COMMERCIAL INSPECTION-360 WESTFIELD AVE-2-1-18 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price J
INSPECTION 100,000 $600.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
22261 02/09/2018 03/15/2018 2018-00000157 $610.00
Less Prepayment $0.00
Total Due- $610.00
City of Waterloo
Fire Inspection Report
Commercialr.
p
Inspection Number 1248
Prior Inspection Fill this field if it is available, it will auto-fill business name and address.
Number
Inspector* Chris Ferguson
Waterloo Fire Rescue
425 E 3rd Street Waterloo, IA 50703
Phone(319)493-1025
Email: chris.ferguson@waterloo-ia.org
File Upload
Address* 360 Westfield
Business name Techworks-TechOne
Inspection Date* 2/1/2018
Proprietor Techworks
Business Phone 319-232-1156
Email* WJames@cedarvalleyalliance.com
Email 2
Property Owner
Emergency Contact
Information
Phone
Violations
CODE Violation &Location
Corrected
Ref#
1 2015 IFC: Section 1104.5 Illumination Emergency Power-All egress
lighting found on 6th floor did not illuminate when test button was
pushed. Corrective Action: provide corrective action so that egress
lights illuminate when test button is pressed.
2 2015 IFC:Section 1104.3 Exit Sign Illumination- Exit signs shall be
internally or externally illuminated. Exit sign found above the south
exit stair tower door on the 6th floor did not illuminate. Provide
corrective action to ensure exit sign illuminates.
Ref#
CODE Violation &Location Corrected
3
Combustible storage located on 5th floor-foam products. Please
remove foam products currently stored on 5th floor in accordance
with agreement regarding sprinkler coverage.
4 2015 IFC: Section 1104.3 Exit Sign Illumination: Exit signs shall be
internally or externally illuminated. Exit sign found above the north
stair tower door on the 3rd floor did not illuminate. Provide
corrective action to ensure exit sign illuminates.
5 2015 IFC:Section 703.2 Opening Protectives: Fire doors and
smoke barrier doors shall not be blocked or obstructed...Fire doors
in the 3rd floor elevator area were found to be blocked open.
Doors were signed to remain closed at all times. Provide corrective
action so that doors remain closed or will close upon activation of
fire alarm.
6 2015 IFC: Section 703.2.3 Door operation: Fire doors shall
close...and latch automatically. Fire doors on 3rd floor leading into
the"Maker's Space"did not close and latch. Please provide
corrective repair.
7 2015 IFC: Section 703.2.3 Door operation: Fire doors shall
close...and latch automatically. Fire doors near 2nd floor elevator
lobby did not close and latch. No striker plate was present for door
to latch into. Please provide corrective repair.
8 2015 IFC: Section 703.2.3 Door operation: Fire doors shall
close...and latch automatically. Fire doors on 2nd floor boiler room
did not close and latch. Please provide corrective repair
9 2015 IFC: Section 901.6 Inspection,testing and maintenance- Fire
detection and alarms...shall be maintained in an operative
condition at all times. Smoke detector in the 2nd floor elevator
lobby was found to be covered. Corrective action: remove cover
and ensure detector is functional.
10 2015 IFC: Section 1031 Maintenance of the means of egress-
Egress light was found on floor, fallen from wall in the north half of
the first floor. Replace light and ensure it is operating.
11 2015 IFC:Section 901.4 Installation- Fire protection systems shall
be maintained in accordance with the installation standards for that
system. Sprinkler piping was found to have old wiring still attached
to it in the 2nd floor elevator lobby. Please remove anything
attached to sprinkler piping that is not related to the operation of
the sprinkler system. (Per Simplex Sprinkler Report)
12 2015 IFC: Section 703.1 Fire-resistance-rated construction-A
ceiling tile was found to be missing in Wes'Office. Corrective
action: replace ceiling tile in office.
13 2015 IFC: Section 906.2 Portable fire extinguisher general
requirements: Portable fire extinguishers shall be serviced
annually.The fire extinguisher next to the main sprinkler riser on
1st floor was found to be past due for annual inspection. Please
provide annual servicing of the extinguisher.
Comments: It is recommended that this property institute a monthly or bi-monthly egress light
and exit sign check program due to the number found to be inoperable. Spot
checking will occur during re-inspection. Feel free to contact me with any questions
or concerns you may have.Thank you for your time and cooperation.
If violations noted during the inspection are not corrected by the given re-inspection date,additional fees
•
are as follows:
$100.00 -First Re-inspection I$150.00-Second Re-inspection I$200 Third and subsequent Re-inspections
Reports
Reports Annual Fire Sprinkler
Comment Tyco-Simplex Grinnell-07/20/2017: See item 11 above.
Reports Annual Fire Alarm
Comment Tyco-Simplex Grinnell-01/16/2018: No deficiencies noted on report.
Inspection Fee $ 600.00
Occupancy Fee $ 10.00
Re-inspection Fee $
Total Fee* $ 610.00