City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1627
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 1620 LaPorte Rd
Business name Taco John's
Inspection Date* 7/6/2018
Proprietor Barb Myers
Business Phone 319-493-9678
Email* tj9080@quikserve.com
Email 2
Property Owner C and M Enterprises INC
Emergency Contact 319-233-3651
Information
Phone
Violations
Ref# CODE Violation &Location Corrected
'I 2015 IFC General Requirements Section 315 General Storage
315.3.1 Ceiling clearance. Storage shall be maintained 2 feet or
more below the ceiling in nonsprinklered areas of buildings or not
less than 18 inches below sprinkler head deflectors in sprinklered
areas of buildings.
*Storage in general storage areas in back area and cooler/freezer
were found to be next to the ceiling
**Corrective action, lower storage down to heights described
above
Ref# CODE Violation &Location Corrected
2 2015 IFC Means cif Egress'Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator.The
installation of the emergency power system shall be in accordance
with Section 604.
*Egress/Exit light by the back door in the prep area was found to
be out when tested
**Corrective action, repair or replace Exit/Egress light
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment B&B Vent Cleaning.2-20-2018
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Superior, 5-2018
Reports Fire Extinguisher Service
Comment Proshield, March 2018
Inspection Fee $ 40.00
Occupancy Fee $ 10.00
Re-inspection Fee
Total Fee* $ 50.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection# Date Time
7/27/2018