COMMERCIAL INSPECTION- 89 FRANKLIN ST- 10-25-18 FOR BILLING INQUIRY: (319)291-4323
1 Description ( Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
9868 11/16/2018 01/17/2019 2019-00010201 $80.00
Less Prepayment $0.00
Total Due—* $80.00
City of Waterloo
Com rcial Fire Inspection Report
Inspection Number 1871
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 89 Franklin St
Business name The Salvation Army
Inspection Date* 10/25/2018
Proprietor Martin Ainsworth
Business Phone 319-235-9358
Email* MARTIN AINSWORTH@USC.SALVATIONAR
MY.ORG
Email 2
Property Owner The Salvation Army
Emergency Contact Martin Ainsworth
Information
Phone 319-464-1797
•
Violations
Ref# CODE Violation &Location Corrected
1 2015 IFC General Requirements Section 315 General Storage
315.3.1 Ceiling clearance. Storage shall be maintained 2 feet or
more below the ceiling in nonsprinkiered areas of buildings or not
less than 18 inches below sprinkler head deflectors in sprinklered
areas of buildings.
*Multiple areas of the building had storage in violation of the
clearances above.
*Corrective action, maintain storage in all areas of the building to
the clearances described above.
Ref# CODE Violation &Location Corrected
2 2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.5 Extension cords. Extension cords and flexible cords shall not
be a substitute for permanent wiring. Extension cords and flexible
cords shall not be affixed to structures, extended through walls,
ceilings or floors, or under doors or floor coverings, nor shall such
cords be subject to environmental damage or physical impact.
Extension cords shall be used only with portable appliances.
*An extension cord was found in the Youth Center Area that was
extended up through the ceiling and came back out of the ceiling
and connected to Christmas lights around a pole.
*Corrective action, extension cords are only to be used as
described above
3 2015 IFC Building Services and Systems Section 605 Electrical
Equipment, Wiring and Hazards
605.10.4 Prohibited areas. Portable,electric space heaters shall
not be operated within 3 feet of any combustible materials.
Portable,electric space heaters shall be operated only in locations
for which they are listed.
*Portable space heaters were found in the Sunday Nursery area
*Corrective action, discontinue the use of portable space heaters
•
Ref# CODE Violation &Location Corrected
4 2015 IFC Building Services and Systems Section 609 Commercial
Kitchen Hoods
609.3.3 Cleaning. Hoods, grease-removal devices,fans, ducts and
other appurtenances shall be cleaned at intervals as required by
Section 609.3.3.1 through 609.3.3.3
2015 IFC Building Services and Systems Section 609 Commercial
Kitchen Hoods
609.3.3.1 Inspection. Hoods,grease-removal devices, fans, ducts,
and other appurtenances shall be inspected at intervals specified
in Table 609.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
2015 IFC Building Services and Systems Section 609 Commercial
Kitchen Hoods
609.3.3.3 Records. Records for inspections shall state the
individual and company performing the inspection,a description of
the inspection and when the inspection took place. Records for
cleaning shall state the individual and company performing the
cleaning and when the cleaning took place.Such records shall be
completed after each inspection or cleaning and maintained.
2015 IFC Building Services and Systems Section 609 Commercial
Kitchen Hoods
609.3.3.3.1 Tags.When a commercial kitchen hood or duct system
is inspected, a tag containing the service provider name,address,
telephone number and date of service shall be provided in a
conspicuous location. Prior tags shall be covered or removed.
2015 IFC Building Services and Systems Section 609 Commercial
Kitchen Hoods
Table 609.3.3.1 Commercial Cooking System Inspection Frequency
Type of Cooking Operations
• High-volume cooking operations such as 24-hour
cooking, charbroiling or wok cooking, Frequency of Inspection 3
months
• Low-volume cooking operations such as places of
religious worship, seasonal businesses and senior centers,
Frequency of Inspection 12 months
•Cooking operations utilizing solid fuel-burning
cooking appliances, Frequency of Inspection 1 month
•All other cooking operations, Frequency of Inspection 6 months
*Hood Cleaning Report is needed for both kitchens,this report
may be emailed to the email address above.
Ref# CODE Violation &Location Corrected
5 2015 IFC Fire and Smoke Protection Features Section 703 Fire-
Resistance-Rated Construction
703.2.2 Hold-open devices and closers. Hold-open devices and
automatic door closers,where provided, shall be maintained.
During the period that such device is out of service for repairs,the
door it operates shall remain in the closed position.
*Multiple doors in the building had kick-stand type hold open
devices on them or foot wedge type hold open devices. Contact
you Fire Alarm contractor to install magnetic/electronic hold open
devices if you would like to keep doors opened. Many of these
doors are fire-rated doors and need to be closed in the event of a
fire. This helps compartmentalize and stops the spread of smoke
and flame throughout the building.
6 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required.The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
2015 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator. The
installation of the emergency power system shall be in accordance
with Section 604.
*Exit and Egress lights were found to be out when tested
*Lights were in the hallway by the Logan Ave exit doors and in the
Martin Bros. Building Exit door.
*Corrective action, repair or replace Exit/Egress lights
7 2015 IFC Means of Egress Section 1010 Doors, Gates and
Turnstiles
1010.1.9 Door operations. Except as specifically permitted by this
section, egress doors shall be readily openable from the egress
side without the use of a key or special knowledge or effort.
*Door in the hallway leading from the main entrance back to the
youth center had a keyed lock above the panic hardware for the
door.
*Corrective action, remove keyed lock from the door.
8 2015 IFC Fire Protection Systems Section 901 General
901.4 Installation. Fire protection systems shall be maintained in
accordance with the original installation standards for that system.
Required systems shall be extended, altered or augmented as
necessary to maintain and continue protection where the building is
altered, remodeled or added to.Alterations to fire protection
systems shall be done in accordance with applicable standards.
*Ceiling tiles were missing in the youth center storage room.
*Corrective action, replace ceiling tiles
Comments: Have the Waterloo Building Department review any work and permits for the work
that was performed in the Martin Bros. Building/garage bay area. There is a
mezzanine in this area that is potentially obstructing exit/egress doors.
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Alarm
Comment Proshield
Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
Reports Annual Generator Service
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Proshield, May 2018
Reports Fire Door
Comment Christie Door Company, Chapel Kitchen, 09-12-2018
Main Kitchen, needs test/report
Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
Reports Fire Extinguisher Service
Comment Proshield, May 2018
Reports
Comment Dryer vent,
Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
**Dryer vent/exhaust cleaning/maintenance should be done in accordance with
manufacturer's recommendations. Document the date,time, personnel performing
maintenance and signature.
Maintenance/cleaning may be done by maintenance/staff personnel.
***Vent was not hooked up to the water exhaust filter
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee S
Total Fee* S 80 00