City of Waterloo
Commercial Fire Inspection Report
Inspection Number 1889
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 45 W Jefferson St
Business name Grand Crossing Apartments
Inspection Date* 10/31/2018
Proprietor Jess Sullivan
Business Phone 319-429-7350
Email* rentals@rentcedarvalley.com
Email 2
Property Owner Brent Dahlstrom
Emergency Contact Jess Sullivan
Information
Phone 970-237-2587
Violations
Ref# CODE Violation&Location Corrected
1 2015 IFC General Requirements Section 315 General Storage
315.3.3 Equipment rooms. Combustible material shall not be stored
in boiler rooms, mechanical rooms,electrical equipment rooms or in
fire command centers.
*Storage was found in most of the equipment rooms.The only
items that are allowed to be stored in the equipment rooms are
items directly related to the equipment, such as air filters for
furnaces.
*Corrective action, remove all storage from equipment rooms.
Ref# CODE Violation &Location Corrected
2 2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.6 Unapproved conditions. Open junction boxes and open-
wiring splices shall be prohibited.Approved covers shall be
provided for all switch and electrical outlet boxes.
*An open junction box with wire splices was found in the Fire
Pump/Riser room.
*Corrective action, replace junction box cover plate.
3 2015 IFC Fire and Smoke Protection Features Section 703 Fire-
Resistance-Rated Construction
703.1 Maintenance.The required fire-resistance rating of fire-
resistance-rated construction, including but not limited to, walls,
firestops, shaft enclosures, partitions,smoke barriers,floors,fire-
resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems, shall be
maintained. Such elements shall be visually inspected by the owner
annually and properly repaired, restored or replaced where
damaged, altered, breached or penetrated. Records of inspections
and repairs shall be maintained.Where concealed,such elements
shall not be required to be visually inspected by the owner unless
the concealed space is accessible by the removal or movement of
a panel, access door, ceiling tile or similar movable entry to the
space. Openings made therein for the passage of pipes, electrical
conduit,wires,ducts,air transfer openings and holes made for any
reason shall be protected with approved methods capable of
resisting the passage of smoke and fire. Openings through fire-
resistance-rated assemblies shall be protected by self-or
automatic-closing doors of approved construction meeting the fire
protection requirements for the assembly.
*Sprinkler piping in the garage by Stairway B is penetrating a
rated-fire-wall and is missing fire caulking around it
*Corrective action,fire caulk around sprinkler piping penetration in
wall
*In the Utility Closet on 3rd floor by the elevator there is a gas line
that is not in use that is penetrating the ceiling in this area.
*Corrective action, cap the gas line.
4 2015 IFC Fire and Smoke Protection Features Section 703 Fire-
Resistance-Rated Construction
703.2.3 Door operation. Swinging fire doors shall close from the
full-open position and latch automatically.The door closer shall
exert enough force to close and latch the door from any partially
open position.
*Fire rated doors were found to not fully close and latch upon
testing
*Doors include;4th floor elevator fire door, stairway door on 1st
floor by room 118, Men's restroom door by 108
*Corrective action, adjust doors so that they are able to fully close
and latch from any open position.
CODE Violation &Location Corrected
Ref#
5 2015 IFC Fire Protection Systems Section 901 General
901.6 Inspection,testing and maintenance. Fire detection,alarm,
and extinguishing systems, mechanical smoke exhaust systems,
and smoke and heat vents shall be maintained in an operative
condition at all times,and shall be replaced or repaired where
defective. Nonrequired fire protection systems and equipment shall
be inspected,tested and maintained or removed.
*Multiple Fire Protection Systems are due for their annual
inspection/testing
*Systems include, Fire Sprinkler, Fire Alarm, Fire Extinguisher, Fire
Pump, Fire Hydrants(Private), Generator, Carbon Monoxide
Detection in garage area
*Please arrange to have these annual inspections performed
6 2015 IFC Means of Egress Section 1008 Means of Egress
Illumination
1008.2 Illumination required. The means of egress serving a room
or space shall be illuminated at all times that the room or space is
occupied.
*Egress lights were found to be out when tested.
*Lights include; Exit/Egress light by room 318, Exit/Egress light
above the door in the garage by parking spot 62, and the exterior
Egress light on this door too
*Corrective action, repair or replace Exit/Egress lights
7 2015 IFC Means of Egress Section 1013 Exit Signs
1013.6.3 Power source. Exit signs shall be illuminated at all times.
To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss,the sign illumination means
shall be connected to an emergency power system provided from
storage batteries, unit equipment or an on-site generator. The
installation of the emergency power system shall be in accordance
with Section 604.
*Exit/Egress lights were found to be out when tested
*See list above
8 2015 IFC Compressed Gases Section 5305 Use and Handling of
Compressed Gases
5305.3 Piping system. Piping, including tubing, valves,fittings and
pressure regulators, shall comply with this section and Chapter 50.
Piping,tubing, pressure regulators, valves and other apparatus
shall be kept gas tight to prevent leakage.
*3rd floor Utility Closet by elevator had gas pipe that needs to be
capped. See item 3 above.
Ref# CODE Violation &Location Corrected
9 2015 IFC Liquefied Petroleum Gas Section 6109 Storage of
Portable LP-Gas Containers Awaiting Use or Resale
6109.2 Exposure hazards. LP-gas containers in storage shall be
located in a manner that minimizes exposure to excessive
temperature rise, physical damage or tampering.
2015 IFC Liquefied Petroleum Gas Section 6109 Storage of
Portable LP-Gas Containers Awaiting Use or Resale
6109.5 Quantity. Empty LP-gas containers that have been in LP-
gas service shall be considered as full containers for the purpose
of determining the ma)amum quantities of LP-gas allowed in
Sections 6109.9 and 6109.11.
2015 IFC Liquefied Petroleum Gas Section 6109 Storage of
Portable LP-Gas Containers Awaiting Use or Resale
6109.7 Storage in basement, pit or similar location. LP-gas
containers shall not be stored in a basement, pit or similar location
where heavier-than-air gas might collect. LP-gas containers shall
not be stored in above-grade underfloor spaces or basements
unless such location is provided with an approved means of
ventilation.
*There was a 20 pound LP tank found in the garage by the bicycle
rack near parking spot 62.
*Corrective action, discontinue the use of storing LP-gas tanks in
this area or the garage area
10 2015 IFC General Requirements Section 304 Combustible Waste
Material
304.1 Waste accumulation prohibited. Combustible waste material
creating a fire hazard shall not be allowed to accumulate in
buildings or structures or upon premises.
2015 IFC General Requirements Section 304 Combustible Waste
Material
304.1.1 Waste material.Accumulations of wastepaper,wood, hay,
straw,weeds, litter or combustible or flammable waste or rubbish of
any type shall not be permitted to remain on a roof or in any court,
yard, vacant lot, alley, parking lot,open space, or beneath a
grandstand, bleacher, pier,wharf, manufactured home,
recreational vehicle or similar structure.
*Cardboard waste was found in the garage area near the bicycle
racks by parking spot 62
*An accumulation of waste not in the garbage bins was found in
the Garage Refuse/Recycling room
*Corrective action, remove excessive waste materials from these
areas.
Comments: 2015 IFC General Requirements Section 308 Open Flames
308.1.4 Open-flame cooking devices. Charcoal burners and other open-flame
' cooking devices shall not be operated on combustible balconies or within 10 feet of
combustible construction.
Exceptions:
1.One-and two-family dwellings.
2.Where buildings, balconies and decks are protected by an automatic sprinkler
system.
3. LP-gas cooking devices having LP-gas container with a water capacity not
greater than 2 1/2 pounds.
*Jess had asked about tenants being able to use gas or charcoal grills on the
balconies. This is the code section that covers that topic. None of the exceptions
are being met.The building has exterior sprinklers on floors 1,2 and 3 but not 4
and most of the grilling units appear to have a 20 pound LP tank.At this time we
are leaving it up to the building management on how to enforce this.
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
This inspection should include the private fire hydrants and the fire pump
Reports Annual Fire Alarm
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
This inspection/test should include the carbon monoxide detection system in the
garage area
Reports Annual Generator Service
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
Reports Annual Generator Load Test
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
Per the Fire Marshal and NFPA 110,the generator needs to be inspected weekly
and exercised under load monthly by qualified personnel.
Reports Fire Extinguisher Service
Comment Please provide current report, report may be emailed to the email address above \
If testing, inspection or servicing is due, please arrange to have it performed <60
Inspection Fee $ 70.00