HomeMy WebLinkAbout325 COMMERCIAL ST (2) INVOICE DATE DUE DATE INVOICE# TOTAL DUE
I�� 11117141r,
mi, ,'i•; 12/17/2018 01/30/2019 2019-00010214 $100.00
Customer#: 22975 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
SINGLE SPEED 715 Mulberry St
325 COMMERCIAL ST WATERLOO, IA 50703
WATERLOO,IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION-325 COMMERCIAL ST- 11-28-18 FOR BILLING INQUIRY: (319)291-4323
LDescription Total Price J
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
22975 12/17/2018 01/30/2019 2019-00010214 $100.00
Less Prepayment $0.00
Total Due-p $100.00
City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1927
Prior Inspection 770
Number Fill this field if it is available, it will auto-fill business name and address.
Inspector* Jeff Siebel
Waterloo Fire Rescue
715 Mulberry Street Waterloo, IA 50703
Phone(319)-230-1224 Fax. (319)-291-4262
Email: Jeff.Siebel@waterloo-ia.org
File Upload
Address* 325 Commercial St
Business name Single Speed
Inspection Date* 11/28/2018
Proprietor Ana Hanisch, Director of Operations
Business Phone 319-883-3604
Email* ANA@singlespeedbrewing.com
Email 2 kegan@singlespeedbrewing.com
Property Owner Dave Morgan
Emergency Contact Ana Hanisch
Information
Phone 319-883-3604
Violations
Ref# CODE Violation &Location Corrected
1 609.3.3.1 Provide current semi-annual kitchen hood exhaust system
cleaning/inspection report with all deficiencies corrected.
2 904.11.6. Provide current semi-annual kitchen hood fire suppression system
2 inspection/testing with all deficiencies corrected by a contractor
certified to work in the State of Iowa
3 NFPA 25 Provide current annual fire sprinkler system inspection/testing
report with all deficiencies corrected by a contractor certified to
perform work in the State of Iowa.
Ref#
CODE Violation &Location Corrected
4 NFPA 72 Provide current annual fire alarm inspection/testing report with all
deficiencies corrected by a contractor certified to perform work in
the State of Iowa.
5 Kitchen pantry walk in cooler:
A. Repair fire sprinkler coverage immediately.
B. Replace missing fire sprinkler head escutcheon.
C. Remove combustibles(wood)from ceiling
6 Repair inside and outside egress lights above main entrance.
7 Remove obstructions,maintain a minimum of 36"clearance to fire
extinguisher at all times.
8 Provide an approved, listed oily waste container with self-closing lid
for all grease laden materials. (See attached).
9 Provide and approved metal container with self closing lid that is
specifically listed and designed for hot ashes.
10 Boiler room:
A. repair excessive moisture problem creating hazard with all
electrical panels and equipment.
B. Properly contain exposed wiring in junction box above boiler
room door.
C. Immediately remove cover from smoke detector.
D. Remove pallet storage(combustibles)from boiler and
equipment room.
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100.00-First Re-inspection I$150.00 -Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports
Comment
Inspection Fee $ 90.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 100.00
Received By Ana Hanisch
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.