COMMERCIAL INSPECTION- 905 FRANKLIN ST- 1-23-18
I FOR BILLING INQUIRY: (319)291-4323
I
LDescription
Total Price J
INSPECTION 2,000
OCCUPANCY FEE $70.00
$10.00
CUSTOMER# BILLING DATE DUE DATE
10918 I 02/09/2018 I 03/15/2018 I INVOICE# CHARGES
2018-00000168
$80.00
Less Prepayment $0.00
Total Due--÷ $80.00
City of Waterloo
Com rcial Fire Inspection'Report
Inspection Number 1227
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Chris Ferguson
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)493-1025
Email:chris.ferguson@waterloo-ia.org
File Upload
Address* 905 Franklin St.
Business name People's Clinic
Inspection Date* 1/23/2018
Proprietor People's Community Clinic
Business Phone 319-272-4300
Email* dadams@peoples-clinic.com
Email 2 dread@peoples-clinic.com
Property Owner
Emergency Contact
Information
Phone
Violations
Ref# CODE Violation &Location Corrected
1 2015 IFC: Section 703.2 Opening Protectives: Opening protectives
shall be maintained in an operative condition at all times. Several
fire rated doors in the 2nd floor conference room were found to be
wedged open. Several other doors were found to be wedged open
as well. Fire rated doors are self-closing and need to either remain
closed or be provided with a hold-open device that will allow them
to close when the fire alarm sounds.
2 2015 IFC:Section 605.1 Abatement of Electrical Hazards:2nd floor
conference kitchen area had a microwave plugged into a portable
power tap.This appliance should be plugged directly into a
permanent wall outlet. This violation was corrected on site.
Ref# CODE Violation &Location Corrected
3 2015 IFC: Section 901.6 Inspection,testing, and maintenance: Fire
extinguishing systems shall be maintained in an operative condition
at all times.A few dirty(loaded)sprinkler heads were found in the
dentistry area. Heads should be cleaned whenever they become
covered with dust, lint,etc.. Consult with your sprinkler contractor
for best practice to clean off heads.
4 2015 IFC: Section 605.4 Multiplug adapters: Multiplug adapters are
prohibited. Several multiplug adapters(3 outlet strip plugged into
one receptacle)were found in the emergency care area and Exam
Room#4.These adapters were removed by maintenance staff.
These violations were corrected on site.
Comments: At this time a re-inspection will not be scheduled. However, maintenance was
advised to work with staff to educate them to no longer use door wedges or
multiplug adapters. Please feel free to contact me with any questions or concerns.
A spot re-inspection may take place later in the year. Thank you for your time and
cooperation.
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
are as follows:
$100.00-First Re-inspection I$150.00-Second Re-inspection I$200-Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Black Hawk Sprinklers-05/2017 no deficiencies noted.
Reports Annual Fire Alarm
Comment Hawkeye Alarm-03/2017 no deficiencies noted.
Reports Fire Extinguisher Service
Comment Annual fire extinguisher servicing-Superior 02/2017
Reports Fire Door
Comment Fire drop door servicing x8-Christie Door Co.,02/2017; no deficiencies noted.
Inspection Fee $ 70.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 80.00