City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1845
Prior Inspection 946
Number Fill this field if it is available, it will auto-till business name and address.
Inspector* Jeff Siebel
Waterloo Fire Rescue
715 Mulberry Street Waterloo, IA 50703
Phone(319)-230-1224 Fax. (319)-291-4262
Email:Jeff.Siebel@waterloo-ia.org
File Upload
Address* 1744 Falls Ave
Business name Active Minds Learning Center
Inspection Date* 10/15/2018
Proprietor Ronni Armstrong
Business Phone 319-234-1060
Email* Ronni@activemindsia.com
Email 2
Property Owner
Emergency Contact Ronni Armstrong
Information
Phone 319-415-4925
Violations
Ref# CODE Violation &Location Corrected
1 NFPA 72 Provide current annual fire alarm inspection/testing report with all
deficiencies corrected by a contractor certified to perform work in
the State of Iowa.
Ref# CODE Violation &Location Corrected
2 2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.4.1 Power tap design. Relocatable power taps shall be of the
polarized or grounded type, equipped with overcurrent protection,
and shall be listed in accordance with UL 1363.
Remove electrical extension cord by TV. Install permanent outlet or
utilize a circuit protected power tap.
3 Exits 1010.1.3
The force for pushing or pulling open interior swinging egress
doors, other than fire doors,shall not exceed 5 pounds. For other
swinging doors, as well as sliding and folding doors,the door latch
shall release when subjected to a 15 pound force.The door shall
be set in motion when subjected to a 30 pound force. The door
shall swing to a full-open position when subjected to a 15 pound
force.
Repair exit door from 2 to 3 year old class room to the outside.
Door must unlatch with less than 15#force and swing to full open.
4 2015 IFC Section 605.7 Electrical Appliances-provide verification
of dryer cleaning to the outside in accordance with manufacturer's
recommendations or regular schedule(ex. once a month)
5 2015 IFC Building Services and Systems Section 605 Electrical
Equipment, Wiring and Hazards
605.3 Working space and clearance.A working space of not less
than 30 inches in width. 36 inches in depth and 78 inches in height
shall be provided in front of electrical service equipment.Where
the electrical service equipment is wider than 30 inches,the
working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated
working space.
Remove obstructions to electrical panel. Maintain a minimum of 36"
clearance at all times.
Comments: Day care licensed for 60 children. Today there were 13 children. 2 children were
under the age of 2.5 years of age.2 to 3 year olds are kept in a classroom with a
direct exit.
Fire drills practiced monthly. Last
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports
Comment
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 80.00
Received By Ronni Armstrong