HomeMy WebLinkAbout3205 KIPLING RD WATERLOO FIRE RESCUE '►vp INSPECTION REPORT , /P" SOUTHVIEW ESTATES,3205 KIPLING RD, WATERLOO IA 50701 `J►, DETAILS Inspection Date:08/17/2022 Inspection Type: Rental Inspection I Inspection Number:8353 1 Shift: N/A I Station: N/A I Unit: N/A I Lead Inspector:BARRY STRATTON j Other Inspectors: N/A j Fee:$150.00 �� /"4 cl� •STATUS CODE DESCRIPTION FAIL 1010.1.9-Door operations Except as specifically permitted by this section,egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Inspector: BARRY STRATTON-Comments:Front door hardware needs replaced. Door hardware needs replaced on sliding door. FAIL 1031.2-Reliability Required exit accesses,exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency where the building area served by the means of egress is occupied.An exit or exit passageway shall not be used for any purpose that interferes with a means of egress. Inspector:BARRY STRATTON-Comments:Door security hardware is needed for rear patio sliding door. FAIL 703.2-Opening protectives Opening protectives shall be maintained in an operative condition in accordance with NFPA 80.Where allowed by the fire code official,the application of field-applied labels associated with the maintenance of opening protectives shall follow the requirements of the approved third-party certification organization accredited for listing the opening protective. Fire doors and smoke barrier doors shall not be blocked or obstructed,or otherwise made inoperable,Fusible links shall be replaced promptly whenever fused or damaged.Fire door assemblies shall not be modified. Inspector: BARRY STRATTON-Comments: Page 1 of 6 STATUS CODE DESCRIPTION FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-B:C.2.Within 30 feet(9144 mm) of commercial cooking equipment.3. In areas where flammable or combustible liquids are stored, used or dispensed.4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1.6.Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. inspector: BARRY STRATTON-Comments: FAIL 907.2.11 -Single-and Listed single-and multiple-station smoke alarms complying with UL 217 shall be multiple-station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON-Comments:Need smoke detectors in each bedroom and outside bedrooms. FAIL 915.1 -General Carbon monoxide detection shall be installed in new buildings in accordance with Sections 915.1.1 through 915.6.Carbon monoxide detection shall be installed in existing buildings in accordance with Section 1103.9. Inspector: BARRY STRATTON-Comments:Need CO detectors outside of bedrooms. FAIL R1 - Unsafe Structures Is the structure found to he dangerous to the life, health, property or safety of either the public or occupants of the structure?(IPMC 108.1.1) Inspector:BARRY STRATTON-Comments:Water damage and mold FAIL R2-Unsafe Equipment Was the presence of unsafe equipment noted during the inspection?Equipment may include boilers,heating equipment, elevator, moving stairways,electrical wiring,and flammable liquid containers.(IPMC 108.1.2) Inspector:BARRY STRATTON-Comments:Water heater, debris/water under mobile home.Condensate running off furnace under trailer Page 2 of 6 STATUS CODE DESCRIPTION FAIL R3-Unfit for Human Is the structure found to be fit for human occupancy according to the code?(IPMC Occupancy 108.1.3) Inspector: BARRY STRATTON-Comments: 111.1.3 Structure unfit for human occupancy.A structure is unfit for human occupancy whenever the code official finds that such structure is unsafe, unlawful or,because of the degree to which the structure is in disrepair or lacks maintenance, is insanitary,vermin or rat infested, contains filth and contamination,or lacks ventilation,illumination,sanitary or heating facilities or other essential equipment required by this code,or because the location of the structure constitutes a hazard to the occupants of the structure or to the public.(Potential Mold)Still no mold mitigation specialist has been contacted to abate mold. FAIL R4- Exterior Property Areas is the exterior property area maintained in a clean,safe,and sanitary condition?This includes grading and drainage,sidewalks and driveways,weeds, and pest infestations.(IPMC 302) Inspector: BA.RRY STRATTON-Comments:Water under trailer FAIL R5- Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and sanitary state?(IPMC 304) inspector: BARRY STRATTON-Comments:Roof leaking. Rear decks on rear of trailer still have not been removed and replaced. Decking and railing rotten. FAIL R6-Interior Structure Has the interior of the structure and equipment inside been maintained in good repair,structurally sound,and in a sanitary condition?(IPMC 305) Inspector: BARRY STRATTON-Comments:Potential mold in back bedroom/bathroom. Mold mitigation specialist shall be obtained to test for the presence of mold.Water damaged material from water leak in back bedroom/bathroom,front bathroom ceiling,and front bedroom. Peeling and abraded paint in front bathroom and front bedroom on ceilings from water leak. Plumbing fixtures installed in back bedroom not installed to code. Need licensed contractor to do plumbing work.Terminate plumbing shut offs not hooked up. FAIL R6.A.-Interior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Unsafe Conditions inspector: BARRY STRATTON-Comments:Potential mold present fro eater leak inside trailer and under trailer FAIL R6.B.-Residential Heating Are dwellings provided with heating facilities capable of maintaining a m room temperature of 68F?(IPMC 602.2) Inspector: BARRY STRATTON-Comments: Duct work exposed on rear bedroom. Bath cabinets removed and not replaced as original design Page 3 of 6 6ENERAL NOTES BARRY STRATTON-08/17/2022 @ 12:47 304.7 Roofs and drainage.The roof and flashing shall be sound,tight and not have defects that admit rain. Roof drainage shall be adequate to prevent dampness or deterioration in the walls or interior portion of the structure. Roof drains,gutters and downspouts shall be maintained in good repair and free from obstructions. Roof water shall not be discharged in a manner that creates a public nuisance. BARRY STRATTON-08/17/2022 @ 12:47 304.10 Stairways,decks,porches and balconies. Every exterior stairway,deck,porch and balcony,and all appurtenances attached thereto,shall be maintained structurally sound, in good repair,with proper anchorage and capable of supporting the imposed loads. Rails and balusters on rear deck need repaired/replaced. BARRY STRATTON-08/17/2022 @ 12:47 304.18 Building security. Doors,windows or hatchways for dwelling units, room units or housekeeping units shall be provided with devices designed to provide security for the occupants and property within. BARRY STRATTON-08/17/2022 @ 12:48 305.3 Interior surfaces. Interior surfaces, including windows and doors,shall be maintained in good,clean and sanitary condition. Peeling,chipping,flaking or abraded paint shall be repaired,removed or covered.Cracked or loose plaster,decayed wood and other defective surface conditions shall be corrected. BA.RRY STRATTON-08/17/2022 @ 12:48 305.5 Handrails and guards. Every handrail and guard shall be firmly fastened and capable of supporting normally imposed loads and shall be maintained in good condition. BARRY STRATTON-08/17/2022 @ 12:48 504.1 General. Plumbing fixtures shall be properly installed and maintained in working order,and shall be kept free from obstructions,leaks and defects and be capable of performing the function for which such plumbing fixtures are designed. Plumbing fixtures shall be maintained in a safe, sanitary and functional condition.Tub in back bathroom is leaking. Kitchen faucet needs replaced.All plumbing work is required to be done by licensed contractors.Sink installed does not have proper venting. BARRY STRATTON-08/17/2022 @ 12:48 504.3 Plumbing system hazards.Where it is found that a plumbing system in a structure constitutes a hazard to the occupants or the structure by reason of inadequate service, inadequate venting, cross connection, backsiphonage, improper installation, deterioration or damage or for similar reasons,the code official shall require the defects to be corrected to eliminate the hazard.Water around and under trailer. BARRY STRATTON-08/17/2022 @ 12:48 505.3 Supply.The water supply system shall be installed and maintained to provide a supply of water to plumbing fixtures,devices and appurtenances in sufficient volume and at pressures adequate to enable the fixtures to function properly,safely,and free from defects and leaks. Page 4 of 6 GENERAL NOTES BARRY STRATTON-08/17/2022 @ 12:49 9-1 B-2 403.6 Mold Present In A Rental Unit.a.When mold is found to be visibly present in small amounts,it can be cleaned in a safe and sanitary manner. b.When mold is found in a rental unit and is determined to be a health risk,the building official may order that a clean air report be obtained from a mold specialist approved by the building official. Obtain the services of a specialist to mitigate potential mold spores. BARRY STRATTON-08/17/2022 @ 12:49 4-2-4:STAGNANT WATER:A.The city council may at any time,by resolution,order any piece of land or lot upon which water at any time becomes stagnant to be filled to such a height,or to be drained in such a manner,and within such time,as the city council in the resolution shall direct. B. It shall be the duty of the owner of a piece of land or lot, subject to subsection A of this section,or his agent,after service on him of a copy of the resolution,or after a publication of the resolution once a week for two(2) consecutive weeks in a newspaper of general circulation in the city,to comply with the directions of the notice within the time therein specified,and in case of failure to do the work, by the owner or agent, it may be done at the expense of the city and the amount of money expended therefor shall be a debt due the city from the owner of the property and shall also be a lien on the piece of land or lot from the time of the adoption of the resolution. C.The expense of filling or draining such piece of land or lot pursuant to subsection B of this section may be levied as a tax thereon.The levy shall be by resolution, and the tax shall be levied and collected in the manner provided for in the collection of other special taxes. D.Any person who shall fail to comply with the resolution of the city council requiring the drainage or filling of land within ten(10) days after notice of the resolution has been served on him or his agent,or within ten (10)days after the last publication of the notice in a newspaper of general circulation in the city,shall be deemed guilty of an offense,and upon conviction thereof shall be punished as provided in section 1-3-1 of this code.(Ord.4292,4-27-1998) BARRY STRATTON-08/17/2022 @ 12:50 9-4-4: DEFECTIVE WORK; UNSANITARY CONDITIONS:Whenever it shall come to the knowledge of the plumbing inspector that the plumbing in a building causes a nuisance or may cause disease,sickness,or otherwise becomes a hazard to health, it shall be the duty of said inspector to make an inspection of such plumbing and render a report to the proper party,setting forth the necessary repairs or alterations required to make such plumbing conform to this chapter.The inspector shall set a limit of time in which such repairs or alterations are to be made,and upon the refusal or neglect of the owner,agent, lessee or tenant to comply with said notice within the time stated, the plumbing inspector shall cause such repairs or alterations to be made and such nuisance abated and the expense of such work shall be taxed against such property and become a prior lien thereon;or the inspector may order the premises vacated and closed to further occupancy until such time as the required repairs or alterations have been made.(Ord. 5392,3-20-2017) BARRY STRATTON-08/17/2022 @ 12:51 9-4C-5:PERSONS AUTHORIZED AND REPORTING:A.Must Be Licensed: No person other than those holding a state plumbing contractor license or pipe layer's license issued by the city of Waterloo,shall not tap any water or sewer mains,nor install any private building sewer,water service,private sewage disposal plant or private water system; nor shall they make any connections,extension, replacement, removals or additions of any nature to the sanitary plumbing or water supply system or disconnect any fixture or change the sanitary or water pipe arrangement. i3 17/2v' _ Page 5 of 6 • . REINSPECTION DATE 09/22/2022 CONTACT SIGNATURE Southview Estates IL Signed on:08/17/2022 @ 12:51 INSPECTOR SIGNATURE BARRY STRATTON Signed on:08/17/2022 @ 12:51 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON barry.stratton@waterloo-ia.org (319)231-9147 nte on 03" Page 6 of 6