COMMERCIAL INSPECTION-226 W 5TH ST- 9-5-18 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23 026 09/04/2018 10/10/2018 2019-00010130 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
REINSPECTION - Commercial Fire Inspection Form
Inspection Number 1613
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 226 W 5th St
Business Name EconoLodge Inn&Suites
Inspection Date* 9/5/2018
Proprietor
Business Phone 319-235-0301
Email* damirhasonovic1980@gmail.com
Email 2 Srizvi0801@gmail.com
Property Owner Birchwood Hospitality LLC
Emergency Contact Damir Hasonovic
Information
Phone 319-349-6174
Violations
Ref# Code Violation &Location Corrected
1 2015 IFC General Requirements Section 315 General
Storage
315.3.1 Ceiling clearance. Storage shall be maintained 2
feet or more below the ceiling in nonsprinklered areas of
buildings or not less than 18 inches below sprinkler head
deflectors in sprinklered areas of buildings.
*Maintain clearances described above throughout the
entire building at all times.
*Storage and maintenance closets were found to be
stacked up to deflector head heights
Ref# Code Violation &Location Corrected
2 2015 IFC Building Services and Systems Section 605
Electrical Equipment,Wiring and Hazards
605.4 Multiplug adapters. Multiplug adapters, such as
cube adapters, unfused plug strips or any other device
not complying with NFPA 70 shall be prohibited.
3 2015 IFC Building Services and Systems Section 605
Electrical Equipment,Wiring and Hazards
605.4.1 Power tap design. Relocatable power taps shall
be of the polarized or grounded type, equipped with
overcurrent protection, and shall be listed in accordance
with UL 1363.
4 2015 IFC Building Services and Systems Section 605
Electrical Equipment,Wiring and Hazards
605.4.2 Power supply. Relocatable power taps shall be
directly connected to a permanently installed receptacle.
*Daisy chained power taps were found in maintenance
closet on 4th floor across from elevators
5 2015 IFC Fire and Smoke Protection Features Section
703 Fire-Resistance-Rated Construction
703.2.3 Door operation. Swinging fire doors shall close
from the full-open position and latch automatically. The
door closer shall exert enough force to close and latch
the door from any partially open position.
*Numerous doors were found to not fully close and latch
properly
*On 9-5-2018 doors 525,412,420,423, 324, 325, 307,
227 did not close and latch properly
*Previously doors 501, 517, 524, 525,412, 327, 325,
303, 229, 224,222, 221 did not close and latch properly
*Ensure that all doors close and latch properly
6 2015 IFC Fire Protection Systems Section 901 General
901.6 Inspection,testing and maintenance. Fire
detection, alarm,and extinguishing systems, mechanical
smoke exhaust systems, and smoke and heat vents shall
be maintained in an operative condition at all times, and
shall be replaced or repaired where defective.
Nonrequired fire protection systems and equipment shall
be inspected,tested and maintained or removed.
*Smoke detectors were found to be out or missing when
tested
*Ensure that smoke detectors are present and in good
working condition at all times
*On 9-5-2018 smoke detectors found to be not working
were, but not limited to: 500 both, 520 both,401,402
both, 405(BR), 414, 420,423, 324(BR), Exercise Room,
Laundry Room, 224, 228, 227
*Previously smoke detectors found to be not working
were, but not limited to:515,516(LR), 517 both, 521 (LR),
525 both,422 both,421 both,416 (LR),415(LR),412
(BR), 303 (LR), 312 (LR), 320(BR), 327 both, 328, 223,
222, 221, 212,203, Hallway smoke by 312
LR=Living Room, BR=Bedroom
Ref# Code Violation &Location Corrected
7 2015 IFC Fire Protection Systems Section 901 General
901.4 Installation. Fire protection systems shall be
maintained in accordance with the original installation
standards for that system. Required systems shall be
extended, altered or augmented as necessary to maintain
and continue protection where the building is altered,
remodeled or added to.Alterations to fire protection
systems shall be done in accordance with applicable
standards.
*Rooms were found to be under construction at the time
of inspection, please ensure that all Fire and Life Safety
Systems are being maintained as initially installed.
*Rooms under construction include 505, 507, 510, 512,
515, 529,407
*On 9-5-2018 The 5th floor had multiple water leaks all
over the entire floor. Ensure that water has not damaged
any Fire or Life Safety Systems
Ceiling tiles are missing from the main storage unit on the
1st floor. Ensure that all ceiling tiles are replaced where
missing.
8 2015 IFC Means of Egress Section 1008 Means of
Egress Illumination
1008.2 Illumination required. The means of egress
serving a room or space shall be illuminated at all times
that the room or space is occupied.
*Egress lights were found to be out when tested.
*Corrective action, repair or replace lights. Lights include
egress light in stairway between 4th and 5th floor by room
528, in stairway between 2nd and 3rd floor by 305,
egress light by 327
9 2015 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at
all times. To ensure continued illumination for a duration
of not less than 90 minutes in case of primary power loss,
the sign illumination means shall be connected to an
emergency power system provided from storage
batteries, unit equipment or an on-site generator. The
installation of the emergency power system shall be in
accordance with Section 604.
*Exit lights were found to be out when tested
*Corrective action, repair or replace lights. Lights
include: Exit light in stairway between 4th and 5th floor by
room 528, Exit light by room 405, Exit light in stairwell of
main lobby
Comments: General housekeeping throughout the building needs improvement. Multiple rooms
were found with trash that had not been emptied for some time. 5th floor ceiling
leaks are destroying drywall.
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
• Comment Black Hawk Sprinkler 9-5-2018, Contractor was there performing inspection on
system as Fire Inspection was taking place. Contractor is supposed to email the
report
Reports Annual Fire Alarm
Comment Proshield. 7-2-2018
Reports Fire Extinguisher Service
Comment Proshield, 7-2018
Inspection Fee $
Occupancy Fee S
Re-inspection Fee S 100.00
Total Fee* $ 100.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection Date Time
9/26/2018