COMMERCIAL INSPECTION- 1825 LA PORTE RD- 8-30-18 FOR BILLING INQUIRY: (319)291-4323
LDescription Total Price J
REINSPECTION 3 $200.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4899 09/04/2018 10/10/2018 2019-00010110 $200.00
Less Prepayment $0.00
Total Due— $200.00
City of Waterloo
REINSPECTION - Commercial Fire Inspection Form
Inspection Number 1335
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 1825 Laporte Rd
Business Name Super 8
Inspection Date* 8/30/2018
Proprietor Imdar Lutchmansingh
Business Phone 319-229-5574
Email* stay@super8waterloo.com
Email 2
Property Owner
Emergency Contact lmdar Lutcmansingh
Information
Phone 1-847-650-7941
Violations
Ref# Code Violation &Location Corrected
1 2015 IFC Building Services and Systems Section 605
Electrical Equipment, Wiring and Hazards
605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited.Approved covers
shall be provided for all switch and electrical outlet boxes.
*Rooms 315 and 216 were written up on the initial
inspection for having exposed wires in the bath fans.
These rooms have not been re-inspected since. Ensure
that the wiring issues are taken care of an allow for re-
inspection.
Ref# Code Violation &Location Corrected
2 2015 IFC Fire and Smoke Protection Features Section
703 Fire-Resistance-Rated Construction
703.2.3 Door operation. Swinging fire doors shall close
from the full-open position and latch automatically.The
door closer shall exert enough force to close and latch
the door from any partially open position.
*On 8-30-2018,the following doors did not self close and
latch properly: 319, 312, 309, 221,217, 206, 205, 203,
121, 111
*Ensure that all doors self close and latch properly
*On Previous inspections doors that did not self close
and latch properly were: Stairway door by 323, 323, 319,
317, 315, 313, 312, 311, Housekeeping by 308, Closet
by 301, Housekeeping by 301, Housekeeping by 208,
Laundry chute on 2nd floor, Storage by 223,223,221,
219, 217, Fire door by 217, 215, 211, 210, 209, 208,
207, 206, 205, 203, 123, Fire door by 117, 117, 116,
113, Elevator Equipment room door, 107, 105, 104,
Storage by 101, Fire door by 101.
*On 8-30-2018 All Fire doors but Fire door by 217
operated correctly. See below
3 2015 IFC Fire and Smoke Protection Features Section
703 Fire-Resistance-Rated Construction
703.2.2 Hold-open devices and closers. Hold-open
devices and automatic door closers,where provided,
shall be maintained. During the period that such device is
out of service for repairs, the door it operates shall
remain in the closed position.
*Fire door by 217 needs hold-open device placed back
onto door, also floor is holding door open, door needs to
be adjusted as to not be held open by the floor.
4 2015 IFC Fire Protection Systems Section 901 General
901.6 Inspection, testing and maintenance. Fire
detection, alarm, and extinguishing systems, mechanical
smoke exhaust systems, and smoke and heat vents shall
be maintained in an operative condition at all times, and
shall be replaced or repaired where defective.
Nonrequired fire protection systems and equipment shall
be inspected,tested and maintained or removed.
*On 8-30-2018 Smoke detectors were not working
properly or were missing from rooms,these rooms
include: 323, 316, 312, 304,218, 214-missing, 117-
missing, 111-missing, 105-missing.
*Previously on inspections, smoke detectors found to be
out were, 315, 313, 312, 311, 219, 218, 217, 215, 202,
210, 118, 115, 111
*Ensure that smoke detectors are present and in good
working condition at all times.
*Follow manufacturer's recommendations as to how long
to keep smoke detectors in service and when to replace
them.Typically it is recommended that smoke detectors
are replaced at least every 10 years.
Comments: All available doors and smoke detectors will be checked again upon re-inspection.
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00 -First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
• Reports
Reports Annual Fire Alarm
Comment Received
Reports Fire Extinguisher Service
Comment Received
Inspection Fee S
Occupancy Fee S
Re-inspection Fee $ 200.00
Total Fee* S 200.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection Date Time
9/24/2018
•
REINSPECTION - Commercial Fire Inspection Form
Inspection Number 1642
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 4015 Loaves Blvd
Business Name Popeyes Chicken
Inspection Date* 8/22/2018
Proprietor Danielle Allen
Business Phone 319-234-2393
Email* danielle.allen@jamrestaurantgroup.corn
Email 2 banksaliyonna06@gmail.com
Property Owner The Chicken Coupe LLC
Emergency Contact Angela Banks
Information
Phone 319-491-1477
Violations
Ref# Code Violation &Location
Corrected
1
Comments: Previous violations have not been corrected. Please see the initial Fire Inspection
Report for a list of the violations found during the initial inspection. Subsequent re-
inspections will generate re-inspection fees listed below.
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200 Third and subsequent Re-inspections
Reports
Reports
Comment
Inspection Fee $
Occupancy Fee $
Re-inspection Fee $ 100.00
Total Fee* $ 100.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload(for long
inspections)
Reinspection
Re-inspection Date
Time
9/12/2018