RENTAL INSPECTION-200 E ARLINGTON ST- 8-9-22 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price j
REINSPECTION FEE 2ND $150.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23 804 10/17/2022 11/20/2022 2023-00020274 $150.00
Less Prepayment $0.00
Total Due-› $150.00
City of Waterloo
pO Si o
WATERLOO FIRE RESCUE U
INSPECTION REPORT tL4 2 .,
200 E ARLINGTON ST, WATERLOO IA 50703 4440
DETAILS
Inspection Date:08/09/2022 I Inspection Type: Rental Inspection Inspection Number:8307 I Shift: N/A ! Station: N/A I
Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A I Fee:$150.00
Dind Islid
STATUS CODE DESCRIPTION
FAIL 1008.1 -Means of egress Illumination shall be provided in the means of egress in accordance with Section
illumination 1008.2. Under emergency power, means of egress illumination shall comply with
Section 1008.3.
Inspector: BARRY STRATTON-Comments: Egress lights still not working in portions of
building.
FAIL 703.2- Opening protectives Opening protectives shall be maintained in an operative condition in accordance with
NFPA 80.Where allowed by the fire code official,the application of field-applied labels
associated with the maintenance of opening protectives shall follow the
requirements of the approved third-party certification organization accredited for
listing the opening protective. Fire doors and smoke barrier doors shall not be
blocked or obstructed,or otherwise made inoperable. Fusible links shall be replaced
promptly whenever fused or damaged. Fire door assemblies shall not be modified.
Inspector: BARRY STRATTON-Comments:Fire doors
FAIL 901.6- Inspection,testing and Fire detection,alarm,and extinguishing systems, mechanical smoke exhaust
maintenance systems,and smoke and heat vents shall be maintained in an operative condition at
all times,and shall be replaced or repaired where defective. Nonrequired fire
protection systems and equipment shall be inspected,tested and maintained or
removed.
Inspector: BARRY STRATTON-Comments:Sprinkler system still has deficiencies that
need corrected. Missing escutcheons in some areas of building.
FAIL ' 01.6.1 -Standards Fire protection systems shall be inspected,tested and maintained in accordance with
the referenced standards listed in Table.
Inspector: BARRY STRATTON-Comments:
FAIL 901.6.2-Records Records of all system inspections,tests and maintenance required by the referenced
standards shall be maintained.
Inspector: BARRY STRATTON-Comments:
Pr rated or 03/09;202 .2 3L
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-B:C.2.Within 30 feet(9144 mm)
of commercial cooking equipment.3. In areas where flammable or combustible
liquids are stored, used or dispensed.4. On each floor of structures under
construction,except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1. 6.Special-hazard areas,
including but not limited to laboratories,computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON-Comments: Fire extinguisher still missing on 1st floor
by elevator.
FAIL R6- Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair,structurally sound,and in a sanitary condition?(IPMC 305)
Inspector: BARRY STRATTON-Comments:Water damage on 2nd floor to Gloria's
room.Water damage to ceiling in North stairway corridor.
FAIL R6.C.-Mechanical Egiupment Are mechanical appliances properly installed and maintained in good working
condition?(IPMC 603.1)
Inspector: BARRY STRATTON-Comments:Water heater is rotted out in mechanical
room and is leaking.
REINSPECTION DATE
09/13/2022
CONTACT SIGNATURE
Roosevelt Housing Partners LP L l \L
Signed on:08/09/2022 @ 12:29
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on:08/09/2022 @ 12:30
Printed on 03/09/2022 1:12:30
Page 2 of 3
QUESTIONS ABOUT YOUR INSPECTION?
BARRY5TRATTON
barry.stnyuon@wvatedoo'ia.org
(319)231'9147
Printed On 08109Y 2022 -'30
Page uoro