HomeMy WebLinkAbout3026 ANSBOROUGH AVE STE B INVOICE DATE DUE DATE INVOICE# TOTAL DUE
IA it I I\V.= 07/10/2018 08/22/2018 2019-00010036 $5 0.00
��, 1
4'ertoo
Customer#: 11636 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
COST CUTTERS 715 Mulberry St
3026 ANSBOROUGH AV B WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION-3026 ANSBOROUGH AVE SUITE B - FOR BILLING INQUIRY: (319)291-4323
7-9-18
[Description I Total Price
INSPECTION 1 $40.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
11636 07/10/2018 08/22/2018 2019-00010036 $50.00
Less Prepayment $0.00
Total Due -* $50.00
City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1637
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 3026 Ansborough Ave Suite B
Business name Cost Cutters
Inspection Date* 7/9/2018
Proprietor Suzy Rund
Business Phone 319-233-9440
Email* jmiller@evanscric.com
Email 2
Property Owner Family Video Movie Club Inc
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation &Location Corrected
1 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
*Egress light was out when tested, egress light on the back wall
*Corrective action, repair or replace egress light
Reif#
CODE Violation &Location Corrected
2 20,15 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator.The
installation of the emergency power system shall be in accordance
with Section 604.
*Exit light was out, light above main door
**Corrective action, repair or replace exit light
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Fire Extinguisher Service
Comment Proshield,April 2018
Reports
Comment **Dryer vent/exhaust cleaning/maintenance should be done in accordance with
manufacturer's recommendations. Document the date,time, personnel performing
maintenance and signature.
Maintenance/cleaning may be done by maintenance/staff personnel.
***Please provide current cleaning report
Inspection Fee $ 40.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 50.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection# Date Time
7/30/2018