Corn,. rci ,l Fire Inspection Report
Inspection Number 1870
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 928 Jefferson St.
Business name SonRise Christian School
Inspection Date* 10/25/2018
Proprietor Tish Jacobsen
Business Phone 319-235-6191 /319-961-4215
Email* preschool@sonrisewaterloo.com
Email 2
Property Owner Open Bible of Waterloo
Emergency Contact Aaron Keller
Information
Phone 319-290-9963
Violations
Ref# CODE Violation &Location Corrected
Ref# CODE Violation &Location Corrected
1 2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.5 Extension cords. Extension cords and flexible cords shall not
be a substitute for permanent wiring. Extension cords and flexible
cords shall not be affixed to structures,extended through walls,
ceilings or floors, or under doors or floor coverings, nor shall such
cords be subject to environmental damage or physical impact.
Extension cords shall be used only with portable appliances.
2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.4 Multiplug adapters. Multiplug adapters,such as cube
adapters, unfused plug strips or any other device not complying
with NFPA 70 shall be prohibited.
*An extension cord with a multi plug adapter end was found to be
plugged into a television in the Nursery Room.
*Corrective action, discontinue the use of extension cords for
permanent wiring.
2 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
2015 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator.The
installation of the emergency power system shall be in accordance
with Section 604.
*Exit/Egress lights were found to be out when tested.
*Batteries are on order for all of these lights
*Staff personnel are able to perform function tests of these lights.
If periodic testing of these lights are performed, please keep a log
and document the date,time, results and name/signature of person
performing these tests.
Comments: Contact your contractor(Proshield)about the hood suppression system.The tag
was out of date,they had provided service to the rest of your building and
systems.The report may be emailed to me at the address above.
You may also email me a log of the Egress/Exit lights when the new batteries have
been installed.
We will schedule a tentative re-inspection 3 weeks from today for the items above.
Once the items have been corrected,email the above records and the inspection
will be closed/completed.
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100,00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Black Hawk Sprinkler, 10-31-2017
*Next annual inspection is scheduled to be performed in upcoming weeks
Reports Annual Fire Alarm
Comment Proshield,4-25-2018
Reports Fire Extinguisher Service
Comment Proshield,Apr 2018
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment B&B Vent, 7-10-2018
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
*Make contact with contractor about this item, may have been done, tag was old
Reports
Comment Fire Door, in kitchen, Overhead Door 9-27-2018
Reports
Comment Fire Drills, monthly log, last performed 9-26-2018
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee S
Total Fee* $ 80.00