COMMERCIAL INSPECTION-205 COMMERCIAL ST- 11-7-18 FOR BILLING INQUIRY: (319)291-4323
LDescription _ Total Price J
INSPECTION 100,000 $600.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12085 11/15/2018 12/20/2018 2019-00010168 $610.00
Less Prepayment $0.00
Total Due—> $610.00
City of Waterloo
REINSPECTION - Commercial Fire Inspection Form
Inspection Number 309
Inspector* Jeff Siebel
Waterloo Fire Rescue
715 Mulberry Street Waterloo, IA 50703
Phone(319)-230-1224 Fax. (319)-291-4262
Email: Jeff.Siebel@waterloo-ia.org
File Upload
Address* 205 Commercial Street
Business Name Ramada Inn
Inspection Date* 11/7/2018
Proprietor Reggie Simuel 217-781-2095
Business Phone 319-233-7560
Email* Jeff.siebel@waterloo-ia.org
Email 2 chris.ferguson@waterloo-ia.org
Property Owner Luke 1-708-785-0264
Emergency Contact Don Schlinger
Information
Phone Don 402-332-9151
Violations
Ref# Code Violation &Location Corrected
1 NFPA 25 Provide current annual fire sprinkler system
inspection/testing report with all deficiencies corrected by
a contractor certified to perform work in the State of Iowa.
Reports to include Electric Fire Pump, Fire Sprinkler
Stand Pipe, and Annual Wet System Inspection.
2 2015 IFC 7 Fire and Smoke Protection Features Section
703
703.4 Horizontal and vertical sliding and rolling fire doors
shall be inspected and tested annually to confirm proper
operation and full closure. Record of inspections and
testing shall be maintained. Provide testing of all elevator
lobby fire doors.
Ref# Code Violation &Location Corrected
3 609.3.3.1 Provide current semi-annual kitchen hood exhaust
system cleaning/inspection report with all deficiencies
corrected. For gas appliances.
4 609.3.3.1 Provide current semi-annual kitchen hood exhaust
system cleaning/inspection report with all deficiencies
corrected. Exhaust Hoods serving Solid Material(wood)
burning material must be cleaned and inspected by a
qualified agency monthly. Maintain record of monthly
cleaning reports for review on nest annual fire
inspections.
5 Provide documentation of dryer vent cleaning to the
outside of building for guest and commercial dryers with
signature and date. Can be performed by
maintenance/staff.
6 Provide documentation of locations and testing of all
emergency egress and exit lighting with all deficiencies
corrected with signature and date.
7 2015 IFC Fire and Smoke Protection Features
Section 703 Fire-resistance-rated construction
703.1 Maintenance
The required fire resistance rating o the fire-resistance-
rated construction, including but not limited to,walls,fire-
stops, shaft enclosures, partitions, smoke barriers,floors,
fire-resistant joint systems, shall be maintained., Such
elements shall be visually inspection by the owner
annually and properly repaired, restored or replace
where damaged, altered, breached or penetrated.
Records of inspections and repairs shall be maintained.
Where concealed, such elements shall not be required to
be visually inspected by the owner unless the concealed
space is accessible by the removal or movement a panel,
access door, ceiling tile or similar movable entry to the
space. Opening made therein for the passage of pipes,
electrical conduit,wires, ducts,air transfer openings and
holes mad for any reason shall be protected with
approved methods capable of resisting the passage of
smoke and fire. Openings through fire-resistance-rated
assemblies shall be protected by self-or automatic-
closing doors of approved construction meeting the fire
protection requirements for the assembly.
A. Patch all openings in corridor ceilings with an
approved listed system providing a 1 hour fire protection
rating.
B. Provide an approved 1 hour fire protection system for
all penetrations around new wires stubbed into all rooms
above ceilings that have been opened.
C. Provide an approved 1 hour fire protection system for
all vertical penetrations in all chases that are opened for
construction.
Provide inspector opportunity to verify all penetrations
have been properly sealed before covering openings in
accordance with 2015 IFC Section 106.3
D. Provide an approved 1 hour fire protection system for
all chase walls and ceilings in ail rooms.
E. Replace all missing ceiling systems and ceiling tile in
all areas including the entire basement.
Ref# Code Violation &Location Corrected
8 Replace all spot smoke detectors with a manufacture
date before October,6, 2008 in all rooms or provide
documentation of their testing and performance from a
approved listing agency.
• 9 A. Repair egress light East stairway hall 10th floor.
B. Repair egress light between floors 9 and 10 East
stairway.
C. Repair egress light 10th floor hall by west stairs.
10 Room 1009:
A.door must completely close and latch.
B. replace all missing lamps in sockets and bath fan.
11 Room 1022:
Refrigerator and microwave must plug directly into wall
outlet. Install permanent power with proper permits and
inspections.
12 Provide access to room 1024 for fire inspection.
13 Room 912, remove refrigerator and microwave from
power strip. Each must plug directly into wall outlet.
14 Room 909
install missing lamps in sockets, provide proper fire
separation as outlined in item#7
15 2013 NFPA 80.
A.4.2.1 labels are permitted to be of metal, paper, or
plastic or can be permitted to be stamped or diecat into
the item. Labels should not be removed, defaced, or mad
e illegible while door is in service . If the label on an
existing fire door has been removed or is no longer
legible, it is acceptable to verify the rating of the fire door
through other means acceptable to the AHJ such as an
inspection or certifications service that provides
acceptable documentation.
Remove paint from fire resistance rating label on fire door
frame in stairways per Fire Marshal.
16 Immediately Remove patrician walls installed without
permits and causing obstructions to fire sprinkler
coverage and exits.
17 Repair egress light in 8th floor hall by west stair.
18 Repair egress light by room 812
19 Room 812
A. Replace fire sprinkler head with paint in rest room.
B. Repair/Replace smoke detector
C. corridor door must completely self close and latch.
20 Room 822
Replace missing lamps in sockets
21 Repair permanent regular light between floors 8 and 7 in
East stairway. Must provide one foot candle of light
minimum at all times.
22 Repair egress light by room 723
Ref# Code Violation &Location Corrected
23 Room 721
A. Repair smoke detector hanging from ceiling
B. Reduce mattress storage to a maximum of 6 feet
above floor level.
• 24 Room 715
Repair smoke seal around top of door with approved UL
material .
25 Room 714
Replace missing smoke detector.
26 Room 711
Replace missing lamps in sockets
Bathroom under construction
27 Room 708
Replace missing smoke detector
28 Rooms 706,708,707,709
Replace missing lamps in sockets, repair exhaust fan
29 Room 705
A. Door must completely self-close and latch
B. Properly contain exposed wiring in listed box
C. Replace missing lamps in sockets
30 Repair egress light in lobby by 701
31 Rooms 607/609:
Replace missing smoke detectors
Replace missing bulbs in sockets.
32 Electric Closet by room 612:
A, Transformer must plug directly into permanent wall
outlet,
B. Replace missing cover on transformer
33 Room 615:
A. Replace missing smoke detector
B. room under construction
34 Room 617/618:
A. Door must completely self-close and latch.
B. Replace missing lamps in sockets.
C. Properly contain exposed wiring.
35 Room 624
Replace missing painted fire sprinkler head by RR.
36 Room 519
Replace smoke detector
37 Room 515
Install smoke seal around door with UL listed smoke seal
installed according to manufacturers recommendations.
38 Room 512:
A. Door must completely self-close and latch.
B. Replace missing lamps in sockets.
39 Room 510
A. Door must completely self-close and latch.
B. Replace missing lamps in sockets
Ref# Code Violation &Location Corrected
40 Room 509
A. replace missing lamps in sockets
B. Replace smoke detector
C.Properly contain exposed wiring.
41 Repair/replace exit light by room 503
42 Replace smoke detector with paint in room 502
43 Replace missing escutcheon on sprinkler head in storag
room by west stairs on 4th floor.
44 Repair/replace emergency egress light 4th floor lobby.
45 Rooms 401,402
A. replace missing lamps in sockets, bath fan
46 Room 405
A. Door must completely self-close and latch
B. repair bath fan
47 Room 412
Install smoke seal around door with UL listed smoke seal
installed according to manufacturers recommendations
48 Room 419
A.door must completely self-close and latch
B. repair bath fan
C. Properly clean loaded fire sprinkler head
49 Room 418 and 422
A. replace smoke detector
50 Room 424:
Replace missing lamps in sockets and bath fan
51 2013 NFPA 13 8.16.4 Protection of Piping
8.16.4.1 Protection of Piping from freezing
8.16.4.1.3 Where above ground water-filled supply pipes,
risers, system risers or feed mains pass through open
areas, cold rooms, passageways or other areas exposed
to temperatures below 40 degrees Fahrenheit the pipe
shall be permitted to be protected against freezing by
insulating coverings,frost-poof casings or other means of
maintains a minimum temperature between 40 deg. F.
and 120 deg. F.
Provide permanent heat solution to maintain a minimum
of 40 deg. F. at all times in all fire sprinkler areas. On
November 7, some room temps were at 42 degrees F.
52 Replace smoke detector room 325
53 Room 323:
A. door must completely self-close and latch
B. Properly contain exposed wires
C. replace missing lamps in sockets and bath fan
54 Room 320
A. replace fire sprinkler head with paint on it
B.clean loaded fire sprinkler head
C. replace missing lamps in sockets and bath fan
55 Room 318
Replace fire sprinkler head with paint on it
Ref# Code Violation &Location Corrected
56 Room 317
A. Reduce storage of mattresses to a maximum of 6 feet
above floor level
B. Replace missing lamps in sockets and bath fans.
57 Electric room by 314;
A. Circuit protected power taps not allowed to daisy
chain. Each must plug directly into wall outlet
B. Remove extension cord running under door and down
hall, down 3 stories to lobby.
58 Room 313
A. replace missing smoke detectors.
59 Room 312
A. Door must completely self-close and latch.
B. replace missing lamps in sockets and bath fan.
60 Room 311 and 309
A. Door must completely self-close and latch.
B. Replace missing lamps in sockets and bath fan.
61 Room 308
A. replace painted fire sprinkler head
B. properly clean loaded fire sprinkler head.
62 Room 304
A. Door must completely self-close and latch
B. replace missing lamps in sockets
C. properly contain exposed wiring
D. room under construction.
63 Room 305
A. Door must completely self-close and latch.
B. replace missing lamps in sockets and bath fan
64 Room 301
A. Door must completely self-close and latch.
B. repair bath fan
65 Repair hole in wall in 3rd floor hall by west stairs.
66 Repair egress light between 4thand 3rd floors in west
stairway.
67 Room 202:
A. Replace smoke detector
B. Replace missing ceiling to original fire resistant
construction in restroom
C. Properly contain exposed wiring
D. door must completely self-close and latch.
68 Room 204
A. Repair missing ceiling to original fire resistant
construction in restroom.
B. Replace missing lamps in sockets and bath fan
C. Reduce mattress storage to a maximum of 6 feet
above floor.
D.
69 Room 207
A. Properly contain exposed wiring approved box
B. Properly clean loaded fire sprinkler head.
Ref# Code Violation&Location Corrected
70 Room 209
A. Properly clean loaded fire sprinkler head
B. repair bath fan
71 Room 208
A. Replace smoke detector
B. Door must completely self-close and latch
C. replace missing lamps in sockets.
72 Room 213
Replace missing ceiling to original fire resistant
construction in restroom
73 Room 210
A. Replace smoke detector
B. Replace painted fire sprinkler escutcheon in rest room
74 Room 212
A. Replace smoke detector
B. Repair sheet rock wall to original fire resistant
construction.
C. Door must completely self-close and latch.
75 Room 215
A. Replace painted fire sprinkler head
B. Replace painted smoke detector.
C. Properly clean loaded fire sprinkler head.
76 Room 214
A. Replace smoke detector
B. Replace lamps in missing sockets.
77 Room 219
A. Door must completely self-close and latch
B. Properly clean loaded fire sprinkler head
C. Repair bath fan
78 Room 218
A. Replace smoke detector
B. Reduce mattress storage to a maximum of 6 feet
above floor.
79 Room 225
A. Properly clean loaded fire sprinkler head
B. Repair bath fan.
80 Room 214
Replace painted escutcheon by vanity.
81 Cedar Room
A. Replace missing ceiling tile
B. Repair egress light.
82 Repair egress light in Wapsi room.
83 Replace missing ceiling tiles in closet across from 1st
floor rest rooms.
84 Repair egress light outside Wapsi room
85 Repair egress light in Black Hawk room
Ref# Code Violation &Location Corrected
86 Red Coral Room
A. Properly clean loaded fire sprinkler head
B. Replace missing ceiling tile in closet.
C. Remove keyed lock from exit door immediately.
87 Replace missing ceiling tile in bar area.
88 Replace ceiling tile in closet by kitchen
89 Replace ceiling tile in kitchen.
90 Remove extension cord in walk in freezer
91 Verify fire sprinkler coverage for restaurant dining area.
92 Replace missing ceiling tile
A. In pool hallway
B. in gym
C. pool
93 Replace entire ceiling system in basement as noted in
item number 7.
94 Repair egress light in maintenance area.
95 Replace fire rated ceiling in main electric room
96 Repair smoke detector hanging by wires in Marco's office.
97 Provide a minimum of 1 foot candle of light at all times in
corridors.At this time there are no lights on 2,3rd, and
4th floors. Obtain proper permits and inspections for all
electrical repairs.
98 904.11.6.2 Provide current semi-annual kitchen hood fire
suppression system inspection/testing with all deficiencies
corrected by a contractor certified to work in the State of
Iowa
Comments:
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00 -Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Alarm
Comment Hawkeye Fire Alarm 4/28/16
Inspection Fee $ 600.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* S 610.00
Received By Don Schlinger
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection Date Time