# CODE Violation&Location Corrected
1 2015 IFC General Requirements Section 315 General Storage
315.3.3 Equipment rooms. Combustible material shall not be stored
in boiler rooms, mechanical rooms, electrical equipment rooms or in
fire command centers.
*Miscellaneous storage was found in the equipment room in room
151A
*Storage was being moved out at the time of inspection
Ref# CODE Violation &Location Corrected
2 2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.7 Appliances. Electrical appliances and fixtures shall be tested
and listed in published reports of inspected electrical equipment by
an approved agency and installed and maintained in accordance
with all instructions included as part of such listing.
*Refrigerator and microwave were found to be plugged into a
power tap in room 131
*Refrigerator and microwave were plugged directly into an outlet
during the inspection. Fixed on scene.
3 2015 IFC Fire and Smoke Protection Features Section 703 Fire-
Resistance-Rated Construction
703.2.2 Hold-open devices and closers. Hold-open devices and
automatic door closers, where provided, shall be maintained.
During the period that such device is out of service for repairs,the
door it operates shall remain in the closed position.
*Foot wedges were found holding doors open by the Gym Offices
and Entrance doors by the Gym
*Foot wedges were removed during the inspection. If these doors
need to be kept open please install approved hold-open devices.
4 2015 IFC Fire Protection Systems Section 901 General
901.4 Installation. Fire protection systems shall be maintained in
accordance with the original installation standards for that system.
Required systems shall be extended,altered or augmented as
necessary to maintain and continue protection where the building is
altered, remodeled or added to.Alterations to fire protection
systems shall be done in accordance with applicable standards.
*Ceiling tiles were missing in room 148
*Corrective action, replace missing ceiling tiles
5 2015 IFC Means of Egress Section 1010 Doors, Gates and
Turnstiles
1010.1.9.4 Bolt locks. Manually operated flush bolts or surface
bolts are not permitted.
*Flush bolt was found on a marked Exit door from the Cafeteria
into the Gym
*Lock was removed at the time of inspection
Comments: Commercial Fire Inspection went well. Most of the items found at the time of
inspection were corrected at the time of inspection. Plans are underway to replace
the missing ceiling tiles. Fire drill is planned to take place. Please send in the
proper documentation for the fire drill and email Chris Ferguson or Brock Weliver
when the ceiling tiles are replaced. No further re-inspections are needed for this
school.
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Black Hawk Sprinkler, 12-22-2017
Hydrants, 6-15-2018
Reports Annual Fire Alarm
Comment Hawkeye Fire&Signal,6-14-2018
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment Harris Cleaning, 3-14-2018
Vents, 3-14-2018
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Superior,2-19-2018
Reports Emergency Egress Exit and Egress Lights Testing.
Comment Central Battery System,Visual Displays indicated systems were ok
Reports Fire Extinguisher Service
Comment Superior,6-28-2018
Inspection Fee $ 225.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 235.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload(for long
inspections)
Reinspection
Re-inspection# Date Time