COMMERCIAL INSPECTION-2060 CROSSROADS BLVD- 1-22-18 I FOR BILLING INQUIRY: (319)291-4323
LDescription
Total Price J
INSPECTION 2,000
$70.00
OCCUPANCY FEE
$10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
9926 02/09/2018 I 03/15/2018
2018-00000173 $80.00
Less Prepayment $0.00
Total Due--> $80.00
City of Waterloo
Com rcial Fire Inspection Report
Inspection Number 1217
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Chris Ferguson
Waterloo Fire Rescue
425 E 3rd Street Waterloo. IA 50703
Phone(319)493-1025
Email: chris.ferguson@waterloo-ia.org
File Upload
Address* 2060 Crossroads Blvd
Business name Evenson's Hallmark
Inspection Date* 1/22/2018
Proprietor
Business Phone
Email* store5@evensonshmk.com
Email 2
Property Owner Crossroads Center
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation &Location Corrected
1 2015 IFC: Section 1031.4- Exit signs: Exit signs shall be installed
and maintained in accordance with Section 1013. None of the exit
signs functioned when the test button was pushed on the unit.
Emergency egress lights in the retail area also did not function
when tested. Corrective action: Provide repair/replacement as
necessary to ensure units will function when test button is pressed.
Ref# CODE Violation &Location Corrected
2 [Back Room Area]2015 IFC: Section 1031.2-Means of Egress
Reliability: Exits shall be maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency...Broken down cardboard boxes were found to be
stacked against the back room exit. Corrective action: remove any
storage even temporary from in front of any exit doors.
3 [Back Room Area]2015 IFC: Section 1031.4- Exit signs: Exit signs
shall be installed and maintained in accordance with Section 1013.
The exit sign above the back room exit door did not function when
test button was pressed. Corrective action: Provide
repair/replacement as necessary to ensure unit will function when
test button is pressed.
4 [Back Room Area]2015 IFC: Section 605.3-Working space and
clearance:A working space of not less than 30 inches in width, 36
inches in depth shall be provided in front of electrical service
equipment. Several electrical panels were found to have storage
located in front of the panels. Corrective action: Remove or reduce
storage in front of electrical panels to meet criteria as above.
5 [Back Room Area]2015 IFC: Section 605.1-Abatement of electrical
hazards:A ceiling mounted fluorescent light fixture showed signs of
malfunctioning previously. It may have a bad ballast within the
fixture. Replace light fixture as soon as possible and discontinue
use until replacement made.
6 [Back Room Mezzanine]2015 IFC: Section 605.3-Working space
and clearance:A working space of not less than 30 inches in width,
36 inches in depth shall be provided in front of electrical service
equipment. Several electrical panels were found to have storage
located in front of the panels. Corrective action: Remove or reduce
storage in front of electrical panels to meet criteria as above.
7 [Back Room Mezzanine]2015 IFC: Section 605.1-Abatement of
electrical hazards: Several ceiling light fixtures were found to have
open wiring hanging from the fixtures. Corrective action: Provide
corrective repair/replacement of any open wiring.
Comments: Please feel free to contact me with any questions or concerns you may have.
Please have above items corrected or a plan of correction in place prior to the re-
inspection date below to avoid further fees.Thank you for your time and
cooperation.
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports
Comment
Inspection Fee $ 80.00 /-\Q
Occupancy Fee $ 10.00
Re-inspection Fee $
A �
Total Fee* 00
Received By
AN INVOICE OF THIS CHARGE WILL FOLLOW. DO NOT PAY FROM THIS FORM.
File Upload(for long
inspections)
Reinspection
Re-inspection# Date Time
1 2/19/2018 10:30