COMMERCIAL INSPECTION- 1825 LA PORTE RD- 8-9-18 FOR BILLING INQUIRY: (319)291-4323
L Description Total Price
REINSPECTION 3 $200.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4899 08/13/2018 09/20/2018 2019-00010089 $200.00
Less Prepayment $0.00
Total Due-p $200.00
City of Waterloo
RI-INSPECTION - Commercial Fire.Inspection Form
Inspection Number 1335
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 1825 Laporte Rd
Business Name Super 8
Inspection Date* 8/9/2018
Proprietor Imdar Lutchmansingh
Business Phone 319-229-5574
Email* stay@super8waterloo.com
Email 2
Property Owner
Emergency Contact Imdar Lutcmansingh
Information
Phone 1-847-650-7941
Violations
Ref# Code Violation &Location Corrected
1 2015 IFC General Requirements Section 315 General
Storage
315.3.1 Ceiling clearance. Storage shall be maintained 2
feet or more below the ceiling in nonsprinklered areas of
buildings or not less than 18 inches below sprinkler head
deflectors in sprinklered areas of buildings.
*During re-inspection on 8-9-2018 all storage areas were
in compliance. Continue to maintain storage as described
above
Re"# Code Violation&Location Corrected
2 2015 IFC Building Services and Systems Section 605
Electrical Equipment,Wiring and Hazards
605.3 Working space and clearance.A working space of
not less than 30 inches in width,36 inches in depth and
78 inches in height shall be provided in front of electrical
service equipment.Where the electrical service
equipment is wider than 30 inches,the working space
shall be not less than the width of the equipment. Storage
of materials shall not be located within the designated
working space.
*During re-inspection on 8-9-2018 storage was in
compliance as described above.Continue to maintain
clearances as described above.
3 2015 IFC Building Services and Systems Section 605
Electrical Equipment,Wiring and Hazards
605.6 Unapproved conditions.Open junction boxes and
open-wiring splices shall be prohibited.Approved covers
shall be provided for all switch and electrical outlet boxes.
*Rooms 315 and 216 were written up on the initial
inspection for having exposed wires in the bath fans.
These rooms have not been re-inspected since. Ensure
that the wiring issues are taken care of and allow for re-
inspection.
4 2015 IFC Fire and Smoke Protection Features Section
703 Fire-Resistance-Rated Construction
703.2.3 Door operation. Swinging fire doors shall close
from the full-open position and latch automatically.The
door closer shall exert enough force to close and latch
the door from any partially open position.
*During re-inspection on 8-9-2018,the following doors
did not self close and latch properly:317, 221,219,217,
205, 203,Along with Fire Doors by 317/stairway and
217 217 also needs hold open device
*Previously doors that would not self close and latch
were; room by 301,closet by 301, housekeeping by 308,
311, 312, 313, 315, 317,319,323, stair door by 323,2nd
floor housekeeping by 208, laundry chute,storage by
223,223,221, 217, 215,211,210, 209, 208,207,206,
203,fire doors by room 101,storage by room 101, 104,
105, 107,elevator equipment room door, 113, 116, 117,
fire door by 117, 123.
*Ensure that all doors self close and latch properly
5 2015 IFC Fire Protection Systems Section 901 General
901.6 Inspection,testing and maintenance. Fire
detection,alarm,and extinguishing systems,mechanical
smoke exhaust systems,and smoke and heat vents shall
be maintained in an operative condition at all times,and
shall be replaced or repaired where defective.
Nonrequired fire protection systems and equipment shall
be inspected,tested and maintained or removed.
*During re-inspection on 8-9-2018 smoke detectors were
found to be not be working in rooms 219/missing and
205.
*Previously smoke detectors in rooms 315,313, 312,
311,219, 218, 217,215,202,201, 118, 115, 111
*Ensure that all smoke detectors are present and in
good working condition at all times
Comments: *Exit and Egress lights were all in_good working condition on re-inspection on 8-9-
2018
*Holes were patched in owners office
*Annual Alarm has been performed
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100,00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Alarm
Comment Hawkeye Fire&Alarm,3-7-2018 •
Reports Fire Extinguisher Service
Comment Proshield, 10-2017
Reports
Comment **Dryer vent/exhaust cleaning/maintenance should be done in accordance with
manufacturer's recommendations. Document the date,time, personnel performing
maintenance and signature.
Maintenance/cleaning may be done by maintenance/staff personnel.
Inspection Fee $
Occupancy Fee $
Re-inspection Fee $ 200.00
Total Fee* $ 200.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload(for long
inspections)
Reinspection
Re-inspection Date Time
8/30/2018