COMMERCIAL FIRE INSPECTION- 135 E. RIDGEWAY AVE FOR BILLING INQUIRY: (319)291-4323
08/04/26
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE ": INVOICE# CHARGES
•
24479 08/12/2026 09/16/2026 2027-00000069 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report 425E.3rd Street
•""'` Kwik Star-135 E Ridgeway AVE,BLDG 135 E Ridgeway Avenue,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type r ] Inspection Number
08104/2026 Annual Inspection(1Yr) O -! cf * 80 rrf) 18556
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
042 06 ® 28
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
08/31/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-08106/2026 @ 07:56
•$80 annual inspection fee
BRAD BALDWIN-08/06/2026 @ 07:56
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-08/06/2026 @ 07:56
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-08/06/2026 @ 07:56
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No et
Report completeded post post inspectionISE
Alicia 2025-store leader Date: BRAD BALDWIN 08/06/2026
CHECKLISTS
GENERATED ON 8/8/26, 8;03 AM 1 OF 4
Emergency Equipment
Status Code Description
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Carwash
in Section 1013,6.3.The system shall be capable of powering Comments:Provide documentation of testing exit signs(2)including
the required load for a duration of not less than 90 minutes. repairs if needed,Document shall be signed,dated and note that exit
signs are operating properly.Signs require magnetic testing,
inspector not able to test at this time.
Additional Codes
Stows Code Description
Fail 2305.2-Equipment maintenance and inspection.
Motor fuel-dispensing facility equipment shall be maintained Location:Gas pumps
in proper working order at all times in accordance with Comments:Necessary repairs shall be made to pumps out of service.
Sections 2305.2.1 through 2305.2.5. Pumps#19,20,&23 out of service on 814126
Fail 2305.2.2-Repairs and service.
The fire code official is authorized to require damaged or Location:Fuel pump#2-Diesel
unsafe containment and dispensing equipment to be repaired Comments:Repair or replace pump hosing that shows signs of
or serviced in an approved manner. leakage and cracking of outer hosing.
Fail 5703.5-Labeling and signage.
The fire code official is authorized to require warning signs Location:South exterior propane cabinet
for the purpose of identifying the hazards of storing or using Comments:Replace missing hazard identification signage.
flammable liquids.Signage for identification and warning
such as for the inherent hazard of flammable liquids or
smoking shall be provided in accordance with this chapter
and Sections 5003.5 and 5003.6.
Commercial Cooking Hood Suppression System
Status Code Description
Fail 606.3.3.1-Inspection.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen hood suppression
appurtenances shall be inspected at intervals specified in Comments:Provide required suppression system inspection report
Table 606.3.3.1 or as approved by the fire code official. with any deficiencies corrected.Contractor must upload report to
Inspections shall be completed by qualified individuals. Compliance Engine.Inspection was due as of 815126
GENERATED ON 8/8/26, 8:03 AM 2 OF 4
Portable Fire Extingusihers
Statics Code Description
Fail 908.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:Parking lot-South end near RidgewaylAir Station
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to extinguisher,last recorded
Exceptions:1.The distance of travel to reach an extinguisher service in 2024.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.