City of Waterloo
Com rcial Fire Inspection Report
Inspection Number 1904
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Brock Weliver
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)883-1615
Email: Brock.Weliver@waterloo-ia.org
File Upload
Address* 214 Washington St.
Business name Bridges Senior Lifestyle Living
Inspection Date* 11/13/2018
Proprietor Ben Gardner
Business Phone 319-233-1133
Email* bgardner@bridgessl.com
Email 2
Property Owner
Emergency Contact Ben Gardner
Information
Phone 319-290-2535/Cell
Violations
Ref# CODE Violation &Location Corrected
1 2015 IFC Building Services and Systems Section 604 Emergency
Power Systems
604.5 Operational inspection and testing. Emergency power
systems, including all appurtenant components, shall be inspected
and tested under load in accordance with NFPA 110 and NFPA
111.
*Provide annual service reports for the generator
*36 month load test is due
Ref# CODE Violation &Location Corrected
2 2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.4.3 Installation. Relocatable power tap cords shall not extend
through walls, ceilings,floors, under doors or floor coverings, or be
subject to environmental or physical damage.
*Power tap was found suspended by it cord during inspection.
Power tap was located in the Salon Room
*Corrective action, place power tap securely on the floor or similar
horizontal surface or mount the power tap to a wall or similar
secure vertical surface.
3 2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.7 Appliances. Electrical appliances and fixtures shall be tested
and listed in published reports of inspected electrical equipment by
an approved agency and installed and maintained in accordance
with all instructions included as part of such listing.
*Freezer, ice cream freezer, in the kitchen area was found to be
plugged into a power tap
*Larger appliances like refrigerator,freezers, microwaves are to be
plugged directly into outlets
*Corrective action, plug freezer directly into an approved outlet
4 2015 IFC Building Services and Systems Section 605 Electrical
Equipment,Wiring and Hazards
605.10.1 Listed and labeled. Only listed and labeled portable,
electric space heaters shall be used.
2015 IFC Building Services and Systems Section 605 Electrical
Equipment, Wiring and Hazards
605.10.2 Power supply. Portable, electric space heaters shall be
plugged directly into an approved receptacle.
2015 IFC Building Services and Systems Section 605 Electrical
Equipment, Wiring and Hazards
605.10.3 Extension cords. Portable,electric space heaters shall
not be plugged into extension cords.
2015 IFC Building Services and Systems Section 605 Electrical
Equipment, Wiring and Hazards
605.10.4 Prohibited areas. Portable, electric space heaters shall
not be operated within 3 feet of any combustible materials.
Portable, electric space heaters shall be operated only in locations
for which they are listed.
*Space heater was found in the Salon Room during inspection
*Corrective action, remove space heater OR meet all of the criteria
listed above.The space heater would need to be rated for
commercial use with documentation.
Ref# CODE Violation &Location Corrected
5 2015 IFC Fire and Smoke Protection Features Section 703 Fire-
Resistance-Rated Construction
703.2.3 Door operation. Swinging fire doors shall close from the
full-open position and latch automatically. The door closer shall
exert enough force to close and latch the door from any partially
open position.
• *Fire doors were found to not fully close and latch when inspected,
these doors were the elevator fire doors on floors 3 through 11
*Corrective action, adjust doors so that they fully close and latch
6 2015 IFC Fire Protection Systems Section 901 General
901.4 Installation. Fire protection systems shall be maintained in
accordance with the original installation standards for that system.
Required systems shall be extended,altered or augmented as
necessary to maintain and continue protection where the building is
altered, remodeled or added to.Alterations to fire protection
systems shall be done in accordance with applicable standards.
*Fire door on 1st floor west stairway was missing a portion of its
smoke seal
*Corrective action, repair/replace smoke seal
*Ceiling in the pool mechanical room had holes in the drywall
around the sprinkler deflector head
*Corrective action, repair/replace drywall
7 2015 lFC Means of Egress Section 1010 Doors, Gates and
Turnstiles
1010.1.3 Door opening force. The force for pushing or pulling open
interior swinging egress doors, other than fire doors, shall not
exceed 5 pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that hold
the door in a closed position. For other swinging doors, as well as
sliding and folding doors,the door latch shall release when
subjected to a 15-pound(67 N)force.The door shall be set in
motion when subjected to a 30-pound (133 N)force. The door shall
swing to a full-open position when subjected to a 15-pound(67 N)
force.
*Marked Exit door in the small/private dining room was unable to
be opened when tested.
*Corrective action, repair/replace door so that it is able to be used
in case of emergency
8 2015 IFC Means of Egress Section 1031 Maintenance of the
Means of Egress
1031.2 Reliability. Required exit accesses,exits and exit discharges
shall be continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress
is occupied.An exit or exit passageway shall not be used for any
purpose that interferes with a means of egress.
*Marked Exit door in the main dining room area was found to have
a table and chairs in front of it.
*Corrective action, ensure that a Egress path approximately the
same size/width of the door or larger is maintained at all times to
allow full and instant use of the Exit door in case of emergency.
Comments: Inspection on 11-13-2018 was for the common areas of the building, offices,
corridors, mechanical rooms,and kitchen areas. Occupant rooms were not
inspected during this inspection.
If violations noted during the inspection are not corrected by the given re-inspection date, additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Black Hawk Sprinkler, 10-4-2018
Reports Annual Fire Alarm
Comment Hawkeye Communication, 10-4-2018
Reports Annual Generator Service
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
Reports Annual Generator Load Test
Comment Please provide current report, report may be emailed to the email address above
If testing, inspection or servicing is due, please arrange to have it performed
Reports Semi-Annual Kitchen hood Cleaning for all Hoods
Comment AKA, scheduled for 11-26-2018, last performed 5-2018
Reports Semi-Annual Kitchen hood Fire Suppression for all Hoods
Comment Proshield, 11-1-2018
Reports Fire Extinguisher Service
Comment Proshield, 11-1-2018
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 80.00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload (for long
inspections)
Reinspection
Re-inspection# Date Time
12/11/2018